Flash Card - Aspe
Flash Card - Aspe
Front Back
What does the Manning Formula describe? The velocity of uniform flow in sloping drains.
If the storm piping is run separately from the sanitary piping, how
many traps are required before connection to the sanitary system or One.
combined sewer?
24 sq.ft To apply this for other rates of rainfall, multiply (24x4) and
At 4 in/hr rainfall, roughly how much area will result in 1 gpm of
divide by the new rate. (There should be tables for this in all
rainfall? plumbing codes)
Are vertical walls included in the calculation for stormwater runoff? Some codes require 50 percent of the area of vertical walls be
added to the horizontal drained area. Some do not.
Strainer, flashing ring (and gravel stop, where required) and drain
Name the three basic components of a roof drain: body or sump.
1 of 36
Siphonic roof drains, which restrict the air flow and swirl, allowing
Special pipe sizing applies to which type of roof drains and why? full use of the downspout for water only.
What minimum velocity is required for storm water piping? And 3 fps and 2 fps.
what is the minimum for sanitary piping?
For 256 FU or less, use 1000 SF. For greater than 256 FU, multiply
the FUs by 3.9 SF to convert to the equivalent drained area. For
What is the procedure for converting sanitary fixture unit loads to continuous or intermittent flow, multiply each GPM of flow by 24 SF
equivalent square feet of drained area? to convert to the equivalent drained area. Add the converted
sanitary equivalent drained area to the storm drainage area and use
table to get pipe size.
To collect and convey all excess storm water from the site to a
The primary objective of a site drainage system is...?
convenient and code-approved storage and/or discharge point.
Where should the subsoil pipe discharge? Into a sump. This sump is not required to be vented.
2 of 36
The exact amount of rainfall is never known, a hypothetical design
storm is used, hydraulic conditions at discharge points are
extremely variable, the percentage of rainfall that actually runs over
Name some unknown and unknowable factors that can complicate the ground, over the parking lot, and off the roof and enters the
storm water piping is the most variable factor of all. It varies with
site drainage design
the time of year, preceding rainfall conditions, soil characteristics,
type of site improvements, slope of ground, etc. Keep these things
in mind and use reasonable assumptions to obtain an economic and
adequate, code compliant site drainage system.
In terms of storm water, what is the “Rational Method” used for? To determine the amount of runoff created in a storm.
The time it takes for the entire area to start contributing to the flow
at a given point. The time of concentration for an inlet is time it
What is “the time of concentration?” takes for rainfall to accumulate and flow over the ground to the
inlet (sometimes called “inlet time.”)
The sum of the inlet time at the upper most inlet plus the time of
What is the time of concentration in a storm sewer system?
flow in the pipe using the average slope of the site.
3 of 36
Manholes: used where no surface water enters the system Drain
inlets: used in any point in paved areas where surface water enters
Name three types of drainage structures (for site drainage) the sewers Catch basins: which are similar to drain inlets but are
located in grassy or unimproved areas.
What type of pipe is not acceptable for storm sewers and why? Vitrified tile pipe because it is brittle and weak in larger diameters.
The water distribution system must always be designed on the basis The minimum pressure available.
of ____?
For building connections Between the building sewer and the first
downstream structure, cast iron soil pipe is recommended. This
pipe will better withstand shock loads from materials and
What are typical pipe types used for different areas of storm equipment likely to be encountered within close vicinity of
sewers? buildings, and has a large variety of fittings available. Reinforced
concrete pipe is most satisfactory for general use elsewhere, and is
often not readily available in sizes under 12 inches. PVC may also be
used. Check the code.
What is the maximum total movement that should be absorbed by 1-1/2 inches.
any expansion loop or offset?
What is one of the most persistent myths in plumbing related to Turning motion occurs at the elbows of an expansion loop. This is
thermal expansion? absolutely false.
What are two types of thermal expansion joints? The slip type and the bellows type.
The slip type joint requires packing and lubrication, and therefore
Describe some design considerations of a slip type joint. maintenance access. Guides must also be installed in the lines into
the slip joint to keep the pipe from bending and binding in the joint.
Does the bellows type joint satisfy the design limitation for The Bellows joint is very satisfactory for the 1-1/2 inch design
movement? What is the limitation and are guides required for a limitation on movement. Guides should be used with this type of
bellows joint? joint to prevent an offset movement.
4 of 36
To control piping expansion occurring with any change in
What is the main point behind supports, anchors, loops, guides and temperature and cause it to move in the direction desired by the
expansion joints? designer. If expansion in a branch is not adequately accounted for,
the branch may break causing flooding damage.
What is the Reynolds Number Range of critical velocity in a pipe? 2,000 to 4,000
In laminar flow, which has the largest effect on flow? (Pipe Viscosity significant, roughness negligible.
roughness or velocity?)
In turbulent flow, which has the largest effect on flow? (Pipe Roughness significant, velocity negligible.
roughness or velocity?)
How do you convert from feet of head to psi? Multiply the height by 0.433.
How do you convert from psi to feet of head? Multiply psi by 2.31.
Friction head loss is inversely proportional to...? The diameter of the pipe.
Friction head loss is directly proportional to...? The roughness and length of the pipe.
What equation is used to determine friction head loss? The Darcy Equation
What are the average values for the coefficient of friction for brass 0.02 for brass and copper, and 0.04 for steel
and copper and for steel?
