Tech Specification VSD
Tech Specification VSD
for
Supply, Fabrication and installation of VSD
Type Screw Air Compressor
Technical Specification:
1 Introduction
Typical Scope includes: “Fabrication & Installation of Screw Air Compressor system for Process Plant. A fully
packaged compact variable speed drive (VSD), single stage, oil injected rotary screw air compressor
system is required at BARC for supply of compressed air for different instrumentation/valve applications.
Here, this compressor system means, it should include all components that are needed to suck air from
ambient up to the terminal point where compressed pure air (oil, moisture and dusts are removed as per
specifications of this document) is delivered, which can be taken by pipe line to different
applicationsthrough buffer tank. This compressor system should be designed for easy to install, simple to
operate and should deliver rated compressor performance. The enclosure should be designed to manage the
environment of the internal components and the cooling ventilation system with suitable fan, at the same
time it should, significantly, reduce the sound level emitted from the machine into the installation
environment. The complete package should be designed to be located on an adequate flat floor without any
special foundations and fixtures on the ground. The fully packaged compressor unit should have sufficient
leak proof components/elements to avoid air and oil leakage. The compressor should have high reliability
for uninterrupted operation for at least 6 months. It should have sufficient instruments & sensors for
monitoring and fault diagnosis and appropriate controls with interlocks for safe operations. This air
compressor system will be used for instrumentation air purpose. For pneumatic control of valves,
instrumentation air is required to have compressed air at 7.5 bar (gauge) pressure and 25 -45degrees
Celsius temperature with flow rate 55 to 300 CFM(cubic feet per minute) at 7.5bar(g)as nominal
requirement. At the outlet of the compressor system, delivered compressed air should be pure and
lubricating oil content in this compressed air should be less than 0.001 PPM (parts per million) by volume.
Detailed requirements and specifications are given below.
5. Single Stage or Double Stage Single stage coupled to internal magnetic motor of oil cooled
compression bearing.
6. Lubricating oil content in air at the ≤ 0.001 PPM By volume (Activated carbon bed may be used
end of compressor system with oil to achieve this. If this is used, a filter should be used at the
removal system. downstream of it to filtrate 10 micron or bigger size carbon
particles coming from this bed). Suitable oil removal system
shall be included.
7. Moisture content in terms of PDP ≤ PDP (pressure dew point) 5 0C.The inbuilt air dryer heat
in terminal point (end of exchanger system shall be included along with filter.
compressor system) discharge air. Automatic condensate /moisture drain valve system also be
included.
8. Air volume flow control or Part Variable Speed Drive / VFD (variable frequency Drive) (it
Load Control method should be able to vary flow at least down to 30% and on
higher side up to 100% of nominal flow rate).
9. Volume Flow rate in cfm (cubic 55 to 300 CFMand as per standard capacity of supplier
feet per minute) at suction
condition (atmospheric pressure
and temperature)
10. Shaft torque /power:Motor of 20 % more than standard requirement for the 100 % nominal
having suitable internal permanent compressed air delivery.SelectedMotor Kw/HP with
magnets preferred. specification shall be given with proposal.
11. Air Temperature at the Outlet of < ambient (Mumbai, atmospheric temperature should be taken
whole compressor unit at any time into account for designing the air coolers) which varies from
in the year 20 0 C to 420 C in Mumbai.
12. Type of delivery pipe end Bolted SS (stainless steel) flange type. Standard flanged end
connection to the application at the pipe with holes for bolting and counter mating flange should
outlet of whole unit be provided by the supplier.
14. Air receiver tank A Single vertical tank of 1000 litreswith following specs
should be supplied connecting two airdischarge of
twocompressor system (one is existing at site) along with
valving for isolation.
Design pressure-12.75 bar (g), working pressur-7.5 bar (g),
maximum tank height-2.5.m ,
Tank construction material: SS304L.
Pressure gauge and pressure relief valve with burst disc along
with burst pressure indicator should be provided. leak
tightness at any location: As per ASME design code/standard
15. Design, fabrication and tests ASME VIII Div-I standard. Design, fabrication and tests
code/standard document along with test record shall be submitted if order is
placed.
17. Noise level < 70db at a distance of 1 meter from the unit.
16. Instrumentation & control Necessary instrumentation and controls for all variable
parameter should have local display with control cabinet.
Three (potential free contacts for remote indication “PLC” for
machine status) shall be provided record parameters in main
control room of plant should give a list of instrumentations
and controls, with make, specifications included in the
supply. This should be also uploaded with quotations for
technical evaluations. Advance microprocessor based controls
will be preferred.
17. Safety and alarm system Necessary safety equipment and alarm provisions shall be
provided. Its list should be given by the supplier along with
quotations/proposals for technical evaluation.
18. Foundation requirement To support the buffer tank on the concrete floor it should have
provision of fixing with anchor-fastener. It should not require
special concrete flooring. Supplier must upload the weight
and dimensions of components/systems along with proposal
for technical evaluation. The available space in which two
compressors is to be installed is width: 1.5 m, length:2 M &
Height: 1.9 M.
19. Flow meter for acceptance test Supplier should provide calibrated flow meter in addition
with standard package to measure air volumetric or mass flow
rate during acceptance test. This should be included as part of
the supply and be integrated in piping by supplier.
20. Power supply available 415 V ± 10%, 50 Hz ± 5% , 3 phase, 5 wire (without back up)
for heavy loads and b) 230 V ± 1%, 50 Hz ± 1Hz , single
phase, 3 wire.
2. Measurement of pressure, temperature and volume flow rate of compressed air near final delivery point
(or terminal point) of the whole system
4. Local oil leaks will be checked visually. There should not be any visible oil leakage.
5. All results should conform to that specified by the supplier within +/- 10 % deviation.
6. On successful completion of site performance tests and reception of all specified documents, the
purchaser will issue a certificate of acceptance.
12. Electrical armoured copper cable FRLS, XLPE 3.5 core, 25 sq. mm. Laying & fitting between machine &
MCC panel.
13. Requirement of civil work, if any for the erection of the unit, to be mentioned in the quotation.
7. Other Requirements:
Safety feature should be incorporated for safety of operator and the machine.
Anti Vibration Mountings should be provided on the compressor frame for vibration isolation
from Screw element, Motor and Oil Separator Tank.
10.Submission of Offer:
1. Vendor should submit their offer on or before the tender due date. Before submission of offer,
vendor can do site visit. Incomplete / Partial offers will not be considered for evaluation of the
offer.
For site visit contact person: Name: K. P. Paradkar , HWD, Engg. Hall-8, Room No. F-3, Trombay,
BARC, Mumbai – 4000085, Off. Ph.: 25596428, Email: [email protected]
2. Vendors have to submit the following documents along with their offer:
i) Necessary Material Test Certificates and.
ii) Work experience certificates regarding the fabrication.
11.General Requirements:
1. The Vendor to whom this contract will be awarded will have to carry out certain formalities with BARC
Security department for the entry of their manpower inside the company premises. Contractor shall make
sure that each person being deployed for execution of the job at site should possess a valid PVC (Police
Verification Certificate) issued by Mumbai Police; Subsequently necessary photo passes will be issued to the
vendor’s personals by security department till the period of execution of the job.
2. The contractor has to sign “Industrial Safety Undertaking” before starting the job at BARC premises.
3. Vendor will be liable to compensate the workmen, in case of any accidents or injury at work site.
Technical Specification
Type Air Cooled
Compressor VSD
Capacity Screw Type
Pressure rating 55-300CFM
Drive Type Direct
Required Pressure 7.5 KG/CM ²(g) Pressure can be adjusted 4 -7 bar
Control Panel Microprocessor based / GRAPHICS monitoring system
Electrical Motor 37KW (50HP) Permanent Magnet Electric Motor Variable speed
drive along with Variable speed Starter (i. e. starting amps never
reaches to full load current at starting….starting torque)
Sound Level 69dB (A) +/- 3dB (A)
Air Filters Supply & Installation of HIGH EFFICIENCY coalescing filter,
40% less pressure drop then tandem filters. For Dust, Foreign
particles Removal, Nautilus design Coalescing Filter (Fibers Glass
Filter) UD 140+ suitable for above flow and remove Liquid water,
dust particles up to 0.001 Micron and aerosol to 0.0009mg/m3,
(0.001ppm)
Air Dryer Refrigerated type Air Dryer CFC free R410A
Quantity 1nos.
Air Receiver Tank AIR RECIVER of capacity 1M3 as per ASME STD and standard
fittings like pressure gauge, Make: Wika or equivalent with test
calibration certificate, size: 1/2’’ NPT threaded, siphon pipe SS304
with cock & coupling size:1/2’’NPT or 1”NPT threaded , safety
valve with test calibration certificate and auto drain valve. (For 10
kg/cm2)
Electronic Drain Valve Capacity 1M3 at 9kg/cm²
Drain Valves Auto Operated
Overall Size, Foundation 1mtr.(L) x 1 mtr.(W) x 100mm(H)