0% found this document useful (0 votes)
209 views

Flow Monitoring MK96 For Flow Sensors MK96-LI01

The MK96-LI01 is a signal processor for connection to standard flow sensors. It has a 4-20mA analog output, adjustment via potentiometer, and 6 LEDs to display flow state. It operates on a 2-wire DC power supply between 19.2-28.8VDC with a maximum current consumption of 100mA. Signal processors process and display measured signals from insertion and inline sensors.

Uploaded by

chikkam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
209 views

Flow Monitoring MK96 For Flow Sensors MK96-LI01

The MK96-LI01 is a signal processor for connection to standard flow sensors. It has a 4-20mA analog output, adjustment via potentiometer, and 6 LEDs to display flow state. It operates on a 2-wire DC power supply between 19.2-28.8VDC with a maximum current consumption of 100mA. Signal processors process and display measured signals from insertion and inline sensors.

Uploaded by

chikkam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Flow monitoring

MK96 for flow sensors


MK96-LI01

■ For connection of a standard flow sen-


sor
■ Adjustment via potentiometer
■ 6 LEDs for display of the flow state
■ 2-wire DC, 19.2…28.8 VDC
■ 4…20 mA analog output

Wiring Diagram

Type designation MK96-LI01


Ident-No. 7525004

Functional principle
Ambient temperature -20…+60 °C
Signal processors not only supply insertion
Operating voltage 19.2…28.8 VDC and inline sensors with voltage, they also pro-
Current consumption ð 100 mA cess and display the measured signals. De-
Output function Analog output vices with MK96…, MS96… and MC96…
Current output 4…20 mA housing styles are available. The individual
Protection class IP20 housing styles are designed for different oper-
Protection class (terminals/housing) IP20 / IP40 ating voltages and feature various output and
supplementary functions. For intrinsically safe
Design Signal processor flow sensors it is required to use signal pro-
Dimensions 70 x 18 x 89 mm cessors with intrinsically safe control circuits
Housing material Polycarbonate/ABS
of the series MS96…Ex… and MC96…Ex… .
Electrical connection Terminal chamber

Flow state display LED chain, red (1x), yellow (1x), green (4x)
LED display red = 4 mA
yellow > 4 mA
1x green > 8 mA
2x green > 12 mA
3x green > 16 mA
4x green = 20 mA
Edition • 2019-02-08T14:04:19+01:00

1/1 TURCK Inc. ñ 3000 Campus Drive Minneapolis, MN 55441-2656 ñ Phone: 763-553-7300 ñ Application Support: 1-800-544-7769 ñ Fax 763-553-0708 ñ www.turck.com