Alfanar Co.: Respon Sibilities Legend CSD

This site test report summarizes electrical testing performed on a digital power demand meter at the Dammam Housing 115/13.8KV Substation #1. The testing included current, voltage, frequency, power, reactive power, apparent power, power factor, maximum demand, and energy measurements. Test results were within specified limits of 0.2-1% depending on the measurement type.

Uploaded by

jayabal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views4 pages

Alfanar Co.: Respon Sibilities Legend CSD

This site test report summarizes electrical testing performed on a digital power demand meter at the Dammam Housing 115/13.8KV Substation #1. The testing included current, voltage, frequency, power, reactive power, apparent power, power factor, maximum demand, and energy measurements. Test results were within specified limits of 0.2-1% depending on the measurement type.

Uploaded by

jayabal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 4

Respon

sibilities SITE TEST REPORT Date :


Customer:
Legend Contractor’s name:
NG-SA
CSD ALFANAR CO.
Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :
DIGITAL POWER DEMAND METER 4400006262
Page 1 of 4
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

1. GENERAL DATA AND INFORMATION.

Panel No: Class

Make Scale

Serial No: VT Ratio

Model No: CT Ratio

ELECTRICAL TEST

1) CURRENT MEASUREMENT TEST. Limits: -0.2 to + 0.1%

Applied Meter Readings in Amps Errors %


secondary Expected
Current Amperes
(A) R Y B R Y B

0.25

0.5

0.75

1.0

TEST DATE: TEST EQUIPMENT CALIB.DATE & DETAIL

TESTING ENGINEER CSD- Engineer

Signature: ________________ Signature: ________________


Name : ________________ Name : ________________
SITE TEST REPORT Date :
Customer:
Contractor’s name:
NG-SA
ALFANAR CO.
Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :
DIGITAL POWER DEMAND METER 4400006262
Page 2 of 4
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

2) VOLTAGE MEASUREMENT TEST L-N. Limits: -0.2 to + 0.1%


Applied Meter Readings in KV Errors %
Secondary
Expected KV
Voltage in
Volts R Y B R Y B

3) VOLTAGE MEASUREMENT TEST L-L. Limits: -0.2 to + 0.1%

Applied Meter Readings in KV Errors %


secondary Expected KV
Voltage in Volts R Y B R Y B

4) FREQUENCY MEASUREMENT TEST. Limits: ± 0.5 %

INJECTED
METER READ OUT Error %
VOLTAGE in Volts FREQUENCY

TEST DATE: TEST EQUIPMENT CALIB.DATE & DETAIL

TESTING ENGINEER CSD- Engineer

Signature: ________________ Signature: ________________


Name : ________________ Name : ________________
SITE TEST REPORT Date :
Customer:
Contractor’s name:
NG-SA
ALFANAR CO.
Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :
DIGITAL POWER DEMAND METER 4400006262
Page 3 of 4
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

5) POWER MEASUREMENT TEST. Limits: ± 1%

Meter
Voltage in Volts Current in Amps Phase Angle Calculated MW reading in Error
MW

6) Reactive POWER MEASUREMENT TEST. Limits: -0.2 to + 0.1%

Voltage in Current in Meter reading in


Phase Angle Calculated MVAR Error
Volts Amps MVAR

7) Apparent POWER MEASUREMENT TEST. Limits: -0.2 to + 0.1%

Current in Calculated Meter reading


Voltage in Volts Error
Amps MVA in MVA

i) Power Factor Test:- Limits: ± 1%


TEST DATE: TEST EQUIPMENT CALIB.DATE & DETAIL

TESTING ENGINEER CSD- Engineer

Signature: ________________ Signature: ________________


Name : ________________ Name : ________________
SITE TEST REPORT Date :
Customer:
Contractor’s name:
NG-SA
ALFANAR CO.
Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :
DIGITAL POWER DEMAND METER 4400006262
Page 4 of 4
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

Meter
Voltage Current Angle Cos Ф % Error
Reading

j) Maximum Demand :- (t =5 min) Limits: -0.2 to + 0.1%

Meter
Voltage in Calculated
Current in Amps Phase Angle reading in Error%
Volts MW
MW

k) Energy Measurement:- (t = 5 min ) Limits: -0.2 to + 0.1%

Calculated Meter reading Error%


Voltage Current Phase
In Volts In Amps Angle MWH MVARH MWH MVARH MWH MVARH

TEST DATE: TEST EQUIPMENT CALIB.DATE & DETAIL

TESTING ENGINEER CSD- Engineer

Signature: ________________ Signature: ________________


Name : ________________ Name : ________________