5 of 36
What is the rule of thumb for determining equivalent length of Assume 50 percent of the developed length as an allowance for
piping in design phase? fittings and valves.
What other factor has an effect on pressure drop through a fitting? Velocity
What should always be of prime importance to the plumbing The maximum velocity of water flow in the piping during periods of
designer? peak demand.
What is water hammer? The noise created by pipes moving as a result of hydraulic shock.
If piping is restrained from moving, it will be subjected to what kind Compressive stress on a temperature rise, and tensile stress on a
of stresses? temperature drop.
When piping cannot move freely, where does failure due to thermal At the pipe joints and fittings, as the pipe itself can usually
expansion and contraction usually occur? withstand these stresses.
What two methods are usually employed to absorb pipe expansion 1. Expansion loops and offsets 2. Expansion joints
or contraction without danger to the piping?
Friction head is the pressure loss along the line of flow caused by
What is friction head and which equation do you use to find it? the friction produced by flowing water. You use Bernoulli’s equation
to solve for it.
6 of 36
1. The density and temperature of the fluid 2. The roughness of the
Name the four things that affect head loss due to friction pipe 3. The length of the run 4. The velocity of the fluid
What is a simplified expression for the increase in pressure caused The Jacowsky Formula
by hydraulic shock?
What is one device that was used as a means of controlling Air chambers. They often were improperly sized and almost always
hydraulic shock until it was deemed ineffective? lost their air charge.
What is an easy way to eliminate noise problems in plumbing? Maintain a flow velocity under 8 FPS in all parts of the pipe.
7 of 36
The flow that will occur if the outlets on all of the fixtures are
opened simultaneously (maximum possible flow). The flow that is
Define Maximum Flow, Average Flow, and Maximum Probable Flow: likely to occur in the piping under normal conditions. The maximum
flow that will occur in the piping under peak conditions (peak
demand or peak flow).
Give examples of continuous demand outlets and intermittent Continuous: hose bibbs, lawn irrigation, air-conditioning make up,
demand outlets. water cooling, etc. Intermittent: plumbing fixtures.
What was the name of the standard that first introduced fixture unit BMS 65, Methods of Estimating Loads in Plumbing Systems by Dr.
Roy B Hunter (published in the 1940s by the National Bureau of
tables? Standards).
So that the highest and most remote water outlet will have the
Why must friction head losses be limited in the water piping required minimum pressure for adequate flow during periods of
system? peak demand.
What is the maximum friction head loss that can be tolerated in the The difference between the pressure at the outlet of the meter
minus the flow pressure required at the fixture minus the pressure
system during peak demand? drop of any equipment or piping accessories in between.
In parallel circuits, the _____ in each branch is such that the _____ Flow, pressure drop.
_____ is also equal.
Why are minimum pipe sizes given in domestic water design? To maintain the velocity of the flow below the maximum 10 fps.
8 of 36
Step one: Draw a riser diagram of the complete water distribution
system showing floor to floor heights, the static pressure at each
floor, the minimum pressure required at the highest outlet and the
minimum available pressure. Step two: Mark the FU value at each
outlet and the sum of FUs for every section of the system. (Add FU
values, not GPM values, except for continuous demands). Step
three: Convert all FU values to GPM values and assign GPM to
Describe the procedure for sizing domestic water systems: continuous demand outlets. Step four: Determine the pressure
available for friction head loss and establish the uniform friction
head loss. Remember the furthest fixture may not always be the
controlling fixture. Step five: Use hydraulic tables or charts to select
sizes. The selection will be based on gpm demand, uniform friction
head loss, and max design velocity. Remember to make sure the
size selected doesn’t exceed the maximum allowable velocity.
Which formula are most all friction head loss tables and charts The Darcy-Weisbach formula.
based on?
What changes in plumbing design if a booster pump or The minimum available pressure is no longer fixed or unchangeable,
hydropneumatic tank are used? it can be selected and determined by the designer.
What are some economic considerations for a booster There are initial savings in piping and insulation costs versus
pump/hydropneumatic tank system? increased initial costs for equipment and increased operating costs.
A design criterion of 4-5 psi per 100 ft uniform friction head loss
generally results in an economically designed system, depending on
What uniform friction head loss (per 100 ft of pipe) is thought of as the length of pipe run. In many specific installations, it can be far
an economically designed booster/hydropneumatic system? more advantageous to design for much lower or much higher
pressure drops, depending on design conditions. Evaluate each
situation independently.
9 of 36
In a pump, if the direction of discharge from the rotating surface is
axial
inline with the shaft, the pump is which type?
Give an example of a centrifugal pump, an axial pump, and a An automobile water pump, a boat propeller, and the human heart
positive-displacement pump.
What is the working limit design pressure for standard plumbing 125 psi.
equipment to minimize the risk of explosion?
25-30 lbs higher than the system operating pressure (or 125 psi) to
avoid false opening and dripping due to normal pressure surges.
What can the pressure setting on the relief valve be set to? The pressure setting must be less than the maximum working
pressure of the materials in the system.
What is the first step in selecting a hot water heater? Knowing the required capacity.
When selecting a hot water heater, what cold inlet and rise 40 degree cold inlet, 100 degree F rise
temperatures are commonly used?
What is a good standard hot water temperature and why? 140F because it kills legionella and other harmful bacteria
When using a fuel fired water heater, you must always provide Combustion air
what?
10 of 36
No built in storage, designed to deliver full capacity rapidly and
continuously. Must have sufficient capacity to meet all demands
simultaneously. Require a high heat input to meet the required
Describe Instantaneous Water Heaters (application, pros, etc.) discharge rate and temperature of hot water. Best applied where
demands are level and constant, such as swimming pools,
dishwasher boosters, industrial processes. They heat the water
through conduction.
How should the instantaneous water heater be configured if the A straight-tube, floating head exchanger should be used in lieu of
characteristics of water are such that rapid scale deposits are the U-tube heater.
possible?
What is the minimum velocity that should be maintained through 4 fps. This will minimize the rate of scale formation in the tubes.
the tubes on an instantaneous water heater?
The heat transfer rate increases or decreases when water velocity increases.
increases in the tubes?
Fixture units. Peak demand for hot water using this method is two
What are the sizing of instantaneous hot water heaters most to three times actual demand, so it is recommended that usage
commonly based on? factors be applied to select the most economically sized
instantaneous hot water heater.
11 of 36
To smooth out peak demands on heating systems with large-volume
changes in hot water demand. When correct storage capacity is
What is the primary reason for selecting a storage type water combined with the correct recovery capacity and the proper size of
heater instead of instantaneous? heating medium control valve, substantial reduction of the peak
heating fluid demand can be realized.
Of the water stored in a storage hot water, what percentage is 70 percent, because the stored water is cooled by the entering cold
useable and why? water.
By what method does hot water supply piping (whether insulated or Convection, conduction, and radiation.
not) transfer heat to surrounding lower-temperature air?
12 of 36
Splashing, which is the main reason someone might want to alter
What does good air gap design avoid? the air gap.
13 of 36
An assembly consisting of two independently acting, internally
loaded check valves separated by a reduced-pressure zone. A
differential pressure relief valve is located within the reduced
pressure zone to maintain the reduced pressure and to discharge
water to the atmosphere in the event of device malfunction. Typical
Describe a reduced pressure backflow device. use is where the nonpotable water source is considered to be toxic
and capable of causing illness or death. For water systems that have
widely fluctuating water pressures of the RPZ, the RPZ can discharge
quite a large amount of water. A separate check valve installed just
upstream of the RPZ will relieve the situation and return the RPZ to
normal discharge.
The stack vent is the pipe from the topmost drainage branch
Define Stack Vent connection through the roof to atmosphere.
How high is a column of air that is equivalent to the static pressure 69.23 feet
exerted by 1 in water column?
What pressure variations must be sustained at the 2” fixture trap for 1” W.C.
100% safety factor?
When air flows in a pipe, a pressure loss occurs due to the friction
between the air and the pipe wall. This loss of pressure is expressed The Darcy Formula
by which formula?
At maximum design flow, water flows down the stack as a sheet of Jul-24
water occupying how much of the cross sectional area of the stack?
As water falls down the stack, it exerts frictional drag on the core of
Why must stacks be extended full size through the roof, and why air and as this air is dragged down, it must be replaced by an
may soil stacks not be reduced in size even though there is less load equivalent quantity of replacement air to avoid violent pressure
on the upper portions of the stack? fluctuations.
How are the rates of air discharge for a pressure relief vent stack Through tables.
sized?
14 of 36
What is the maximum length of vent piping for any particular size
with a maximum allowable pressure drop of 1 in w.c.: the The equivalent length.
developed length or the equivalent length? What’s the difference?
The principle of gravity circulation of air is utilized to keep the entire Foul odors, slime and fungi.
sanitary system free of what?
The stack vent may be connected with the vent stack before
extending through the roof or may be connected together with
Can other things connect into the stack vent? other stack vents or vent stacks in a vent header, and the vent
header may be extended through the roof as a single pipe.
What is any connection from the vent stack called? Branch vent.
An individual vent vents one fixture only and is seldom used unless
Define “individual vent.” the fixture is not part of a group.
A vent for two trapped fixtures on the same floor level (connecting
to a common vertical drain), or a horizontal branch drain for two
Define “common vent.” wall outlet fixtures. Keep in mind the maximum distance from the
trap to the vent.
15 of 36
The waste stack in this case acts as the waste stack and vent. No
offsets, water closets or urinals are included, each fixture connects
Describe “waste stack vent” separately, and fixtures must be of the same type. Some codes limit
this arrangement to three floors. This has special sizing tables and
the stack shall be the same size for its entire length.
What is the exception to the “one pipe diameter” slope of the vent
Water closets and other similar fixtures
opening and the trap?
This serves a drain line that has horizontal branches, and no food
waste grinders or chemical sinks can be included. This pipe carries
Describe “combination drain and vent”
air and water, and in some codes, the permitted sizes are one size
more than the calculated drain size. (Other codes use a table).
With respect to the horizontal axis, what degree can an offset be Less than 45 degrees. Any offset 45 degrees and greater is
and still be considered horizontal? considered a horizontal offset and sized as such.
How many branch intervals are permitted on a drainage stack for Two, and up to five in some codes.
each attendant vent stack, according to the CPD manual?
The vent stack should extend full size through the roof, connect to a
Where are the three places the vent stack can terminate? vent header, or connect to the stack vent of the drainage stack at
least 6” above the overflow of the highest fixture.
What is the size of the vent stack based on? What is it’s minimum The size is based on drainage fixture unit load and the developed
size? length. It should be not less than one-half of the waste stack size.
16 of 36
Within 10 feet of any door, window, or ventilation intake unless they
Vent terminals should not be located near what? Unless what? are extended at least 2ft above such openings.
Yes, but the terminal must turn down and be covered with a wire
Can a vent terminal be extended through a wall? How? What screen. It should never be located beneath a building overhang or
should you consider for placement? immediately adjacent to an exterior building wall.
Name the four alternate methods acceptable in lieu of individual Wet venting Stack venting Circuit and Loop Venting Combination
trap venting. waste and vent venting
What is the maximum distance of vent to trap on a 2” plumbing 60 inches, see table for other sizes.
line?
A fixture drain that slopes more than one pipe diameter between
Why must the vent pipe opening never be below the weir of the vent opening and trap weir has a greater tendency to self siphon
fixture trap? the trap seal than a fixture drain installed at a slope of not more
than one pipe diameter.
The lower end should connect to the drainage stack below the
Where should the relief vent connect? drainage branch connection, and the upper end should connect to
the vent stack at least 3 feet above floor level.
Suds flow down the stack and settle in the lower sections of the
In sanitary drainage systems, where do suds occur? drainage system and at any offset greater than 45 degrees in the
stack.
Air and water travel down the stack, the water passes through the
How do air and water affect suds in a drainage stack? suds without carrying them away, and air displaces the suds
through any available outlet (drains, branches, vents, etc.)
What happens with suds near the hydraulic jump or where relief Excessively high suds pressure can develop, blowing the seals off of
paths are not available? the traps.
17 of 36
Do vent pipe sizing tables generally account for the more
No.
demanding flow of suds?
Are suds more or less dense than air? More dense, 2 to 19 lb/ft^3 depending on the detergent.
For equal rates of flow and pressure, how must vent pipe diameter The vent pipe diameter for suds pressure relief flow must be from
for suds relief flow be sized compared to regular venting? 20 to 80 percent greater than for air flow.
Where does the suds pressure zone extend to at the base of a soil The suds pressure zone extends 40 stack diameters upward from
or waste stack? the base fitting.
The suds pressure zone extends 10 stack diameters from the base
Where does the suds pressure zone extend to at the horizontal fitting, and where an offset greater than 45 degrees in the
drain from the base of a stack? horizontal occurs, the pressure zone extends 40 stack diameters
upstream and 10 diameters downstream from the offset fitting.
The suds pressure zone extends the vent stack base connection
Where does the suds pressure zone extend to in a vent stack upward to the level of the suds pressure zone in the soil or waste
connected to a suds pressure zone? stack.
18 of 36
All the requirements for the proper design of the sanitary system
When designing sump or ejector vents, what requirements are are applicable, thus, the air must be conveyed by the vent piping at
applicable? the same rate as the maximum rate at which sewage enters or is
pumped out of the receiver.
What is the minimum vent size to allow for frost enclosure? 3 inches
Vent terminals should be no smaller than what? The stack served (1-1/2 inches minimum).
What is the telltale sign of an overloading BHP pump curve? When the BHP curve continues to increase with increased capacity
Why are pumps with non-overloading power curves advantageous? The drive is not overloaded under any operating condition.
When altering a pump impeller, what percent decrease can be For an average impeller, 20 percent of the original maximum
achieved without adverse effects? diameter.
19 of 36
What are the definitions of each of the pump affinity laws in terms 1) The capacity varies with the diameter 2) The head varies with the
square of the diameter 3) The brake horsepower varies with the
of IMPELLER DIAMETER? cube of the diameter
For multiple pump system proper operation, all pumps should have Continuously rising characteristic.
what type of curve?
For series operation, the pump capacities must be equal, but what Pump heads.
may have different values?
For parallel operation, the pump heads must be equal, but what Pump capacities.
may vary?
When selecting a centrifugal pump, in addition to determining the The system head/capacity curve to avoid possible future problems.
required head at the design capacity, it is very important to also The pump must be able of satisfying minimum and maximum
check what? requirements in addition to the design requirements.
On a pump curve, pump head (ft) is proportional to what? The ratio of the GPM squared
What does NPSHr vary with? The speed and capacity of the pump.
20 of 36
What is the benefit of operating pumps in parallel? To obtain greater capacities.
When is a good time to use two or more pumps in parallel? When the system demand varies greatly.
For series operation of two or more pumps, the combined The heads vertically at the same capacities. (100 GPM at 30‘ + 100
performance curve is obtained by adding what? GPM at 30‘ = 100 GPM at 60’)
For parallel operation of two or more pumps, the combined The capacities horizontally at the same heads. (100 GPM at 30‘ +
performance curve is obtained by adding what? 100 GPM at 30‘ = 200 GPM at 30’)
An ejector handles what? Sewage (ejector basin is airtight and requires venting)
A sump handles what? Clear waste water (sump basin not airtight, needs no venting)
What two types of lifting devices are employed for the automatic 1) Centrifugal pumps 2) Pneumatic ejectors
discharge of sump or ejector basin contents?
When the discharge rate is 100 GPM or less, when large solids must
be handled, where ground conditions are such that the space below
When are pneumatic-type ejectors commonly used? the floor is restricted, where compressed air is readily available, and
in explosion proof conditions.
Use the water supply fixture unit method to determine flow into
What is used to size the ejector pump? the receiver, then total FU is converted to GPM using a table.
Add the static head, measured from the low water line in the
How do you determine the head of the ejector pump? receiver up to the highest point pumped, and the friction head loss
in the discharge piping and fittings.
From the pump outlet to the highest point, it should be at least the
In an ejector system, how is the length of run measured and what same size as the pump discharge outlet. (after this point, the piping
its the minimum size? is sized as required for the gravity house drain)
What is the minimum run time on an ejector system to avoid 5 minutes of pump capacity between high and low water levels
excessive pump cycling?
21 of 36
The high water level should be at least 3 inches below the invert of
the entering piping to prevent backflow and allow air circulation.
In an ejector basin, the high and low water levels should be The low water level should be at least 6 inches above the bottom of
maintained where and why?
the basin to ensure the suction intake of the pump is covered by
water.
What does NFPA 14 address? Standard for the installation of Standpipe and Hose Systems
Ejector basins should not retain the waste discharge for a period 12 hours
exceeding how long?
When an ejector vent is connected to the building venting system, By converting the gpm discharge rate into FU.
how is the addtional load on the vent pipe calculated?
How many fixture units are equivalent to 1 gpm of pump discharge 2 FUs
(in an ejector system)?
Assign a size that is one-half the size of the subdrain discharge pipe
What is a good rule of thumb for ejector vent sizing? into the basin, or a minimum of 3 inches.
What should always be installed at the discharge of each pump A check valve and shutoff valve (the shutoff valve on the discharge
discharge line (sump/ejector basin)? side of the check valve so the check valve can be serviced)
What should always be provided to keep harmful debris away from A settling basin.
the pump in a sump basin?
By assigning a value of 2 gpm for each 100sf area where the soil is
How is the rate of discharge from a subsoil drainage system sandy and 1 gpm per 100sf for clay soils. Don’t forget to add the
calculated? additional flow rate of clear water wastes such as condensate
drains, etc.
For paved and impervious areas collected in a sump, how is runoff A value of 1 gpm for every 24 sf can be assigned for locations where
calculated? the annual rate of rainfall is 4in/hr
What three things make up the “fire triangle”? Oxygen, heat, and fuel.
22 of 36
Fire suppression systems put out fires by taking away one or more
How does a fire suppression system work against the “fire triangle”? elements from the fire triangle
What plays a role in determining whether or not fire sprinklers are Building height and use classification.
required?
Standard for the Installation of Sprinkler Systems (13D: one and two
What does NFPA 13 address?
family dwellings) (13R: residences up to and including 4 stories)
What does NFPA 20 address? Standard for the Installation of Stationary Pumps for Fire Protection
Standard for the Installation of Private Fire Service Mains and Their
What does NFPA 24 address? Appurtenances
What are the four authorities that may have jurisdiction regarding 1) State fire marshal 2) Local fire department 3) Building
fire sprinkler design? department 4) Insuring agency
What are the four common types of automatic water-based 1) Wet pipe 2) Dry pipe 3) Deluge 4) Preaction
sprinkler systems?
23 of 36
500 gpm for the hydraulically most remote standpipe, 250 gpm per
What are the minimum flow rates for Class I and Class III
additional standpipe, with the total not exceeding 1250 gpm, or
standpipes? 1000 gpm for fully sprinklered buildings
100 psi (not to exceed 175 psi at the top) at the outlet of the
hydraulically most remote 2-1/2” hose connection and 65 psi (not
What are the minimum pressure outlet requirements for to exceed 100 psi at the top) at the outlet of the hydraulically most
hydraulically calculated standpipe systems? remote 1-1/2” hose connection. Ensure these values with a
pressure regulating device or fire pump.
When the pressure in the fire sprinkler system drops below a set
What activates a fire pump? threshold which is typically the performance value of the jockey
pump.
What is the heat and water content of natural gas? 1,000 BTU/ft^3 and a low water content
540 BTU/ft^3 and some water content, which may cause corrosion
What is the heat content and water content of manufactured gas? problems
What is the name and heat content of the two types of LPG? Propane: 2,500 BTU/ft^3 and Butane: 3,175 BTU/ft^3
24 of 36
2 psi. Low pressure gas is less than 2 psi, usually no greater than 0.5
Pressure threshold is deemed “high pressure” for natural and
psi (14 in wc). Gas is distributed throughout the building at 0.5 psi
manufactured gas? and on occasion, 1 psi.
How are propane and butane made available? They come in cylinders at a pressure of 80 to 120 psi.
With regards to natural and manufactured gas and LPG, what is Natural and manufactured gas is lighter than air, LPG is heavier than
their density compared to air? air.
Black steel is preferred, brass and copper can be used when the gas
is not corrosive, stainless steel and corrugated stainless steel may
What is the preferred material for gas piping, and when and what also be used. Underground services 6” and larger can be cast iron,
other materials can be used? but it must be steel pipe entering the building. Don’t forget to use
plug or ball valves rated for gas service.
What is a special consideration for burying steel piping? Protect it with a corrosion-resistant material (bitumastic paint, etc.)
Their rules and regulations, the point at which the utility company’s
Before commencing design of the system, the engineer should work ends and the contractors work begins, BTU value and pressure
contact the local utility company to determine what? of gas supplied, any special requirements
What range should the total pressure drop fall within from the gas 0.2 to 0.5 in wc, never exceeding 10 percent of the available gas
meter to the farthest outlet? pressure.
All risers should be valved, and drips should be located at all low
points in the building and at the base of all risers. Connections from
What design considerations are there for gas piping within a the mains should be from the top or side whenever possible, if
building? impossible, a connection can me made from the bottom with either
a drip or a pitch down to the main in the branch piping. Each piece
of equipment should have a shutoff valve.
25 of 36
1) Allowable pressure drop from meter to farthest outlet 2) Demand
(load) in (ft^3/h) 3) Actual length of run (see NFPA 54 National Fuel
What five factors are involved in the sizing of gas systems? Gas Code for gas sizing tables) 4) Specific gravity of gas 5) Diversity
factor (or factor of usage) if allowed by code
1) The longest length method sizes the main from the meter to the
farthest gas user (stay constant along the maximum horizontal
What two methods of gas sizing may be used? length). The same maximum length can be used for branches. 2)
The branch length method sizes the branches (not the main) based
on their individual actual lengths from the meter.
Gases that are used as part of a healthcare procedure other than for
What is the definition of medical gases and can you name the 8 normal body functions. 1) Oxygen, 2) Medical Air 3) Nitrous Oxide
major gases? 4) Carbon dioxide 5) Nitrogen 6) Instrument Air 7) Vacuum and 8)
WAGD
What is the pressure, delivery rate, pressure drop, and static 50 psig pressure, 100 liters per minute (3.5 standard cfm, or scfm)
pressure for oxygen, nitrous oxide, medical air and carbon dioxide delivery, pressure drop of no more than 5 psi, and a static pressure
outlets? of 50-55 psig
What is the delivery rate, pressure drop, and static pressure for 140 liters per minute (5 standard cfm, or scfm) delivery, pressure
support outlets? drop of no more than 5 psi, and a static pressure of 160-185 psig
What is the delivery required for oxygen and medical air outlets 170 liters per minute (6 standard cfm) for a minimum of three
serving critical areas? seconds
26 of 36
Seamless, hard-drawn type K, L or M copper tube or stainless steel
What type of piping material is used for vacuum or WAGD medical
tube. For level 3 vacuum systems, schedule 40 wall pvc plastic may
gas? be used.
Med gas mains and branches: 1/2” Vacuum mains and branches:
What are minimum medical gas pipe sizes? 3/4” Drops to individual outlets/inlets: 1/2” Piping to alarm panels:
1/4”
In medical gas piping, how is diversity calculated? From simultaneous use factors given in a table.
How is maximum pressure drop calculated for a medical gas Identify the maximum pressure drop allowed for the specific gas
system? system, divide it by equivalent length, and multiply by 100.
The gravitational force induced by the slope of the drain and the
Flow in piping and open channels is caused by what? height of water in that drain.
What formula determines the velocity of uniform flow in sloping The Manning Formula
drains?
How is the quantity “rate of flow” expressed? Cross sectional area of flow times the average velocity.
The ratio of the cross sectional area of flow to the wetted perimeter
The hydraulic mean depth of flow or hydraulic radius is what ratio of pipe surface, expressed as D/4 where D is diameter in feet. It is
and what value? the same ratio for full and half flow.
What is the minimum velocity of flow to achieve scouring action in 2 fps, 4 fps, 3 fps. Dont forget to limit the length of runs for 1-1/2
piping? For keeping grease in suspension in greasy wastes? For and 2” pipe to maintain scouring action.
suspension in Storm Sewers?
The designer must know what as related to the sewer, water, and The actual elevation of all of the floors of the building.
gas inverts and locations?
27 of 36
What is the recommended value of n, the coefficient of roughness,
0.0145
for storm drains of all sizes?
For interior drainage systems, the minimum fixture drain size is The minimum size of the fixture trap (often given in a table)
what?
For interior drainage systems, the rate of flow in a fixture drain The same as the rate of flow discharged at the fixture outlet.
should be what?
A minimum of 1.5 times the indirect pipe size above the flood level
For an indirect waste, the discharge outlet should be what? of the receptacle.
Special wastes, tank overflows, tank emptying lines, releif valve Through an air break to an appropriate receptacle (floor drain or
discharges, etc. should discharge where and why? other) to prevent overpressurization of the drainage system.
What is a general term for any vertical line of soil or waste piping
that collects water and wastes from fixture drains and horizontal A Stack.
branch drains from two or more floors of a building?
28 of 36
Soil stacks collect wastes that contain fecal matter, and waste stacks
What is the difference between soil stacks and waste stacks? collect wastes that do not contain fecal matter (lavatories, sinks, etc)
The long radius tee-wye fitting gives the water a greater downward
What is one positive and one negative of a tee-wye fitting? component than a sanitary tee, but also has a greater probability of
siphoning the traps
What is the total recommended maximum permissible flow in a 7/24 of the total cross sectional area of the stack.
stack?
Does an interior drainage stack that offsets 45 degrees or less from No. Any more than a 45 degree offset requires sizing the offset as a
the vertical require a change in size? house drain.
House drains are designed to flow how full? 1/2 full to 3/4 full max under uniform flow conditions
3 in pipe and smaller: 1/4 in/ft 4-6 in pipe: 1/8 in/ft 8 in pipe and
What minimum slopes are required for building drains and why? larger: 1/16 in/ft to maintain 2 fps scouring action if low flow
fixtures are present, 1/4 in/ft for all is a good idea
29 of 36
How many fixture units are equivalent to 1 gpm continuous or 2 FUs, sump pumps, ejectors, air conditioning equipment, water
semicontinuous flow and what are examples of these types of flow? cooled, equipment, etc
At the upper portion of the pipe (above the 1/2 - 2/3 full mark)
because: 1) there is a lower chance of stoppages in the branch 2)
Branch connections to the house drain should be made where and there is less flow interference at the point of connection 3) When
why? there is no flow in the branch, the full area of the pipe is available to
relieve pneumatic pressure fluctuations in the house drain
What are the slopes of pipe inside the building that correspond to 2 1/4 in per foot for 3 in and smaller 1/8 in per foot for larger pipe all
fps velocity? elbows, taps, tees etc are tapped at a pitch of 1/4” per foot
A sanitary tee may be used in the vertical but what may not be used A double sanitary tee because the possibility of flow crossover and
excessive pressures when one branch is discharging and the other
in the vertical and why? isn’t are possible
The maximum length from the vent connection to any future drain To prevent a dead end where slime, sludge and fungi can grow, 2
outlet is required by code, why, how long is the distance (listed in feet, unless the piping must be extended to an accessible location
the book), and what’s the exception? for a cleanout
Any offset of the stack greater than what can cause hydraulic jump? 45 degrees
Not to the horizontal offset to the stack if at all possible, unless its
Where should and shouldn’t you connect branch connections to at least 10 pipe diameters downstream, and ideally 2 feet above the
stack offsets? offset or 2 feet below to avoid pressure fluctuations.
30 of 36
A water test upon completion of the rough piping and prior to
concealment of 10 ft wc minimum (except the topmost 10 feet of
pipe), not to exceed 100 ft wc. If system is higher than 100 feet, test
What are the testing procedures for the storm and sanitary system? plugs must be installed to facilitate testing, rarely are more than 7
stories tested at one time. A peppermint oil test may also be done
with 2 oz of peppermint oil and 10 qt boiling water, and searching
for peppermint smell at leaks, however it is difficult to pinpoint the
leak by this method
Yes, if a water test is not possible, at a pressure of 5 psi, are tests are
Is an air test acceptable for a storm and sanitary system? impractical and costly
What happens in a storm and sanitary system after it passes the A smoke pressure test is recommended with a smoke pressure of 1
water test? in wc to prove the system gas tight.
What is the specific weight of water? 62.4 lbs per cubic foot
What two factors go into determining the rate of discharge of storm Size of the area draining, and maximum rate of rainfall per hour.
water?
If maximum rainfall rate is 4 in.hr., how much surface area will result 24 sq ft.
in 1 gpm of collection?
Describe the process to convert sanitary fixture unit loads to <256 FU, use 1000 sq. ft. >256, multiply FU by 3.9 sq. ft. For
equivalent square feet of drained area. continuous or intermittent flow multiply gpm by 24 sq. ft.
For site drainage, what storm frequency should be used for an 10 years
average site?
The time it takes for rainfall to accumulate and flow over the ground
For site drainage, describe concentration time for an inlet. to the inlet.
What is the most satisfactory pipe material for storm sewers? Reinforced concrete
Name the two types of flow that occurs with water in a pipe. Laminar and turbulent
31 of 36
The sudden and rapid change in velocity of water, such as with a Hydraulic shock
quick closing valve, leads to what?
What type of check valve should be used on the discharge side of a Spring-loaded check valve
pump?
Fluids flowing around a short radius bend at a high velocity can Cavitation.
cause what?
How can most noise problems be avoided in a domestic water Maintain a velocity lower than 8 fps.
system?
What are the two methods used in the US for determining peak The empirical method and the method of probability.
demand of fixtures?
The practice of assigning fixture units to fixtures is based upon what
The method of probability.
method?
What is the maximum allowable pneumatic pressure fluctuation in 1" wc
a vent pipe?
In a multistory building with two or more branch intervals, where Below all drainage connections and preferrably at the top of the
should the vent stack connect to the drainage stack? horizontal drain immediately adjacent to the stack base fitting
The size of a vent stack should never be ______________ of the Less than 1/2
waste stack size.
Where should indirect waste drain to in relation to the receptacle 1.5 times the indirect pipe size above the flood level of the
that it's draining into? receptacle
Indirect waste is usually limited to…. sinks, lavatories, condensate drains, etc.
Do fixtures using discharging to indirect waste require traps? Vents? Yes traps, no vent unless indirect piping is over 100 ft.
Why should clean outs be provided often in indirect waste systems? Lower velocities result in more stoppages.
Pipe size, flow, and ratio (most authorities use 1/4 or 7/24) of cross-
What is stack capacity based on? sectional area of sheet of water to cross-sectional area of stack
What is hydraulic jump? The phenomenon of sudden rise in water at the base of a stack.
If a connection to a horizontal stack offset must be made, how far At least 10 pipe diameters downstream to avoid the hydraulic jump.
down the horizontal run should it be made?
What is the Manning Formula used for? To determine velocity of uniform flow in sloping drains.
What is the coefficient of roughness (n) for a plumbing sanitary 0.014: 1-1/2":n=.012, 2-3":n=0.013, 4":n=0.014, 5-6":n=0.015, 8
drain with pipe size 4" diameter? and larger: n=0.016 (use 0.0145 for storm)
32 of 36
What is the minimum velocity of flow required to achieve scouring 2, 4, and 3 fps, respectivly
in a drain line? Greasy waste? Storm drain?
Rate of flow in fixture drains is dependent on what two conditions? Minimum diameter of waste outlet and height of water above that
minimum diameter.
How is fixture unit flow rate calculated? Total discharge flow of fixture (gpm) divided by 7.5 gal/cu. ft.
How is uniform friction head loss calculated? total friction head loss divided by equivalent length of run x 100
What is the rule of thumb method to determine equivalent length? 1.5 x developed length
If the utility were to quote 50 psi available, what number should the 40 psi
designer use for pressure available?
What are the basic methods to increase water pressure to an Gravity tank, hydropneumatic tank, booster pump.
adequate level?
What type of valve was added to water heater piping to protect the A temperature and pressure (T&P) relief valve.
water heater against bursting or exploding?
What is the standard design working pressure for water heaters and 125 psi
storage tanks?
The pressure setting of a T&P valve must always be less than The maximum working pressure of the material in the system.
_____?
Do you consider heat loss of the return line when sizing a recirc No
pump?
Do you consider height of piping above the pump when sizing a No
recirc pump?
The unit increase in length of a material per 1 degree F increase in
Define coefficient of expansion. temperature.
What is the only thing that limits the amount of expansion that can Developed length of pipe available for expansion.
be accommodated in an expansion loop?
A sump pump handles storm water and other clear water discharge
What is the difference between a sump pump and an ejector? and a sewage ejector handles sewage.
Is a vent required on a sump basin or ejector basin? An ejector basin yes, a sump basin no.
What is the recommended design velocity to use while selecting an 5-10 fps
ejector pump?
33 of 36
When sizing an ejector basin, what minimum time should be 5 minutes
planned between high and low water levels?
What valves should be installed at the discharge of each ejector A check valve and shut-off valve.
pump?
What are the four types of automatic sprinkler systems? Wet pipe, dry pipe, deluge, and preaction.
What are the two types of flow alarms used in automatic sprinkler Vane type or pressure type and Water motor.
systems?
What classifies a type C fire? electrical
Large LPG tanks must be located ______. a. away from the building
in case of leaks b. near the appliances being served c. inside the a. away from the building in case of leaks
building in a fire-rated enclosure d. underground
Cost estimating is broken down to what two basic categories? Material costs and labor costs
What is the Manning Formula used to calculate? Determining the velocity of uniform flow in sloping drains.
What does R represent in the Manning Formula? Hydraulic radius = Area of flow/wetted perimeter = d/4
What pH level is neutral, acidic, and alkaline? 7 is neutral, lower is acidic, higher is alkaline (or basic)
34 of 36
which of the following is true for a fuel gas system? a. The flow rate
of an appliance is equal to the consumption divided by 1,000. b. a. The flow rate of an appliance is equal to the consumption divided
natural gas is stored on site in large tanks. c. Gas systems always by 1,000.
should be vented. d. Gas that is vented through regulators can
always discharge into occupied space.
In the table giving uniform flow velocity of drains at 1/4" slope, 0.707
multiply values by _____ to solve for a drain at 1/8".
What does ASTM stand for and what plumbing components do they Originally the American Society for Testing and Materials, piping
set standards for? and fittings.
What does ASME stand for and what plumbing components do they American Society of Mechanical Engineers, fixtures, drains, clean
set standards for? outs, some tubing, stainless steel piping.
What does ASSE stand for and what plumbing components do they American Society of Sanitary Engineers, Performance requirements
for backflow preventers, vacuum breakers, thermostatic mixing
set standards for? valves, pressure reducing valves, and some residential components.
What does AWWA stand for and what plumbing components do American Water Works Association, ductile iron pipe, double
they set standards for? detector check valves, disinfection of water mains and tanks.
What does ANSI stand for and what plumbing components do they American National Standards Institute, gas water heaters and
appliances, manually operated gas valves, corrugated steel gas
set standards for? piping, plastic plumbing fixtures, and toilet seats.
When sizing a house drain, how many drainage fixture units should 150 DFU (2 per every 1 gpm for sump pumps, ejectors, AC
be applied for a sump pump with a discharge rate of 75 rpm? equipment, etc.)
35 of 36
What is the Darcy Weisbach equation used to determine? Pressure loss
The Hazen-Williams equation is most often used for what plumbing Fire Protection
discipline?
How do you calculate head in a pumping system if PSI is known? PSI x Specific Gravity (usually 1.0) x 2.31
Regarding pump selection, what does NPSH stand for? Net Positive Suction Head
What is NPSHa? Net Positive Suction Head available, determined by the system.
Energy can no longer be transferred from the pump to the fluid due
Regarding pump selection, describe dead head. to no flow at maximum head, so it is transferred to heat and will
burn out a pump.
What is the rule of thumb for minimum flow of a pump? 25% of impeller size best efficiency point.
Series = Add Head; Parallel = Add Flow. With pumps in series, each
pump is sized for 1/2 the head but the same flow. With pumps in
What is the significance of SHPF (Sheep Have Pretty Farmers) parallel, the head is the same for each pump but the flow is
increased.
36 of 36