Grounding in MV
Grounding in MV
System Grounding
1. System grounding
2. Equipment grounding
3. Transients in grounding systems
System grounding refers to the electrical connection between the phase conductors and
the ground and dictates the manner in which the neutral points of wye-connected trans-
formers and generators or artificially derived neutral systems through delta–wye or zig-
zag transformers are grounded.
Equipment grounding refers to the grounding of the exposed metallic parts of the elec-
trical equipment, which can become energized and create a potential to ground—say due
to breakdown of insulation or fault—and can be a potential safety hazard. In the ground-
ing grids for substations, the criteria of safety are limiting the step, touch, and transfer
potentials to safe limits, see Reference [1].
Transients in grounding systems occur under lightning impulse currents, and the
impulse response of the grounding grids must be studied.
In this volume, we will confine to system grounding.
Further aspects of grounding are as follows:
All of these aspects are not discussed. The grounding systems are also discussed in
Volume 1. There is some repletion of the concepts presented in Volume 1, which is carried over in
this chapter.
231
232 Power Systems Protective Relaying
XGO
Ungrounded 52
XGO
Solidly grounded 52
XGO 3RN
RN
Resistance grounded 52
XGO 3XN
XN
Reactance grounded 52
XGO 3XN
XN
Ground fault
52
neutralizer
FIGURE 7.1
Various methods of system grounding.
System Grounding 233
The coefficient of grounding (COG) is the ratio of ELg/ELL in percentage, where ELg is the
highest rms voltage on an unfaulted phase, at a selected location, during a fault effecting,
one or more phases to ground and ELL is the rms phase-to-phase power frequency voltage
obtained at that location with the fault removed. Solidly grounded systems are, generally,
characterized by COG of 80%. Approximately, a surge arrester with its rated voltage calcu-
lated on the basis of the system voltage multiplied by 0.8 can be applied. See Volume 1 for
further discussions and calculations of COG.
The utility systems at transmission, subtransmission, and distribution levels are solidly
grounded. The main reason for this is that on occurrence of a ground fault, enough ground
fault current should be available to selectively trip the faulty circuit.
The utility generators, connected in step-up configuration to a generator transformer,
are invariably high-resistance grounded. If a generator neutral is left ungrounded, there
is a possibility of generating high voltages through inductive–capacitive couplings.
Ferroresonance can also occur due to the presence of generator PTs.
The utility substations serving large chunks of power at high voltages for industrial plants
through delta–wye transformers have low-resistance grounded secondary wye windings.
The most common voltages of distributions for the industrial plants are 13.8 , 4.16, and 2.4 kV.
The low-voltage systems in industrial power distribution systems used to be solidly
grounded. However, this trend is changing and high-resistance grounding (HRG) is being
adopted.
The solidly grounded systems have an advantage of providing effective control of over-
voltages, which become impressed on or are self-generated in the power system by insu-
lation breakdowns and restriking faults. Yet, these give the highest arc fault current and
consequent damage and require immediate isolation of the faulty section. Single-line-to-
ground fault currents can be higher than the three-phase fault currents. These high mag-
nitudes of fault currents have a twofold effect:
Yet, some systems according to National Electric Code (NEC) must be solidly grounded.
These include systems below 120 V ac, control systems, lighting systems, and commercial
distributions. Also solidly grounded systems are required where three-phase four-wire
loads are required to be served.
The arc fault damage to the equipment for low-voltage 480 V systems has been investi-
gated using laboratory models [3]. Stanback reported that for single-phase 277 V arcing
fault tests using spacing of 1–4 in from bus bars to ground and for currents from 3000 to
26,000 A, the burning damage can be approximated by the following equation:
VD = K s (I )1.5t (in.)3 (7.2)
234 Power Systems Protective Relaying
where Ks is the burning rate of material in in.3/As1.5, VD is the acceptable damage to mate-
rial in in.3, I is the arc fault current, t is the duration of flow of fault current, and Ks depends
upon the type of material and is given by
The NEMA [4] assumes a practical limit for the ground fault protective devices, so that
where Ir is the rated current of the conductor, bus, disconnect, or circuit breaker to be
protected.
