Project:
ETAP Page: 1
12.6.0H
Location: Date: 13-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS BESAR_B_4 Config.: Normal
SHORT- CIRCUIT REPORT
Fault at bus: Bus3
Nominal kV = 500.000
Voltage c Factor = 1.10 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus3 Total 0.00 0.083 0.00 168.75 175.78 0.006 0.006 1.45E+001 1.53E+002 6.32E+003 1.37E+002
Bus2 Bus3 46.15 0.062 99.47 99.50 100.49 0.005 0.006 1.30E+001 2.05E+002 6.32E+003 1.37E+002
Bus7 Bus3 11.83 0.011 0.56 177.37 184.49 0.001 0.000 2.23E+002 1.18E+003
Bus28 Bus3 11.83 0.011 0.56 177.37 184.49 0.001 0.000 2.23E+002 1.18E+003
Gen9 Bus2 100.00 1.073 100.00 100.00 100.00 0.088 0.107 1.21E+001 2.31E+002 1.21E+001 8.50E+001
Gen13 Bus2 100.00 1.073 100.00 100.00 100.00 0.088 0.107 1.21E+001 2.31E+002 1.21E+001 8.50E+001
U1 Bus2 100.00 0.090 100.00 100.00 100.00 0.005 0.003 6.55E+001 2.75E+003 6.55E+001 2.75E+003
Bus62 Bus7 11.83 0.000 0.56 177.37 184.49 0.000 0.000
Bus48 Bus7 22.56 0.034 1.07 177.54 184.42 0.002 0.000 1.86E+002 1.05E+003
Bus63 Bus28 11.83 0.000 0.56 177.37 184.49 0.000 0.000
Bus47 Bus28 22.56 0.034 1.07 177.54 184.42 0.002 0.000 1.86E+002 1.05E+003
3-Phase L-G L-L L-L-G
Initial Symmetrical Current (kA, rms) : 0.083 0.006 0.072 0.074
Peak Current (kA), Method C : 0.207 0.015 0.181 0.184
Breaking Current (kA, rms, symm) : 0.006 0.072 0.074
Steady State Current (kA, rms) : 0.062 0.006 0.072 0.074
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 2
12.6.0H
Location: Date: 13-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS BESAR_B_4 Config.: Normal
Fault at bus: Bus7
Nominal kV = 150.000
Voltage c Factor = 1.10 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus7 Total 0.00 0.209 0.00 167.43 175.42 0.017 0.017 3.34E+001 1.81E+002 6.56E+003 2.05E+002
Bus62 Bus7 2.50 0.098 0.21 167.42 175.42 0.008 0.008 1.26E+002 3.71E+002 1.37E+004 4.52E+002
Bus48 Bus7 11.51 0.036 0.63 167.66 175.36 0.002 0.000 1.86E+002 1.05E+003
Bus3 Bus7 25.93 0.077 4.61 156.71 164.51 0.007 0.009 1.37E+000 4.97E+002 1.26E+004 3.72E+002
Bus75 Bus62 5.01 0.098 0.43 167.41 175.42 0.008 0.008 1.16E+002 3.70E+002 1.37E+004 4.49E+002
Bus128 Bus62 2.50 0.000 0.21 167.42 175.42 0.000 0.000
Mtr19 Bus48 100.00 0.002 100.00 100.00 100.00 0.000 0.000 5.99E+004 8.39E+004
Mtr20 Bus48 100.00 0.002 100.00 100.00 100.00 0.000 0.000 5.99E+004 8.39E+004
Mtr21 Bus48 100.00 0.002 100.00 100.00 100.00 0.000 0.000 5.99E+004 8.39E+004
Lump14 Bus48 100.00 0.088 100.00 100.00 100.00 0.005 0.000 4.31E+002 2.88E+003
Lump15 Bus48 100.00 0.088 100.00 100.00 100.00 0.005 0.000 4.31E+002 2.88E+003
Lump16 Bus48 100.00 0.088 100.00 100.00 100.00 0.005 0.000 4.31E+002 2.88E+003
Bus2 Bus3 57.59 0.044 94.77 94.90 95.59 0.004 0.005 1.30E+001 2.05E+002 6.32E+003 1.37E+002
Bus28 Bus3 10.02 0.020 0.85 167.40 175.42 0.002 0.003 1.15E+002 4.34E+002 1.32E+004 3.09E+002
3-Phase L-G L-L L-L-G
Initial Symmetrical Current (kA, rms) : 0.209 0.017 0.182 0.186
Peak Current (kA), Method C : 0.475 0.039 0.413 0.422
Breaking Current (kA, rms, symm) : 0.017 0.182 0.186
Steady State Current (kA, rms) : 0.139 0.017 0.182 0.186
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 3
12.6.0H
Location: Date: 13-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS BESAR_B_4 Config.: Normal
Fault at bus: Bus41
Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus41 Total 0.00 7.776 0.00 173.14 173.21 0.006 0.006 8.72E+002 1.54E+003 6.80E+006 1.18E+003
Bus42 Bus41 80.28 7.776 99.99 100.00 100.00 0.006 0.006 * 8.72E+002 1.54E+003 6.80E+006 1.18E+003
Bus40 Bus42 80.28 0.000 100.00 99.99 100.00 0.000 0.000
Bus39 Bus42 80.28 0.000 100.00 99.99 100.00 0.000 0.000
Bus43 Bus42 80.28 0.000 100.00 99.99 100.00 0.000 0.000
Bus63 Bus42 90.27 0.156 100.00 100.00 100.00 0.000 0.000 7.37E+002 2.85E+002
3-Phase L-G L-L L-L-G
Initial Symmetrical Current (kA, rms) : 7.776 0.006 6.736 6.737
