This document provides notes for the bill of quantities for a fire alarm and public address system project. It includes 10 items: 1. All work must fulfill the basis of design and specifications. Equipment and methods must conform to standards. 2. Rates include all materials, labor, equipment, transportation, taxes and risks to fully execute the work. 3. Quantities are for guidance only. The contractor will be paid for actual work based on approved drawings at contract rates.

Uploaded by

Kamran Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
236 views

FA - PA Works Wo Revised Boq

This document provides notes for the bill of quantities for a fire alarm and public address system project. It includes 10 items: 1. All work must fulfill the basis of design and specifications. Equipment and methods must conform to standards. 2. Rates include all materials, labor, equipment, transportation, taxes and risks to fully execute the work. 3. Quantities are for guidance only. The contractor will be paid for actual work based on approved drawings at contract rates.

Uploaded by

Kamran Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 15

ANNEXURE : I

GENERAL NOTES FOR BILL OF QUANTITIES


PROJECT : RIVALI PARK, WINTER GREEN
NAME OF WORK: FIRE ALARM & PUBLIC ADDERESS SYSTEMS

1
All items of work under this Contract shall be executed strictly to fulfill the requirements laid down under “Basis of Design” in the specifications.
Type of equipment, material specification, methods of installation and testing and type of control shall be in accordance with the specifications,
approved shop drawings and the relevant Indian Standards, however capacity of each component and their quantities shall be such as to fulfill
the above mentioned requirement.

2 The rate for each item of work included in the Schedule of Quantities shall, unless expressly stated otherwise, include cost of :

a All materials, fixing materials, accessories, appliances tools, plants, equipment, transport, labour and incidentals required in preparation for and
in the full and entire execution, testing, balancing, commissioning and completion of work called for in the item and as per Specifications and
Drawings.

b Wastage on materials and labour.

c Loading, transporting, unloading, handling/double handling, hoisting to all levels, setting, fitting and fixing in position, protecting, disposal of
debris and all other labour necessary in and for the full and entire execution and for the job in accordance with the contract documents, good
practice and recognize principles.

d Liabilities, obligations and risks arising out of Conditions of Contract.

e All requirements of Specifications, whether such requirements are mentioned in the item or not. The Specifications and Drawings where
available, are to be read as complimentary to and part of the Schedule of Quantities and any work called for in one shall be taken as required for
all.

f In the event of conflict between Schedule of Quantities and other documents including the Specifications, the most stringent shall apply. The
interpretation of the Architect / Engineer shall be final and binding.

3
All equipments, quantities and technical data indicated in this Schedule are for the Contractor’s guidance only, these are based on the
documents prepared by the Services Consultant. This schedule must be read in conjunction with other documents. The Contractor shall be paid
for the actual quantity of work executed by him in accordance with the approved Shop Drawings at the contract rates.

4
This Schedule shall be fully priced and the extensions and totals duly checked. The rates for all items shall be filled in INK including NIL items.

5
No alteration whatsoever is to be made to the text or quantities of this Schedule unless such alteration is authorised in writing by Services
Consultant. Any such alterations, notes or additions shall, unless authorized in writing, be disregarded when tender documents are considered.

6 In the event of an error occurring in the amount of the Schedule, as a result of wrong extension of the unit rate and quantity, the unit rate
quoted by the tenderer shall be regarded as firm and the extensions shall be amended on the basis of rates.

7 Any error in totaling in the amount column and in carrying forward total shall be corrected. Any error, in description or in quantity, omission of
items from this Schedule shall not vitiate this Contract but shall be corrected and deemed to be variation required by the Services
Consultant/Project Manager.

8 The Contractor shall procure and bring Materials/Equipment to the site only on the basis of drawings approved for construction and shop
drawings and not on the basis of Schedule of Quantities which are approximate only. This also applies to the Contractor’s requisition for Owner
supplied materials.

9 The unit rate for all local equipment or materials (not being procured against duty benefit) in Indian Rupees shall include cost of equipment and
materials including all taxes and duties and also including forwarding, freight, insurance and transport into Contractor’s store at site, storage,
installation, testing, balancing, commissioning and other works required.

10 The rates for item being procured against duty benefit shall be quoted under following heads.
TYPE OF WORK : WITH MATERIALS WORKS

UNIT RATE (Rs.)


ITEM. ITEM DESCRIPTION UNIT AMOUNT
NO. A B C D E F TOTAL SUPPLY INSTALLATION TOTAL (Rs.)
NTA Wing Wing Wing Wing Wing Wing
A FIRE ALARM SYSTEM

1 Supply,Installation,Testing & Commissioning of the Fire Alarm System consisting


of the following:

Multi Loop Microprocessor based xx loop (each loop shall be able to connect
minimum 125 detectors and 125 modules) intelligent ,analogue addressable type
fire alarm control panel with minimum 80 character LCD display, four access levels,
400 event historical logging, flash EPROM sufficient numbers of programmable
relay controls, 240 volts AC power supply, automatic battery charger, 24 volts
sealed lead acid batteries sufficient for 48 hours normal working and then be
capable of operating the system for 30 Minutes during an emergency
1.1 condition including all necessary software for remote programming of fire alarm
system through central control station. Panel should be integrated with phase-1A
panel. All the panel should be networkable on decicated fire alarm network
through Copper connectivity cable vendor to considerate the necessary
accessories , module to take all the panel in networking & to make the system
functional .
(Location - FACP panel will be located at Fire Control Room , Podium -1 & NTA
FACP will be kept in D wing Fire Control Room)

a 10 loops No. 1 R.O. R.O. R.O. R.O. R.O. R.O. 1 540,000.00 540,000.00
b 6 loops No. R.O. 1 R.O. R.O. 1 R.O. R.O. 2 490,000.00 980,000.00
c 4 loops No. R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. 400,000.00
d 2 loops No. 1 R.O. R.O. R.O. R.O. R.O. R.O. 1 179,550.00 179,550.00

Fire Alarm System software capable of following functions : * Seamless integration


to BAS software * Uploading and downloading of information to FACP. * Graphics
1.2 including autocad drawings. * All Detector information and change of detector Set R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. 110,400.00
setting Software as described above. All necessary License & software cost to be
included in the cost. (Location- Fire Control Room for Wing - D , Podium -1 )

1.3 Fire work station as per specification for the Above mention GUI software. No R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. 41,400.00

Networkable Repeater panel with 40 character back lite super twist LCD display
1.4 with system function keys like system reset. Alarm acknowledge, Alarm Silence, 1 1 1 1 1 1 7 54,000.00 378,000.00
Trouble Acknowledge etc. Quoted price (Location of Repeater panel :Entrance No 1
Lobby of Each Tower , Main Security Gate )

Addressable Monitor modules monitor status like flow Switch,Tamper Switch in


1.5 Fire fighting & other applications as per specifications No. 75 43 7 11 43 7 11 197 1,214.00 239,158.00

AECOM INDIA PVT. LTD., MUMBAI SQ-2 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
UNIT RATE (Rs.)
ITEM. ITEM DESCRIPTION UNIT AMOUNT
NO. A B C D E F TOTAL SUPPLY INSTALLATION TOTAL (Rs.)
NTA Wing Wing Wing Wing Wing Wing
Adressable Control modules for Fans Tripping & activating smoke extract fans
1.6 ,Elevator recall, fire damper, Pressurization fan Liftwell & Stairwell , PA system, etc. No. 40 86 7 22 86 7 22 270 2,187.00 590,490.00
As per specification

1.7 Intelligent Analogue addressable photoelectric type smoke detector with R.O. 238 21 66 238 21 66 650 2,611.00 1,697,150.00
No.
mounting base, LED, intelligent address complete as per specifications

Intelligent addressable rate of rise cum fixed temperature heat detector with
1.8 mounting base, LED, intelligent address complete as per specifications No. 1317 R.O. R.O. R.O. R.O. R.O. R.O. 1317 2,074.00 2,731,458.00

1.9 Intelligent addressable type Multicriteria type detector with mounting base, LED, R.O. R.O. R.O. R.O. R.O. R.O. 155 3,106.00 481,430.00
intelligent address Complete as per specifications(AFC & BFC) No. 155

1.10 Addressable Gas Leak Detector with required accessories such as power suuply if R.O. 247 28 66 247 28 66 682 1,701.00 1,160,082.00
required etc. No.

1.11 Standalone Gas Leak Detector with required accessories such as power suuply if R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. 2,800.00
required etc. No.

1.12 Addressable Monitor modules monitor status like Gas leak Detector applications R.O. 247 28 66 247 28 66 682 1,795.00 1,224,190.00
as per specifications No.

1.13 Addressable type dual action manual Pull Station unit as per specifications No. 40 86 7 22 86 7 22 270 2,244.00 605,880.00

Surface mounted addressable type fully solid state circuitory dual tone Electronic
1.14 loud speaker type hooters with strobe lights of 110 Cd intensity as per No. 76 86 7 22 86 7 22 306 3,240.00 991,440.00
specifications

1.15 Addressable Fault Isolation Module as per specifications No. 109 43 7 11 43 7 11 231 2,250.00 519,750.00

1.16 Response Indicator as per Specification No. R.O. 10 R.O. R.O. 10 R.O. R.O. 20 150.00 3,000.00

1.17 Auto Dialer unit as per Specification No. 1 R.O. R.O. R.O. R.O. R.O. R.O. 1 9,000.00 9,000.00

1.18 Magnetic Door Contact along with Monitor Modules as per Specification No. R.O. 4 2 2 4 3 3 18 2,100.00 37,800.00

1.19 Telephone jack along with Control Modules as per Specification No. 40 86 7 22 86 7 22 270 3,105.00 838,350.00

1.20 Telephone receiver as per Specification No. 1 1 1 1 1 1 1 7 10,900.00 76,300.00

AECOM INDIA PVT. LTD., MUMBAI SQ-3 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
UNIT RATE (Rs.)
ITEM. ITEM DESCRIPTION UNIT AMOUNT
NO. A B C D E F TOTAL SUPPLY INSTALLATION TOTAL (Rs.)
NTA Wing Wing Wing Wing Wing Wing

Standalone UPS with 15 min. Battery backup. The Contractor to confirm the
capacity of UPS for giving power supply for all control room equipment in IBMS
room & Field levels as mention below such as workstation,System Integration
1.21 Unit,Gateways/Switch ,Fire panel & Workstation, PA System Rack, Hooter Power R.O. 1 R.O. R.O. 1 R.O. R.O. 2 315,000.00 630,000.00
supply,Workststions screens at all levels etc. Contractor should mention the Set.
capacity of the UPS selected with calculations at the time of quoting the tender
vendor to considered 20% spare capacity above actual load in the UPS. (UPS FOR
Each wing located at Fire Control Room , Podium -1 )

Note - From UPS to floor level UPS DB & to Socket (UPS point) near to IBMS
equipments (field devices & Panels), Power supply etc. will be in electrical vendor
scope (Electrical Vendor to provide Cabling to socket ,DB etc.for IBMS field
equipments such as hooter power supply, workstations etc.) IBMS Vendor to share
the all the IBMS equipment required UPS power point layout to electrical vendor
for execution as per approved design.

TOTAL AMOUNT (A) 13,913,028.00

B PUBLIC ADDRESS SYSTEM

1 Supplying, Installing, Testing & Commissioning of the Public Address system


consisting of the following:

Audio amplifiers & Controllers Routers etc including all necessary control desk
and microprocessor based control unit with microphone, BGM, Call Station & PC
input including providing necessary rack for mounting the Amplifier.Contractor to
decide on the number, depending upon his amplifiers capacity. Vendor shall
1.1 calculate related controller, router, call station and keypad. (Contractor shall Set 1 1 1 1 1 1 1 7 27,000.00 189,000.00
furnish quantity and unit rate for each type of amplifier considered by him.)
(Location - FACP panel will be located at Fire Control Room , Podium -1 & NTA
FACP will be kept in D wing Fire Control Room). Amplifier selection shall be at full
load rating

1.2 6 W Ceiling Mounted Speaker with Multi Tapping Feature. Nos. 40 129 21 44 129 21 44 428 694.00 297,032.00

1.3 6 W Wall Mounted Box Type Vendal Proof Cabinet speakers with Multi Tapping 86 7 22 86 7 22 306 1,035.00 316,710.00
Feature. Nos. 76

1.4 15 W Wall Mounted Type Horn Type Speaker with Multi Tapping Feature. Nos. 178 R.O. R.O. R.O. R.O. R.O. R.O. 178 1,715.00 305,270.00

Announcement console complete with microphone and Zone selection as per


1.5 Specifications ( Security Room,Each Fire Control Room At Podium Floor) Set R.O. 1 R.O. R.O. 1 1 R.O. 3 72,900.00 218,700.00

Integrated music source consisting of CD player, tape deck etc for Voice Evacuation
1.6 & Back Ground Music (should be capable of playing MP3,VCD,CD).as per Set R.O. 1 R.O. R.O. 1 1 R.O. 3 2,700.00 8,100.00
specifcation
AECOM INDIA PVT. LTD., MUMBAI SQ-4 Contractor's Signture
NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
UNIT RATE (Rs.)
ITEM. ITEM DESCRIPTION UNIT AMOUNT
NO. A B C D E F TOTAL SUPPLY INSTALLATION TOTAL (Rs.)
NTA Wing Wing Wing Wing Wing Wing

1.7 Car Calling system as per specifcation Set R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. 100,000.00

TOTAL AMOUNT (B) 1,334,812.00

C. CABLES & ACCESSORIES FOR FAS & PA

1 CABLES & ACCESSORIES FOR FAS

Supplying, installing, testing and commissioning of FRLS armored cables with 2C X


1.5 sqmm annealed copper conductor having Cross linkable Fire retartdant Low
smoke insulation and FRLS inner and outer sheath. Armored cables should comply
to BS 6387 & BS 7846:2009 (latest edition). Armored cables should meet BS
1.1 7846:2009. Fire test as per BS 8434. Cable should be Fire RED in color, Cables shall 17900 1410 3630 17900 1410 3630 72783.45 90.00 6,550,510.50
be estimated per device basis as per the drawings. Cabling for response indicator/ Mtrs. 26903.45
Input & Output modules to field equipment/ power shall not be considered
seperatelyas device. The cost shall be included the all fixing accessories such as
clips, nails, screws,saddles Spacers ,heavy guage Junction Boxes & Glandings etc in
the unit rate estimated for per device as per specifcation.

Supplying, installing, testing and commissioning of FRLS armored cables 18 AWG,2


paired (4 nos conductor ) armored Sheilded twin twisted pairs ATC cable for fire
detection and alarm system with Cross linkable FRLS Outher Sheet,Conductor shall
1.2 have covered by an extruded layer of FRLS insulation and FRLS inner sheath. R.O. R.O. R.O. R.O. R.O. R.O. 1975 134.00 264,650.00
Armored cables as per BS standards. The quoted rate shall be inclusive of suitable Mtrs. 1975
saddles spacers, hardware,fire rated junction boxes/Back & Glands for termination
etc. complete as per specifcation. (Note:Contractor has to design the Qty as per
FACP & Repeater loctaion considered/desinged by them )

Supplying, installing, testing and commissioning of 2 mm thick GI trunking with


1.3 cover of the following sizes complete with angle iron supports/hanging
arrangement etc as per Specifcation

a. 40 x 300 x 40 Mtrs. 50 R.O. R.O. R.O. R.O. R.O. R.O. 50 1,530.00 76,500.00

b. 40 x 200 x 40 Mtrs. 50 R.O. R.O. R.O. R.O. R.O. R.O. 50 1,170.00 58,500.00

c. 25 x 150 x 25 Mtrs. R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. 990.00

2 CABLES & ACCESSORIES FOR PA SYSTEM

AECOM INDIA PVT. LTD., MUMBAI SQ-5 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
UNIT RATE (Rs.)
ITEM. ITEM DESCRIPTION UNIT AMOUNT
NO. A B C D E F TOTAL SUPPLY INSTALLATION TOTAL (Rs.)
NTA Wing Wing Wing Wing Wing Wing

Supplying, installing, testing and commissioning of FRLS armored twisted,Sheilded


cables with 2 core annealed copper conductor having FRLS inner and outer sheath.
2xsheathed copper conductor armored ATC cables Twisted pair 2 core 1.5 sq mm
2.1 cables as per specifications Armored cables should comply to BS 7846:2009 (latest 12020 100.00 1,202,000.00
edition) ) Cables shall be estimated per Speaker basis as per the drawings. The cost Mtrs. 5300 2450 260 650 2450 260 650
shall be included the all fixing accessories such as clips, nails, screws,saddles
Spacers ,heavy guage junction Boxes & Glandings etc in the unit rate estimated for
per speaker with complete accessiories as per specfication

TOTAL AMOUNT (C) 8,152,160.50

TOTAL AMOUNT (A+B+C) 23,400,000.50

CGST 9% 2,106,000.05
SGST 9% 2,106,000.05

TOTAL AMOUNT INCLUDING TAXES (A+B+C) 27,612,000.59

The rate of each item of work for Fire Detection and Alarm System & PA shall also include the following :
1. All materials, fixing materials, accessories, appliances, tools and equipment.
2. Approved cover plates for inspection, junction and outlet boxes.
3. 2 mm thick outlet boxes and junction boxes.
4. All fixing accessories such as clips, nails, screws etc.
5. Providing and fixing approved saddles, hooks and grouting the same as required, in the case of all exposed cable work.
6. Embedding cables and accessories in wall, floors etc. during construction and / or cutting chases and making good as in the case of all concealed cables work.
7. Testing and commissioning of each device, circuit as per the requirements of NFPA 72, TAC, local authorities and to be witnessed by the PMC / Architect / Consultant.

AECOM INDIA PVT. LTD., MUMBAI SQ-6 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
490000

54000

52202

AECOM INDIA PVT. LTD., MUMBAI SQ-7 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
188082

621418

420147

443365

192984

278640

96750

1500

8400

267030

10900

AECOM INDIA PVT. LTD., MUMBAI SQ-8 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
315000

27000

89526

89010

72900

2700

AECOM INDIA PVT. LTD., MUMBAI SQ-9 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
1611000

AECOM INDIA PVT. LTD., MUMBAI SQ-10 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
245000

5577554

AECOM INDIA PVT. LTD., MUMBAI SQ-11 Contractor's Signture


NODD12032-LV-06-0000-00_00 – Residential Project at Borivali, Mumbai : SOQ for FAS & PA System
ANNEXURE : I
BILL OF QUANTITIES

NAME OF WORK: FIRE ALARM & PUBLIC ADDERESS SYSTEMS


WO NO : #REF!

ITEM. RATE (Rs.)


NO. ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL
A FIRE ALARM SYSTEM

1 Supply,Installation,Testing & Commissioning of the Fire Alarm System consisting


of the following:

Multi Loop Microprocessor based xx loop (each loop shall be able to connect
minimum 125 detectors and 125 modules) intelligent ,analogue addressable type
fire alarm control panel with minimum 80 character LCD display, four access levels,
400 event historical logging, flash EPROM sufficient numbers of programmable
relay controls, 240 volts AC power supply, automatic battery charger, 24 volts
sealed lead acid batteries sufficient for 48 hours normal working and then be
capable of operating the system for 30 Minutes during an emergency
1.1 condition including all necessary software for remote programming of fire alarm
system through central control station. Panel should be integrated with phase-1A
panel. All the panel should be networkable on decicated fire alarm network
through Copper connectivity cable vendor to considerate the necessary
accessories , module to take all the panel in networking & to make the system
functional .
(Location - FACP panel will be located at Fire Control Room , Podium -1 & NTA
FACP will be kept in D wing Fire Control Room)

a 10 loops No. 1 540,000.00 540,000.00

b 6 loops No. 0 490,000.00 -

c 4 loops No. R.O. 400,000.00

d 2 loops No. 1 179,550.00 179,550.00

Fire Alarm System software capable of following functions : * Seamless integration


to BAS software * Uploading and downloading of information to FACP. * Graphics
1.2 including autocad drawings. * All Detector information and change of detector Set R.O. 110,400.00
setting Software as described above. All necessary License & software cost to be
included in the cost. (Location- Fire Control Room for Wing - D , Podium -1 )

1.3 Fire work station as per specification for the Above mention GUI software. No R.O. 41,400.00

Networkable Repeater panel with 40 character back lite super twist LCD display
1.4 with system function keys like system reset. Alarm acknowledge, Alarm Silence, 1 54,000.00 54,000.00
Trouble Acknowledge etc. Quoted price (Location of Repeater panel :Entrance No
Lobby of Each Tower , Main Security Gate )

1.5 Addressable Monitor modules monitor status like flow Switch,Tamper Switch in 75 1,214.00 91,050.00
Fire fighting & other applications as per specifications No.

Adressable Control modules for Fans Tripping & activating smoke extract fans
1.6 ,Elevator recall, fire damper, Pressurization fan Liftwell & Stairwell , PA system, etc. No. 40 2,187.00 87,480.00
As per specification

Wintergreen / Podium / FA PA System / BOQ 12 Contractor's Signature


ITEM. RATE (Rs.)
NO. ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL

Intelligent Analogue addressable photoelectric type smoke detector with


1.7 mounting base, LED, intelligent address complete as per specifications No. 0 2,611.00 -

1.8 Intelligent addressable rate of rise cum fixed temperature heat detector with 1317 2,074.00 2,731,458.00
mounting base, LED, intelligent address complete as per specifications No.

1.9 Intelligent addressable type Multicriteria type detector with mounting base, LED, 155 3,106.00 481,430.00
intelligent address Complete as per specifications(AFC & BFC) No.

1.10 Addressable Gas Leak Detector with required accessories such as power suuply if 0 1,701.00 -
required etc. No.

1.11 Standalone Gas Leak Detector with required accessories such as power suuply if R.O. 2,800.00
required etc. No.

1.12 Addressable Monitor modules monitor status like Gas leak Detector applications 0 1,795.00 -
as per specifications No.

1.13 Addressable type dual action manual Pull Station unit as per specifications No. 40 2,244.00 89,760.00

Surface mounted addressable type fully solid state circuitory dual tone Electronic
1.14 loud speaker type hooters with strobe lights of 110 Cd intensity as per No. 76 3,240.00 246,240.00
specifications

1.15 Addressable Fault Isolation Module as per specifications No. 109 2,250.00 245,250.00

1.16 Response Indicator as per Specification No. 0 150.00 -

1.17 Auto Dialer unit as per Specification No. 1 9,000.00 9,000.00

1.18 Magnetic Door Contact along with Monitor Modules as per Specification No. 0 2,100.00 -

1.19 Telephone jack along with Control Modules as per Specification No. 40 3,105.00 124,200.00

1.20 Telephone receiver as per Specification No. 1 10,900.00 10,900.00

Standalone UPS with 15 min. Battery backup. The Contractor to confirm the
capacity of UPS for giving power supply for all control room equipment in IBMS
room & Field levels as mention below such as workstation,System Integration
1.21 Unit,Gateways/Switch ,Fire panel & Workstation, PA System Rack, Hooter Power 0 315,000.00 -
supply,Workststions screens at all levels etc. Contractor should mention the Set.
capacity of the UPS selected with calculations at the time of quoting the tender
vendor to considered 20% spare capacity above actual load in the UPS. (UPS FOR
Each wing located at Fire Control Room , Podium -1 )

Wintergreen / Podium / FA PA System / BOQ 13 Contractor's Signature


ITEM. RATE (Rs.)
NO. ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL

Note - From UPS to floor level UPS DB & to Socket (UPS point) near to IBMS
equipments (field devices & Panels), Power supply etc. will be in electrical vendor
scope (Electrical Vendor to provide Cabling to socket ,DB etc.for IBMS field
equipments such as hooter power supply, workstations etc.) IBMS Vendor to share
the all the IBMS equipment required UPS power point layout to electrical vendor
for execution as per approved design.

TOTAL AMOUNT (A) 4,890,318.00

B PUBLIC ADDRESS SYSTEM

1 Supplying, Installing, Testing & Commissioning of the Public Address system


consisting of the following:

Audio amplifiers & Controllers Routers etc including all necessary control desk
and microprocessor based control unit with microphone, BGM, Call Station & PC
input including providing necessary rack for mounting the Amplifier.Contractor to
decide on the number, depending upon his amplifiers capacity. Vendor shall
1.1 calculate related controller, router, call station and keypad. (Contractor shall Set 1 27,000.00 27,000.00
furnish quantity and unit rate for each type of amplifier considered by him.)
(Location - FACP panel will be located at Fire Control Room , Podium -1 & NTA
FACP will be kept in D wing Fire Control Room). Amplifier selection shall be at full
load rating

1.2 6 W Ceiling Mounted Speaker with Multi Tapping Feature. Nos. 40 694.00 27,760.00

1.3 6 W Wall Mounted Box Type Vendal Proof Cabinet speakers with Multi Tapping 76 1,035.00 78,660.00
Feature. Nos.

1.4 15 W Wall Mounted Type Horn Type Speaker with Multi Tapping Feature. Nos. 178 1,715.00 305,270.00

1.5 Announcement console complete with microphone and Zone selection as per 0 72,900.00 -
Specifications ( Security Room,Each Fire Control Room At Podium Floor) Set

Integrated music source consisting of CD player, tape deck etc for Voice Evacuation
1.6 & Back Ground Music (should be capable of playing MP3,VCD,CD).as per Set 0 2,700.00 -
specifcation

1.7 Car Calling system as per specifcation Set R.O. 100,000.00

TOTAL AMOUNT (B) 438,690.00

C. CABLES & ACCESSORIES FOR FAS & PA

1 CABLES & ACCESSORIES FOR FAS

Wintergreen / Podium / FA PA System / BOQ 14 Contractor's Signature


ITEM. RATE (Rs.)
NO. ITEM DESCRIPTION UNIT QUANTITY AMOUNT
SUPPLY INSTALLATION TOTAL

Supplying, installing, testing and commissioning of FRLS armored cables with 2C X


1.5 sqmm annealed copper conductor having Cross linkable Fire retartdant Low
smoke insulation and FRLS inner and outer sheath. Armored cables should comply
to BS 6387 & BS 7846:2009 (latest edition). Armored cables should meet BS
1.1 7846:2009. Fire test as per BS 8434. Cable should be Fire RED in color, Cables shall 26903.45 90.00 2,421,310.50
be estimated per device basis as per the drawings. Cabling for response indicator/ Rmt.
Input & Output modules to field equipment/ power shall not be considered
seperatelyas device. The cost shall be included the all fixing accessories such as
clips, nails, screws,saddles Spacers ,heavy guage Junction Boxes & Glandings etc in
the unit rate estimated for per device as per specifcation.

Supplying, installing, testing and commissioning of FRLS armored cables 18 AWG,2


paired (4 nos conductor ) armored Sheilded twin twisted pairs ATC cable for fire
detection and alarm system with Cross linkable FRLS Outher Sheet,Conductor shall
have covered by an extruded layer of FRLS insulation and FRLS inner sheath.
1.2 Armored cables as per BS standards. The quoted rate shall be inclusive of suitable Rmt. 1975 134.00 264,650.00
saddles spacers, hardware,fire rated junction boxes/Back & Glands for termination
etc. complete as per specifcation. (Note:Contractor has to design the Qty as per
FACP & Repeater loctaion considered/desinged by them )

Supplying, installing, testing and commissioning of 2 mm thick GI trunking with


1.3 cover of the following sizes complete with angle iron supports/hanging
arrangement etc as per Specifcation

a. 40 x 300 x 40 Rmt. 50 1,530.00 76,500.00

b. 40 x 200 x 40 Rmt. 50 1,170.00 58,500.00

c. 25 x 150 x 25 Rmt. R.O. 990.00

2 CABLES & ACCESSORIES FOR PA SYSTEM

Supplying, installing, testing and commissioning of FRLS armored twisted,Sheilded


cables with 2 core annealed copper conductor having FRLS inner and outer sheath.
2xsheathed copper conductor armored ATC cables Twisted pair 2 core 1.5 sq mm
2.1 cables as per specifications Armored cables should comply to BS 7846:2009 (latest 5300 100.00 530,000.00
edition) ) Cables shall be estimated per Speaker basis as per the drawings. The cost Rmt.
shall be included the all fixing accessories such as clips, nails, screws,saddles
Spacers ,heavy guage junction Boxes & Glandings etc in the unit rate estimated for
per speaker with complete accessiories as per specfication

TOTAL AMOUNT (C) 3,350,960.50

TOTAL AMOUNT (A+B+C) 8,679,968.50

CGST 9% 781,197.17
SGST 9% 781,197.17

TOTAL AMOUNT INCLUDING TAXES (A+B+C) 10,242,362.83

The rate of each item of work for Fire Detection and Alarm System & PA shall also include the following :
1. All materials, fixing materials, accessories, appliances, tools and equipment.
2. Approved cover plates for inspection, junction and outlet boxes.
3. 2 mm thick outlet boxes and junction boxes.
4. All fixing accessories such as clips, nails, screws etc.
5. Providing and fixing approved saddles, hooks and grouting the same as required, in the case of all exposed cable work.
6. Embedding cables and accessories in wall, floors etc. during construction and / or cutting chases and making good as in the case of all concealed cables work.
7. Testing and commissioning of each device, circuit as per the requirements of NFPA 72, TAC, local authorities and to be witnessed by the PMC / Architect / Consultant.
Wintergreen / Podium / FA PA System / BOQ 15 Contractor's Signature