Combining these equations, we can write
VD = 250K s I r (7.5)
Example 7.1
As an example, consider a circuit of 4000 A. Then, the NEMA practical limit is 1.0 × 106
(A)1.5 s and the permissible damage to copper, from (7.5), is 0.72 in.3. To limit the arc fault
damage to this value, the maximum fault clearing time can be calculated. Consider that
the arc fault current is 20 kA. Then, the maximum fault clearing time including the relay
operating time and breaker interrupting time is 0.35 s. It is obvious that vaporizing
0.72 in.3 of copper on a ground fault which is cleared according to established standards
is still damaging to the operation of the equipment. A shutdown and repairs will be
needed after the fault incidence.
Due to high arc fault damage and interruption of processes, the solidly grounded
systems are not in much use in the industrial distribution systems. However, ac circuits
of less than 50 V and circuits of 50–1000 V for supplying premises wiring systems and
single-phase 120/240 V control circuits must be solidly grounded according to NEC [5].
Figure 7.2 shows a sustained arc fault current in a 3/16 in. gap in a 480 V three-phase
system [3]. Experimentally, an arc is established between phase c of the bus and ground,
and a current of 1100 A flows. After three-cycle phase a is involved and the arc current
for two-line to enclosure fault is 18,000 A, the arc energy equals 7790 kW cycles.
Approximately 70% of the faults in the electrical systems are line-to-ground faults.
Sometimes, these may be self-clearing and of transient nature (e.g., in over head (OH)
line systems) or may evolve into three-phase faults over a period of time.
Thus, the probability of a worker being subject to arc flash due to ground faults is
much higher. A footnote in NFPA 70E reads as follows:
High resistance grounding of low-voltage and 5 kV (nominal) systems, current limi-
tations, and specifications of covered bus within equipment are techniques available
to reduce the hazard of the system.
1-Varc
2-Is
3-Vc
4-Ia
5-Ib
6-Ic
1-387 V/IN
1-in.
2-8.7A/IN
3-431V/IN
4-31800A/IN
6-31750A/IN
FIGURE 7.2
Arcing fault in a 3/16 in. gap, 480 V three-phase system.
Another consideration is selective protective relaying for various systems, see Chapter 8.
It is documented that though the selective ground fault clearance is possible in a solidly
grounded low-voltage system, practically, compromises are made (see Chapter 8).
The insulation of the bus system impacts the arc transfer to other phases. With insulated
buses, the arcing fault can be expected to remain stationary at the point of fault and it can
easily burn down 480/277 V systems.
Thus, it becomes imperative that low-level ground faults are cleared quickly to prevent
conductor and equipment damage. As the current reduces, the time to clear a fault on
inverse characteristics relays will increase. The problem will be to precisely calculate the
ground fault current as the return path involves a number of factors. Lucks [7] lists the
following factors:
• Metallurgy of enclosure
• Size and type of ground conductor
• Corrosion on pressure contacts
• Rectification from dissimilar materials
• Mutual inductance
• Skin effect
• Phase to neutral voltage
• Earth conductivity
where Vln is the line-to-neutral voltage and Ic is the stray capacitance current of each phase
conductor. Figure 7.3 depicts transient voltage in percent of normal line-to-ground crest
voltage versus the resistor kW/charging capacitive kVA [10]. The transients are a minimum
when this ratio is unity. This leads to the requirement of accurately calculating the stray
capacitance currents in the system. These calculations for a high-resistance system are not
documented here. Cables, motors, transformers, OH lines, surge arresters, and genera-
tor windings have distributed stray capacitances to ground—all contribute to the stray
capacitance current. For the purpose of HRG, we can consider all these distributed stray
capacitances lumped together. Surge capacitors connected line-to-ground must be consid-
ered in the calculations. The authors of [11–13] provide charging current (stray capacitance
current) data of electrical system components. Once the system stray capacitance is deter-
mined, then the charging current per phase, Ic, is given by
Vln
Ic = (7.7)
X co
where Xco is the capacitive reactance of each phase, stray capacitance considered lumped
together.
400
normal line -to-ground crest voltage
320
Transient voltage in percent of
Unfaulted phases
240
Neutral to ground
160
Faulted phase
80
0
0 0.4 0.8 1.0 1.2 1.6 2.0
Ratio: resistor KW/charging KVA
FIGURE 7.3
Overvoltage versus ratio of resistor kW/charging kVA. (From Westinghouse, Transmission and Distribution
Handbook, Westinghouse, East Pittsburg, PA, 1964.)
238 Power Systems Protective Relaying
Example 7.2
An HRG system for a wye-connected neutral of a 13.8 kV-0.48 transformer is shown
in Figure 7.4a. This shows that the stray capacitance current per phase of all the dis-
tribution system connected to the secondary of the transformer is 0.21 A per phase.
In a three-phase system, the three phases are symmetrical (though not perfectly) with
respect to each other; we can assume that the charging currents of all three phases are
equal. Figure 7.4b shows that under no-fault condition, the vector sum of three capaci-
tance currents is zero, as these are 90° displaced with respect to each voltage vector and
therefore 120° displaced with respect to each other:
Ia + Ib + Ic = 0 (7.8)
Thus, the grounded neutral does not carry any current and the neutral of the system is
held at the ground potential; no capacitance current flows into the ground or in the neutral-
connected grounding resistor.
On occurrence of a ground fault, say in phase a, the situation is depicted in Figure 7.4c
and d. The capacitance of faulted a phase is short circuited to ground, and this phase
does not contribute to any capacitance current. The faulted phase, assuming zero fault
resistance, is at the ground potential (see Figure 7.4d) and the other two phases have
line-to-line voltages with respect to ground. Therefore, the capacitance current of the
(a) (b)
B Vbc C
B C
Vb Vc
Ic
Ic Ib Ground
0.21 A Ia
0.21 A
Vab Ib Va Vac
Grounding
resistor 0
Phase rotation ABC
A
A
0.21 A Ia
Ground
0.21 A
(c) (d) (e)
B C Ic
B C Ib
Ic Ib 0.63A
Ig
0.364 A
0.364 A
Ir
A
1A Ir 1A
A
Ig
Ground
FIGURE 7.4
(a and b) The stray capacitance currents and voltages in a wye-connected HRG system under no-fault condi-
tions, (c) the flow of capacitance and ground currents, phase a faulted to ground, (d) voltages to ground, phase a
grounded, and (e) phasor diagram of summation of capacitive and resistance components of current.
System Grounding 239
B C
Voltage vectors
with varying neutral shift N
N1
A Ground
N3
FIGURE 7.5
The neutral shift in high-resistance grounded systems, depending on the fault resistance.
unfaulted phases b and c increases proportional to the voltage, that is, 3 × 0.21 = 0.365 A.
Moreover, this current in phase b and c reverses, flows through the transformer wind-
ings, and sums up in the transformer winding of phase a. Figure 7.4e shows that this
vector sum of the capacitance currents in phases b and c is equal to 0.63 A. This is con-
ceptually important. Note that no capacitance current returns to the faulted point through the
grounding resistor, also see Chapter 8.
Now consider that the ground current through the grounding resistor is limited to
1 A only. This is acceptable according to Equation 7.6 as the total stray capacitance current
is 0.63 A. This resistor ground current also flows through transformer phase winding a
to the fault (Figure 7.4e) and the total ground fault current is I g = 12 + 0.632 = 1.182 A.
The above analysis assumes a full neutral shift, ignores the fault impedance, and
assumes that the ground grid resistance and the system zero-sequence impedances are
zero. Practically, the neutral shift will vary, see Figure 7.5.
7.5 Ungrounded Systems
In an ungrounded system, there is no intentional connection to ground except through
potential transformers or metering devices of high impedance. In reality, an ungrounded
system is coupled to ground through distributed phase capacitances. It is difficult to assign
X0/X1 and R0/X0 values for ungrounded systems. The ratio X0/X1 is negative and may vary
from low to high values and COG may approach 120%. These systems provide no effec-
tive control of transient and steady-state voltages above ground. A possibility of resonance
with high voltage generation, approaching five times or more of the system voltage, exists
for values of X0/X1 between 0 and −40. For the first phase-to-ground fault, the continuity
of operations can be sustained, though unfaulted phases have 3 times the normal line-
to-ground voltage. All unremoved faults, thus, put greater than normal voltage on system
insulation, and an increased level of conductor and motor insulation may be required. The
grounding practices in the industry are withdrawing from this method of grounding.
If an inductor of certain size gets connected to ground, then the possibility of high volt-
ages exist, as the overvoltage is given by:
XL
Vov = Vt (7.9)
(X co / 3) − X L
240 Power Systems Protective Relaying
Broken line
grounded
Blown
fuse
Inductive winding
grounded
FIGURE 7.6
Connections of an inductance to ground for faults in ungrounded systems.
where Vt is the applied terminal voltage and XL is the inductance of the grounded induc-
tor. Figure 7.6 shows three possible cases of a high inductance that may get connected to a
phase, and give rise to resonant voltages.
1. The coil of a motor starter may be inadvertently connected between phase and
ground due to a ground fault.
2. A fuse can operate in one phase due to a ground fault, which connects reactances
of the other two phases in parallel between phases and ground.
3. A broken conductor on the load side of the transformer connects reactances of two
phases in parallel between phase and ground.
The phenomena of arcing grounds and resulting overvoltages which may escalate to five
to six times the normal rated voltage can be explained with reference to Figure 7.7. It is
somewhat similar to restrikes in circuit breakers discussed in Volume 1. Intermittent
ground faults can give rise to these phenomena.
Figure 7.7a shows normal voltage vectors rotating counterclockwise. Consider that phase
a is grounded, see Figure 7.7b. The current in a capacitor is zero when the voltage is at its
peak and therefore at the instant shown in Figure 7.7b, the capacitance is charged to the
line voltage and the current is zero; thus, the arc tends to extinguish. During the next half
cycle, as the voltage vectors rotate, the phase a charges from zero (at the neutral point)
to twice the line voltage, which is denoted by dotted lines. This value of line-to-ground
potential of phase a may be sufficient to break down the gap in the ground fault circuit,
which got extinguished a half cycle before. Thus, a pulse current flows and the phase a
voltage may swing between plus and minus two times the rated voltage at a frequency of
20–100 times the fundamental, due to the presence of reactance in the circuit. If there were
a solid metallic connection between the phase a and the ground, it would leave the phase
System Grounding 241
V΄΄΄b V΄΄΄c
(a) (b)
V΄΄΄a
½ Cycle
Vb Vc V΄a
Vb Vc
(c)
Va V΄΄b V΄΄c
V΄΄a
FIGURE 7.7
(a–c) Illustration of arcing faults in ungrounded systems and consequent escalation of voltages.
a conductor at ground potential. Associated with the transitory oscillation of the voltage,
there will be a corresponding oscillatory charge current. This transient charging current
or restrike current will again reach zero when the system voltage angle is at its maximum
excursion in the negative direction, see the lower part of Figure 7.7c. In the next half cycle
as the voltage vectors rotate further, the phase a voltage will escalate from –2 to –4, as
indicated in the lower part of Figure 7.7c. This increased voltage across the gap, which may
again result in a restrike.
7.6 Reactance Grounding
In reactance grounding, a reactor is connected between the system neutral and the ground;
the magnitude of the ground fault current that will flow depends upon the size of the reac-
tor. The ground fault current should be at least 25% and preferably 60% of the three-phase
fault current to prevent serious transient overvoltages (X0 < 10X1). This current is consid-
erably higher than that in a resistance grounded system and the reactance grounding is
not an alternative to resistance grounding. The system is generally used for grounding of
242 Power Systems Protective Relaying
small generators, so that the generator ground fault current does not exceed three-phase
fault current and three-phase four-wire loads could be served. Reactance grounded sys-
tems are not common in the United States.
Up to around the 1940s, the utility left their generators ungrounded to limit the internal
ground fault currents in the generator to very low values. However, when these genera-
tors were connected to transmission lines many insulation failures occurred, due to high-
voltage transients as discussed in ungrounded systems.
The next step was to ground the generator neutral through primary of a potential
transformer, the secondary connected to a voltage relay—the actuation of voltage relay
will trip the generator. Practically, it increased the generator failures due to arcing
grounds.
Examine circuit of a generator shown in Figure 7.1; the generator grounded through a
high reactance Xn, with a line-to-ground fault near one terminal. The small arcing current
through Xn tries to extinguish and reignite with increasingly high voltages. The high-
reactance grounded systems are no longer in use.
7.7 Resonant Grounding
Figure 7.1 also shows a resonant grounding system, with ground fault neutralizer. A
reactor can be connected between the neutral of a system and the ground and tuned to
the system charging current so that the resulting current is resistive and of low mag-
nitude. This current is in phase with the line-to-neutral voltage, so that the current
and voltage zeros occur simultaneously. The system is used for voltages above 15 kV,
consisting of overhead transmission or distribution lines. The system is rarely used for
industrial and commercial establishments. A disadvantage of the system is that the
resonant tuning can change due to switching conditions, that is, when a part of the
system may be out of service or when the system expansion takes place. This ground-
ing method is not common in the United States, though sometimes used in Europe and
Russia.
7.8 C
orner of Delta Grounded Systems
Low-voltage systems which in the past were supplied from delta-connected secondary were
inherently ungrounded. These were grounded by connecting one corner of the secondary
delta windings to ground, through an adequate connection and there was no additional
impedance inserted in this connection to obtain a grounded system (see Figure 7.8a). These
are no longer in use. It is necessary to positively identify the grounded phase throughout
the system to avoid connecting meters, instruments, and fuses in the grounded phase. A
higher line-to-neutral voltage will occur on two phases than in a neutral grounded system.
There is a possibility of exceeding the interrupting ratings of marginally applied circuit
breakers, because for a ground fault, the interrupting duty on the affected circuit breaker
pole may exceed the three-phase fault duty. There is a high probability of sustaining arc-
ing for 480 V or higher phase-to-phase, single-phase circuit extension without escalating
to a three-phase fault.
System Grounding 243
(a)
(b)
FIGURE 7.8
(a) Corner delta grounded system and (b) midpoint grounded delta grounded system.
The NEC Table 430–37 requires that for a three-phase system three overloads are used,
one in each phase for motor protection. The control circuit for motor starting has to be
carefully designed, so that a ground fault in it does not automatically start or stop a motor.
Some advantages of the system are low cost of establishing a grounded system, the
effective control of transient overvoltages, though a maximum of 1.73 times the normal
phase-to-ground voltage can exist between two conductors and ground, and a fault from
phase-to-ground can be easily detected.
One phase of a delta system can be grounded at the midpoint, see Figure 7.8b. The sys-
tem is not recommended for voltages above 240 V. Serious arc flash hazard from a phase-
to-ground fault can exist because of high fault levels [2]. Grounding of one phase of a delta
system at midpoint of that phase for three-phase systems with phase-to-phase voltages
over 240 V has little application. The shock hazard of the high phase leg to ground is 1.73
times the voltage from the other two phases. These systems are no longer in use.
Note that mostly molded case circuit breakers (MCCBs) are suitable for high-resistance
grounded systems, but all MCCBs may not be suitable for corner-grounded systems.
(a)
a1 b1 C1
Current
a2 mmf
b2 C2
(b) H1 X1
l0
Load
H2
0 H3 X3 X2 3l0
2I0
l0
l0 l0
3l0
R
3l0
FIGURE 7.9
(a) Flow of ground fault current in the windings of a zigzag transformer. (b) Application of a zigzag transformer
to derive an artificial neutral and current flows for a downstream fault.
circuit can be similarly drawn. The neutrals of large utility generators directly connected to
the step-up transformers generator step up (GSUs) are not directly connected to the ground
through a high resistance but through a distribution transformer which is loaded on the
secondary windings with a grounding resistor. An example will clarify the calculations.
Example 7.3
See Example 5.3 in Volume 1. This conveys important concepts for sizing of the ground-
ing resistor in HRG or low-resistance grounded (LRG) systems.
This example showed that all the sequence impedances, including that of the ground-
ing transformer, can be ignored without an appreciable error in sizing the grounding
resistor. The reason is that all system sequence impedances are much lower than the
grounding resistor zero-sequence impedance.
System Grounding 245
Facility
Transformer case Transformer case Meter service entrance
3-Phase
4-wire loads
MV LV
HV
PEN PEN N
PE
Neutral to PE bond
NEC bonding jumper
FIGURE 7.10
Typical grounding practice for a wye-service entrance, served by a multiple grounded system in North America.
L Consumer load
L
L
Utility transformer
L–CG–UG4–UG3–UG2 L–CG–UG4–UG3 L–CG–UG4 L–CG
CG
UG1 UG2
UG3 UG4
CG+UG2+UG3+UG4
Substation ground
FIGURE 7.11
Distribution of load currents in phase and neutral/ground conductor in multiple grounded system; the ground/
neutral conductor develops differential voltages.
246 Power Systems Protective Relaying
Facility
Transformer case Meter service entrance
3-phase
4-wire loads
HV MV
N
Insulated neutral
carried only for 4-wire service
(low-voltage)
FIGURE 7.12
Typical grounding practice in industrial distribution systems; the transformer neutral is grounded only at the
source in North American systems.
This also applies to direct buried underground cables. The voltage between neutral and
earth can originate from variety of sources. A 60 Hz voltage can exist between objects con-
nected to neutral and earth. A short-duration transient can exist, when the lightning cur-
rent is dissipated into the earth. A differential voltage between the neutral and the ground
is more likely to occur when the same service transformer feeds two or more consumers.
Figure 7.12 illustrates the grounding practice for industrial establishments. Here, the
neutral is grounded only at one point, which is at the source. This figure shows that
the neutral from the utility transformer is not required to be run for industrial plant
medium-voltage three-phase loads. In case the industrial plant needs some loads like
lighting and controls to be served from low-voltage grounded systems, these lower volt-
ages are served from a separate transformer with artificially derived neutral. In case
the service is at low voltage, a neutral may be run to supply phase-to-neutral loads, but
it is not grounded anywhere in the plant except at the service transformer. There is no
bonding of neutral conductor with the ground at the service entrance, a practice which
is invariably followed for industrial medium- or high-voltage grounded systems or sepa-
rately derived industrial systems.
IF
IN
ZE (n-2)/2
n–1
1 ZE1 ZE2 ZE3 ZE4 ZE (n–4)/2 ZE (n–2)/2
3 5 7 9 n–5 n–3
IE
FIGURE 7.13
An equivalent circuit diagram of a multiple grounded system for a line-to-ground fault at remote node.
• The NESC requires grounded items on joint poles (e.g., for power and communi-
cation) to be bonded together either using single grounding conductor or bond-
ing the supply grounding conductor to the communication grounding conductor,
except where a certain separation is maintained (Rule 97A), in which case there
should be insulation between the grounding conductors. A hazardous potential
difference can exist between the two conductors. Rule 215C3 requires bonding
between messengers at typically four times per mile.
• It is required that a common ground electrode system should be created by the
two utilities for the communication and power supply systems. If separate elec-
trode systems are used, these should be bonded together with a minimum #6
AWG conductor. This is to ensure that dangerous potentials do not exist between
the two grounding systems. A user of computer modem, fax machine, answering
machines, and other communication equipment could be exposed to an electrical
shock apart from damage to the equipment.
• The NEC (250.24(A)(5)) prohibits bonding of the equipment grounding conductor
and neutral inside the premises. Note that the neutral will carry a current and a
difference of potential exists between the neutral and the ground conductor. Again,
bonding is required to metal water pipes, which limits the possibility of a potential
difference between the water system and other noncurrent carrying parts within
the building. (A coupling can occur through soil resistivity.) It is prohibited using
interior metal water piping system located more than 5 in. from the entrance to the
building from being used to interconnect grounding electrodes within the building.
E= ∫ i dt
k
(7.10)
The value of k varies from 1 to 2, and for a purely resistive circuit, this value is 2.
Note that the source and the generator are both grounded through 400 A resistors which
have been a common industrial practice.
Considering fast relaying, the source current of 400 A is interrupted in six cycles, which
is the sum of relay operating time of one cycle (assumption) and interrupting time of
breaker which is equal to five cycles.
The curves in Figure 7.15 show the damage indices. Figure 7.15a shows the energy with
respect to the magnitude of the fault current and Figure 7.15b shows the energy accumula-
tion. These figures show the energy associated with the source current.
In six cycles, the generator breaker is tripped; however, the energy to the fault is not inter-
rupted. It continues to be fed for a relatively higher time as the generator current decays
slowly in about 0.8–1 s, depending on the generator single-line-to-ground fault constant.
System Grounding 249
400 A
400 A
52 52
13.8 kV bus
FIGURE 7.14
A typical grounding system, the transformer and generator are each grounded through a 400 A resistor.
Figure 7.15c shows this energy accumulation. Therefore, in 1 s, the energy into the fault is
approximately six times the energy released by the source fault current.
In this scenario, no neutral breaker is considered. A neutral breaker is often provided and tripped
simultaneously with the line breaker for faults such as differential phase and ground and also ground
faults. If the neutral breaker is present, it will limit the energy into the fault to a much lower value.
This has been studied by other authors.
The IEEE/IAS working group published four papers in IEEE Transactions on Industry
Applications, which are referenced in [16].
The concept of hybrid grounding is illustrated in Figure 7.16. For industrial bus-
connected generators, selective ground fault protection is required, and the generators
cannot be simply grounded through a 10 or 8 A resistor. The generators are generally the
last to trip on an external ground fault and the other system protection must operate faster
to clear the fault. This cannot be achieved if the industrial generators are high-resistance
grounded like the utility unit-connected generators.
In Figure 7.16, the low-resistance section of 400 A is connected through a neutral breaker.
The neutral breaker is tripped simultaneously with the main line breaker. After the neutral
breaker is tripped, the high-resistance ground section through 8 A remains connected and
limits the fault energy. The low-resistance grounded section provides ground fault coordi-
nation with the rest of the system. See Chapter 8 for an example of ground fault relaying.
7.13 Grounding of ASDs
A brief reference can be made to the grounding of variable speed drives (VSD) systems,
where special considerations apply. Consider a three-phase six-pulse bridge rectifier circuit
in Figure 7.17. Only two phases conduct at a time, and the dc plus and negative voltages
to midpoint are shown. These voltages do not add to zero and the midpoint oscillates at
thrice the ac supply system frequency. The dc positive and negative buses have common-
mode voltages and its magnitude changes with the firing angle. The peak of the voltage is
approximately 0.5 Vln, where Vln is the peak line-to-neutral point input voltage.
Consider common-mode voltages on the motor isolated neutral to ground of a 4160 V drive
system gate turn-off (GTO) inverter. The peak line-to-ground Vl−g voltage is 4100 V and the
250 Power Systems Protective Relaying
(a)
1000
750
Fault energy W s
500
250
(b)
1000
750
Fault energy W s
500
250
0
0.01 0.1 1.0 10
Current (A)
(c)
10,000
7,500
5,000
Fault energy W s
2,500
0
0.001 0.01 0.1 1.0 10
Current (A)
FIGURE 7.15
(a and b) Fault energy for the system source fault and (c) fault energy for the generator fault through the neutral
connection.
System Grounding 251
400 A
52
8A
400 A
52 52
13.8 kV bus
FIGURE 7.16
Hybrid grounding system for the generator, see the text.
DC+
C
C
M2
R
A N
M M1 A
R M3
B
B
DC–
DC+
V1n peak
DC–
1 2
Cycles
FIGURE 7.17
Generation of common-mode voltages in a six-pulse converter.
252 Power Systems Protective Relaying
waveform has a frequency of 60 Hz. The peak neutral-to-ground voltage is 2500 V and has
a frequency of 180 Hz. The operation of the output bridge creates a common-mode voltage
by exactly the same mechanism as the input bridge does, where the back EMF of the motor
is analogous to the line voltage.
Thus, the worst case condition for the common-mode voltage is no-load, full-speed
operation, as the phase-back angle is 90° for both the converters, and the motor volt-
age is essentially equal to the line voltage. The sum of both common-mode voltages is
approximately Vln at six times the input frequency. Since the input and output frequencies
are generally different, the motor experiences a waveform with beat frequencies of both
input and output frequencies and there will be instances when twice the rated voltage is
experienced, see Reference [17].
The grounding must assure that the motor insulation system is not stressed beyond its
design level. Figure 7.18 shows three possible methods. Figure 7.18a shows an output drive
isolation transformer with its secondary grounded. The transformer primary winding
insulation can tolerate the common-mode voltage swings better than the motor insulation.
This option is tricky as the drive isolation transformer is subjected to residual dc offset in
the drive and high harmonic content passing through the transformer windings. A better
location for the drive isolation transformer will be at the input line end (Figure 7.18b), and
the secondary winding is left ungrounded. The neutral of the filter capacitors on the out-
put of the inverter provides a convenient place to ground the load side of the inverter and
a small resistor rated 1 A or so is enough to do it. The line-to-neutral voltages must, then,
be taken into account for the insulation of the secondary of the transformer. Also the cables
forming the transformer secondary to the input rectifier bridge must be rated for higher
voltage to ground, for example, for a 4.16 kV drive system, cables with 173% insulation level
will be required; alternatively, 8 kV cables can be used.
An input or output drive transformer increases the cost and reduces the efficiency of the
drive system. In a transformerless GTO drive system, a line reactor may be used on the
input side to affect commutation notches, but the motor insulation must withstand twice
the normal voltage stress to ground, see Figure 7.18c.
(a)
M
Drive isolation
transformer Common mode voltage across
transformers sec.