Peak Current (kA), Method C : 13.190 0.010 11.426 11.428
Breaking Current (kA, rms, symm) : 0.006 6.736 6.737
Steady State Current (kA, rms) : 7.424 0.006 6.736 6.737
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 4
12.6.0H
Location: Date: 13-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS BESAR_B_4 Config.: Normal
Fault at bus: Bus42
Nominal kV = 20.000
Voltage c Factor = 1.10 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus42 Total 0.00 0.785 0.00 164.63 175.53 0.090 0.090 8.47E+001 3.57E+002 9.38E+003 3.82E+002
Bus40 Bus42 0.00 0.000 101.34 95.05 100.02 0.000 0.000
Bus39 Bus42 0.00 0.000 101.34 95.05 100.02 0.000 0.000
Bus41 Bus42 0.00 0.000 101.34 95.05 100.02 0.000 0.000
Bus43 Bus42 0.00 0.000 101.34 95.05 100.02 0.000 0.000
Bus63 Bus42 50.23 0.785 30.90 141.65 150.46 0.090 0.090 8.47E+001 3.57E+002 9.38E+003 3.82E+002
Bus28 Bus63 50.64 0.054 31.06 141.64 150.47 0.006 0.006 4.29E+001 3.50E+002 1.28E+004 3.91E+002
Bus75 Bus63 50.77 0.051 31.05 141.64 150.47 0.006 0.006 9.63E+001 3.66E+002 1.34E+004 4.30E+002
3-Phase L-G L-L L-L-G
Initial Symmetrical Current (kA, rms) : 0.785 0.090 0.681 0.703
Peak Current (kA), Method C : 1.672 0.191 1.451 1.498
Breaking Current (kA, rms, symm) : 0.090 0.681 0.703
Steady State Current (kA, rms) : 0.629 0.090 0.681 0.703
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 5
12.6.0H
Location: Date: 13-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS BESAR_B_4 Config.: Normal
Fault at bus: Bus63
Nominal kV = 150.000
Voltage c Factor = 1.10 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus63 Total 0.00 0.210 0.00 167.43 175.37 0.017 0.017 3.40E+001 1.80E+002 6.56E+003 2.05E+002
Bus28 Bus63 2.78 0.109 0.23 167.42 175.39 0.009 0.009 4.29E+001 3.50E+002 1.28E+004 3.91E+002
Bus75 Bus63 2.59 0.101 0.22 167.42 175.38 0.008 0.008 9.63E+001 3.66E+002 1.34E+004 4.30E+002
Bus42 Bus63 0.00 0.000 0.00 167.43 175.37 0.000 0.000
Bus47 Bus28 12.49 0.036 0.74 167.65 175.32 0.002 0.000 1.86E+002 1.05E+003
Bus3 Bus28 25.75 0.073 4.61 156.71 164.48 0.007 0.009 2.88E+001 5.20E+002 1.28E+004 3.87E+002
Bus62 Bus75 5.18 0.101 0.44 167.41 175.38 0.008 0.008 8.65E+001 3.65E+002 1.34E+004 4.27E+002
Bus68 Bus75 2.59 0.000 0.22 167.42 175.38 0.000 0.000
Bus40 Bus42 0.00 0.000 101.25 96.67 100.03 0.000 0.000
Bus39 Bus42 0.00 0.000 101.25 96.67 100.03 0.000 0.000
Bus41 Bus42 0.00 0.000 101.25 96.67 100.03 0.000 0.000
Bus43 Bus42 0.00 0.000 101.25 96.67 100.03 0.000 0.000
3-Phase L-G L-L L-L-G
Initial Symmetrical Current (kA, rms) : 0.210 0.017 0.183 0.187
Peak Current (kA), Method C : 0.471 0.039 0.409 0.419
Breaking Current (kA, rms, symm) : 0.017 0.183 0.187
Steady State Current (kA, rms) : 0.140 0.017 0.183 0.187
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 6
12.6.0H
Location: Date: 13-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS BESAR_B_4 Config.: Normal
Fault at bus: Bus125
Nominal kV = 0.400
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus125 Total 0.00 7.776 0.00 173.14 173.21 0.006 0.006 8.72E+002 1.54E+003 6.80E+006 1.18E+003
Bus128 Bus125 80.28 7.776 99.99 100.00 100.00 0.006 0.006 * 8.72E+002 1.54E+003 6.80E+006 1.18E+003
Bus123 Bus128 80.28 0.000 100.00 99.99 100.00 0.000 0.000
Bus129 Bus128 80.28 0.000 100.00 99.99 100.00 0.000 0.000
Bus124 Bus128 80.28 0.000 100.00 99.99 100.00 0.000 0.000
Bus62 Bus128 90.27 0.156 100.00 100.00 100.00 0.000 0.000 7.37E+002 2.85E+002
3-Phase L-G L-L L-L-G
Initial Symmetrical Current (kA, rms) : 7.776 0.006 6.736 6.737
Peak Current (kA), Method C : 13.190 0.010 11.426 11.428
Breaking Current (kA, rms, symm) : 0.006 6.736 6.737
Steady State Current (kA, rms) : 7.424 0.006 6.736 6.737
# Indicates a fault current contribution from a three-winding transformer
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer