How To Recharge Air Conditioner: Purpose, Do's and Don'ts, and Some Advice
How To Recharge Air Conditioner: Purpose, Do's and Don'ts, and Some Advice
There are three different ways of how to recharge air conditioner systems. The
methods for this air conditioning maintenance are,
refrigerant charging from high pressure side,
refrigerant charging from low pressure side,
refrigerant of 4xx series, e.g. R-404a are non azeotrope type refrigerants,
EXCEPT for R-410.
So, what’s the big deal between azeotrope and non azeotrope refrigerant?
Non azeotrope refrigerants on the other hand, DO NOT act like a single
refrigerant.
The implication is that, the blends will be lost from the system at different
proportions due to different boiling temperatures, whenever there is a
leakage in the non azeotrope refrigerant.
Hence, charging of non azeotrope refrigerant can only be carried out from
zero to full. Never top up this type of refrigerant in case of leakage.
1
do not overcharge as this will cause compressor damage,
do not undercharge
correct problems within the system, if subcooling or superheat is inadequate,
even if the pressure in the system has reached design state
never use open flame to heat up refrigerant cylinders. Use warm water
instead
recover the excess refrigerant into recovery cylinder, if the system is
overcharged
A little more before we go further into how to recharge air conditioner systems.
It’s about time we look into details of "How to Recharge Air Conditioner".
Other criteria that will require this technique are inadequate subcooling, and to top
up refrigerant.
First,
5. attach plain pressure gauge’s hose of the gauge set, to the liquid line service
valve of the air conditioning unit.
2
Make sure that the protective cap of the service valve is taken out
Other criteria that will require this technique are inadequate superheat, and to top
up refrigerant.
First,
3
4. purge the line by throttling the compound gauge’s regulator, and the
refrigerant cylinder’s regulator.
5. attach compound pressure gauge’s hose of the gauge set, to the suction
service valve of the air conditioning unit.
Make sure that the protective cap of the service valve is taken out
The pressure within the system shall be less than the condensing pressure of
the refrigerant
4
How to recharge air conditioner style 3: Using weight:
This method is used to charge refrigerant to an evacuated, or newly assembled, and
moisture removed air conditioning unit.
The steps,
5. attach compound pressure gauge’s hose of the gauge set, to the suction
service valve of the air conditioning unit.
Make sure that the protective cap of the service valve is taken out
OR
5
6
Air Conditioning Troubleshooting
Are you an equipment owner with a question about air conditioning troubleshooting?
Our air conditioning problem page has some guidance that might help you get your
air conditioner running.
If you're working on a Trane unit, our page about troubleshooting Trane air
conditioning controls has some tips about Trane's microprocessor controls that you
might find useful.
Are you a technician doing some air conditioning troubleshooting on a totally dead
unit?
Are your shoe soles already gummy from a previous service call on somebody's unit
on a tar-paper roof?
Did you just finish a service call 20 minutes ago where you were sweating buckets
wriggling around in somebody's steam-kettle attic?
If you're done with your diet soda; grab your tools, crank up the can-do attitude,
and let's go troubleshoot this air conditioner.
This unit's acting dead, so check the breaker, check the disconnect and fuses, and
check to make sure you have correct power supplied to the unit.
If the breaker is tripped and/or a fuse is blown, check the unit for grounds or shorts.
Disconnect the leads from the air conditioning compressor terminals and check for
grounded, shorted, or open windings.
Check the evaporator and condenser fan motors for grounded or shorted windings.
Check the control and power circuits for shorts or grounds.
7
If your air conditioning troubleshooting call is for a unit that has good supply voltage
but is otherwise dead:
If your supply power checks out ok, make sure the thermostat is turned on, that
there is control power to it, and verify that it actually works.
If there's control power to the thermostat and it works, make sure the wires to the
evap fan relay and condensing unit aren't broken at the thermostat, or somewhere
between the thermostat and the units.
Air conditioning troubleshooting when the air conditioning condenser won't run.
If the oil safety switch has tripped, check the oil level.
It will also trip if the contactor closes but the compressor doesn't run for some
reason,
So check for open compressor windings, verify that the compressor terminal
connections and contactor connections are tight, and verify that there is actually
good voltage at the compressor when the contactor pulls in.
8
If the safety contacts are closed, you should have control power at your contactor.
If there is no control power at the contactor coil, check for a broken wire somewhere.
If you have control power at the contactor coil but the contactor doesn't pull in, the
contactor has failed.
See our air conditioning contactor page for contactor troubleshooting tips.
If you're on an air conditioning troubleshooting call where the contactor pulls in but
the compressor doesn't run, check for open compressor windings, verify that the
compressor terminal connections and contactor connections are tight, and verify that
there is actually good voltage at the compressor when the contactor pulls in.
If it's a single phase compressor, check the start relay and the capacitors.
The best way to test the start relay and capacitors is to replace them with new parts.
If the condenser fan doesn't run, check the relay, motor windings and capacitor, and
fan blade, the same way as with the evaporator fan.
Be thorough as you trace down wiring and look for failed components, and always
follow safety precautions during your air conditioning troubleshooting jobs.
By the time you reach this point of air conditioning troubleshooting, you will have
found the failed component and repaired or replaced it, and the unit will be ready to
run.
Good Job!
For a few more tips on condensing unit troubleshooting, and some unusual
condensing unit problems I've run into, see our Troubleshoot Air Conditioning
Condensing Unit page.
Air conditioning troubleshooting on a unit that runs but doesn't seem to be cooling
efficiently.
Verify that the evaporator and condenser coils are clean and air flow is not blocked.
9
Verify that the condenser is getting normal temperature outside air, and that another
unit isn't blowing hot air into it.
Verify that the evaporator supply and return ducting is not leaking; losing cold air or
picking up warm outside air.
At this point in this air conditioning troubleshooting job, attatch your gauges and
check your pressures and temperatures.
Before we get started though, in case you're interested, on our Air Conditioning
Manifold Gauges page I discuss a couple of my favorite brands of manifold sets.
With the unit off and pressures equalized, verify that the system contains the correct
refrigerant.
You can do this by taking the temperature of the evaporator coil. It should match the
pressure/temperature indication on your low side gauge or pressure/temperature
chart.
When the space has cooled down and is about 5 degrees above design temperature,
look for the following pressures and temperatures.
If all of your operating characteristics fall within these ranges, the unit is running
good.
If you're interested in more air conditioning troubleshooting tips, you might want to
take a look at our System Evaluation and Chiller Evaluation manuals.
10
They have troubleshooting diagrams, and more detailed information about how to
evaluate direct expansion and chilled water type air conditioning and refrigeration
system operating characteristics.
At this stage of air conditioning troubleshooting, if there is still a concern about the
unit not cooling properly, you will need to do a capacity check.
Measure the wet bulb temperatures of the air entering and leaving the evaporator.
Using a psychrometric chart or an enthalpy conversion table, convert the wet bulb
temperatures to enthalpy values, and calculate the difference between the two
values.
Multiply the difference in enthalpy values times 4.5, which is a constant used in this
calculation, and then multiply that product times the CFM.
This will tell you how many btu of heat the evaporator is absorbing from the air
flowing through it.
If the difference between design capacity and running capacity is minor, it can be
adjusted by adjusting evaporator blower speed.
If the unit is running at or near design capacity but still not handling the load of the
space being cooled, the unit is simply too small.
I hope this page has provided some useful tips about air conditioning troubleshooting,
and please, feel free to contact us with any specific HVAC questions you might have,
including questions about air conditioning on Guam, or refrigeration on Guam.
11