Model Answer For Second Mid Term
Model Answer For Second Mid Term
POC 400
PF = cos θ = = = 0.234 lagging
VOC ∗ IOC 8000 ∗ 0.214
The excitation admittance is
IOC 0.214 1 1
YE = VOC < − cos−1 PF = < − cos−1 0.234 = 0.0000063 − j0.0000261 = RC − j XM
8000
1 1
Therefore: RC = = 159kΩ; XM = = 38.3kΩ
0.0000063 0.0000261
VSC 489
ZSC = < cos −1 PF = < 78.7° = 38.4 + j192 Ω
ISC 2.5
Therefore: Req = 38.3 Ω; Xeq = 192Ω
(a) Find the equivalent circuit of this transformer referred to the high-voltage side.
(b) Find the equivalent circuit of this transformer referred to the low-voltage side.
(c) Calculate the full-load voltage regulation at 0.8 lagging power factor, 1.0 power
factor, and at 0.8 leading power factor.
(d) What is the efficiency of the transformer at full load with a power factor of 0.8
lagging?
Solution:
Solution: VT = 240 V, RA = 0.064Ω, RF = 93.6Ω
Pout 22380
Efficiency = × 100 = × 100 = 88.5
Pin Pin
22380∗100
Pin = = 25288 W
88.5
Pin 25288
The line current IL = = = 105.37 A
VT 240
VT 240
the field current IF = = = 2.564 A
RF 93.6
Therefore, at full load armature I2R losses are PA = I2ARA = (102.8)2*0.064 = 673.34 W
At full load field circuit I2R losses are Pf = I2FRF = (2.564)2*93.6 = 615.33 W
The output power Pout = Pin – PA – Pf – Prot - Pstray
Prot = 1366.45 W
Prot 1366.45
Percentage of Rotational losses = × 100 = × 100
Pin 25288
Rs + 0.064 = 1.334
Rs = 1.27Ω
n1 ∅2 0.9 ∅
(c) = =
n2 ∅1 ∅
n1 1150
n2 = = = 1277.77 rpm
0.9 0.9