(c)
M
Common mode voltage
Liner reactor across motor
FIGURE 7.18
(a) Isolation transformer with grounded secondary to withstand common-mode voltage. (b) Drive transformer
at input, common-mode voltage across secondary of the transformer. (c) Input line reactor, common-mode volt-
age across drive motor windings.
System Grounding 253
Substation
Ground-fault
protection
Power 51 G Outgoing circuit
transformer to mine
52
Surge
Incoming arresters
Power conductors
power
conductors To station Pilot conductor
Surge Control ground
arresters Y Grounding conductor
transformer
95
Grounding Ground
59N
resistor check
Backup
monitoring
To fencing ground-
and fault
Protection Portable switchhouse Incoming
substation
metal Grounding conductor coupler
structures Station
ground Pilot conductor
Frame
ground Surge
Ground beds separated arresters
Control
trans-
former 52 52
50 G or
Ground- 50 G 51 G
check
monitoring
Ground-
95 fault
Portable power center protection
95
Ground-fault Control
protection transformer
Out-going 50 G To control
couplers circuitry Outgoing
52 couplers
To other Power
portable As transformer
equipment below Incoming
50 G
coupler To other
Portable power cable
switch houses
To other 52 52
or power centers
portable As Surge
equipment below ∆ arresters
50 G
Grounding conductor
52
Pilot conductor
Grounding
Ground- resistor
check
monitoring
95
Frame ground
Equipment
training Mobile mining equipment
cable
To machine power circuits
Pilot conductor
Grounding conductor
Frame ground
FIGURE 7.19
A simplified mine power distribution system with a safety grounded system, see the text. (IEEE Standard 142,
IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems, 1991.)
254 Power Systems Protective Relaying
References
1. ANSI/IEEE Std. 80. IEEE Guide for Safety in Substation Grounding, 2000.
2. IEEE Standard 142. IEEE Recommended Practice for Grounding of Industrial and Commercial
Power Systems, 1991.
3. HI Stanback. Predicting damage from 277 volt single phase to ground arcing faults. IEEE
Transactions on Industry Applications vol. IA-13, no. 4, pp. 307–314, July/August, 1977.
4. NEMA PB1-2. Application Guide for Ground Fault Protective Devices for Equipment, 1977.
5. NEC National Electrical Code, NFPA 70, 2017.
6. JR Dunki-Jacobs. The escalating arcing ground fault phenomenon. IEEE Transaction on Industry
Applications vol. 22, no. 6, pp. 1156–1161, November 1986.
System Grounding 255
7. DG Lucks. Calculating incident energy released with varying ground fault magnitudes on
solidly grounded systems. IEEE Transactions on Industry Applications vol. 46, no. 2, pp. 761–769,
March/April 2010.
8. HB Land, III. The behavior of arcing faults in low-voltage switchboards. IEEE Transactions on
Industry Applications vol. 44, no. 2, pp. 437–444, March/April, 2008.
9. IEEE Std. 493 (Gold Book). Recommended Practice for Design of Reliable Industrial and
Commercial Power System, 2007.
10. Westinghouse. Transmission and Distribution Handbook. Westinghouse, East Pittsburg, PA, 1964.
11. DS Baker. Charging current data for guess-free design of high-resistance grounded systems.
IEEE Transactions on Industry Applications vol. 15, no. 2, pp. 136–140, March/April 1979.
12. GE Industrial Power Systems Data Book, GE, Schenectady, New York.
13. JR Dunki-Jacobs. The reality of high-resistance grounding. IEEE Transactions on Industry
Applications vol. 13, pp. 469–475, September/October 1977.
14. National Electrical Safety Code, C-2.
15. LJ Powell. The impact of system grounding practices on generator fault damage. IEEE
Transactions on Industry Applications vol. 34, no. 5, pp. 923–927, September/October 1998.
16. IEEE/IAS Working Group Report. Grounding and ground fault protection of multiple genera-
tor installations on medium voltage industrial and commercial power systems. Parts I, II, III and
IV, IEEE Transactions on Industry Applications vol. 40, no. 1, pp. 11–28, January/February 2004.
17. JC Das, H Osman. Grounding of AC and DC low-voltage and medium-voltage drive systems.
IEEE Transactions on Industry Applications vol. 34, no. 1. pp. 295–216, January/February 1998.
18. ANSI/IEEE Std. 367-1987. IEEE Recommended Practice for Determining the Electrical Power
Station Ground Potential Rise and Induced Voltages form a Power Fault.