0% found this document useful (0 votes)
56 views6 pages

Stairwell Pressurization Estimate For Summer: Deg R

1) The document estimates stairwell pressurization for a summer scenario and provides dimensions, temperatures, and airflow areas/rates. 2) Key results include an average pressure difference of 0.102 inches of water between the stairwell and building, and 1.36 inches of water between the stairwell and outdoors. 3) The estimated supply air CFM needed during summer is between 12,133 and 18,511 CFM.

Uploaded by

kaushik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views6 pages

Stairwell Pressurization Estimate For Summer: Deg R

1) The document estimates stairwell pressurization for a summer scenario and provides dimensions, temperatures, and airflow areas/rates. 2) Key results include an average pressure difference of 0.102 inches of water between the stairwell and building, and 1.36 inches of water between the stairwell and outdoors. 3) The estimated supply air CFM needed during summer is between 12,133 and 18,511 CFM.

Uploaded by

kaushik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

STAIRWELL PRESSURIZATION ESTIMATE FOR SUMMER

Stairwell Dimensions (length & width) (ft)


length ( A ) = 20
width ( B ) = 11

Number of floors (N) 24


Floor Height (ft) 11
Total Height (H) (ft) 264

Flow coefficient ( C ) 0.65


deg R
Outdoor temprature To (F) 106 566
Temperature in stairwell Ts (F) 95 555
Indoor temperature Tb (F) 75 535

staircase length in common with building Lsb (ft) 31.00


building to outdoor common length Lbo (ft) 23
staircase length in common with outdoor Lso (ft) 31.00

Different flow areas


Flow area (a) Low Average High
flow area for stairwell walls (asb )(sft) 0.000014 0.000110 0.000350
flow area for single door, Closed (a1) (sft) 0.08 0.16 0.24
flow area for double door, Closed (a2) (sft) 0.34 0.34 0.34
flow area for Building walls (ab ) (sft) 0.00035 0.00035 0.00035
flow area for Roof (ar) (sft) 0.000052 0.000052 0.000052

Asb = Flow area between the stairwell and building (in sft)
Calculate Asb
Wall leakage area = (H xLsb x asb), (sft) 0.114576 0.90024 2.8644
single closed doors leakge area =( N x a1) (sft) 1.92 3.84 5.76
{assuming per floor 1 closed door between stair and
building}

Asb= 2.035 4.740 8.624

Abo = Flow area between the building and outdoor (in sft)
Calculate Abo
Wall leakage area = (Hx Lbo x ab) (sft) 2.1252 2.1252 2.1252
double door leakage area = (1xa2), (sft) 0.34 0.34 0.34
{Assuming one double door at first floor }
Abo= 2.465 2.465 2.465

Asou = uniform flow area between the stairwell and outside (in sft)
Calculate Asou
Asou=Walls (Hx Lso x ab) (sft) 2.86 2.86 2.86
Aso1= leakage area of closed door at stair bottom, 0.08 0.16 0.24
(sft) (considering one door)

roof leakage area = (AxBXar) (sft) 0.0114 0.0114 0.0114

Roof access hatch ( sft) 0.24 0.24 0.24


Aso2 = 0.25 0.25 0.25

Low Average High


Mass flow from stairwell to building Msb (lb/s) 2.11 4.92 8.95
Mass flow from stairwell to outdoors Mso (lb/s) 10.82 10.82 10.82
Mass flow from exterior door at 1st floor Mso1 (lb/s) 0.31 0.61 0.92
Mass flow from roof Mso2 (lb/s) 0.94 0.94 0.94
Mass flow of supply air to stairwell, Mt (lb/s) 14.18 17.29 21.63

Density of air at To (lb/ft3) 0.0701

Supply Air CFM during Summer 12133 14798 18511


Temperature factor Ft -0.000248
Flow area factor Fr 13.24
Pressure difference from stairwell to the
building at stair top ,in. of H2O 0.10

Pressure difference from stairwell to the


building at stair bottom ,in. of H2O 0.105

Avg press difference,in. of H2O, 0.102

Pressure difference from stairwell to the


outdoors at stair bottom,in. of H2O 1.39

Pressure difference from stairwell to the


outdoors at stair top ,in. of H2O 1.324

Avg press difference,in. of H2O, 1.36

You might also like