This test report summarizes electromagnetic compatibility (EMC) testing of uninterruptible power supply (UPS) models SRC10000UXI, SRC8000UXI, and SRC8000UXICH by American Power Conversion Corp. The UPS units were tested for emissions and immunity according to relevant standards. For emissions, the UPS met category C2 limits for conducted emissions on the main port and radiated emissions. For immunity, the UPS met performance criterion levels for electrostatic discharge, radiated radio frequency, electrical fast transients, surge immunity, conducted radio frequency disturbances, power frequency magnetic fields, and low frequency conducted disturbances. Photographs in the report documented the test configurations.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views

Ce Emc Test Report

This test report summarizes electromagnetic compatibility (EMC) testing of uninterruptible power supply (UPS) models SRC10000UXI, SRC8000UXI, and SRC8000UXICH by American Power Conversion Corp. The UPS units were tested for emissions and immunity according to relevant standards. For emissions, the UPS met category C2 limits for conducted emissions on the main port and radiated emissions. For immunity, the UPS met performance criterion levels for electrostatic discharge, radiated radio frequency, electrical fast transients, surge immunity, conducted radio frequency disturbances, power frequency magnetic fields, and low frequency conducted disturbances. Photographs in the report documented the test configurations.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 61

Reference No:90819401-E

Report No: T100201405-E

CE EMC
TEST REPORT
for

U.P.S.
Model : SRC10000UXI
Data Applies To : SRC10000UXICH ; SRC8000UXI ;
SRC8000UXICH
Brand Name : APC
Test Report Number:
T100201405-E

Issued for
American Power Conversion Corp.
85 Rangeway Road Building 2 North Billerica MA 01862 USA

Issued By:
Compliance Certification Services Inc.
Tainan Laboratory
No. 8, Jiu Cheng Ling, Jiaokeng Village, Sinhua
Township, Tainan Hsien 712, Taiwan R.O.C.
TEL: 886-6-580-2201
FAX: 886-6-580-2202
Issued Date: February 04, 2010

Note: This report shall not be reproduced except in full, without the written approval of Compliance
Certification Services Inc. This document may be altered or revised by Compliance Certification
Services Inc. personnel only, and shall be noted in the revision section of the document. The client
should not use it to claim product endorsement by TAF, NIST or any government agencies. The test
results in the report only apply to the tested sample.

Page 1 / 61
Reference No:90819401-E
Report No: T100201405-E

REVISION HISTORY

Issue
Rev. Revisions Effect Page Revised By
Date
00 August 22, 2009 Initial Issue ALL Selena.Chong

01 February 04, 2010 Update Applicant ALL Selena.Chong

Page 2
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

TABLE OF CONTENTS
1 TEST CERTIFICATION.................................................................................................... 4
2 TEST RESULT SUMMARY .............................................................................................. 5
3 EUT DESCRIPTION........................................................................................................... 6
4 TEST METHODOLOGY ................................................................................................... 7
4.1. DECISION OF FINAL TEST MODE................................................................................... 7
4.2. EUT SYSTEM OPERATION ............................................................................................... 7
5 SETUP OF EQUIPMENT UNDER TEST ........................................................................ 8
5.1. DESCRIPTION OF SUPPORT UNITS ................................................................................ 8
5.2. CONFIGURATION OF SYSTEM UNDER TEST............................................................... 9
6 FACILITIES AND ACCREDITATIONS ....................................................................... 10
6.1. FACILITIES ........................................................................................................................ 10
6.2. ACCREDITATIONS ........................................................................................................... 10
6.3. MEASUREMENT UNCERTAINTY.................................................................................. 10
7 EMISSION TEST .............................................................................................................. 11
7.1. CONDUCTED EMISSION MEASUREMENT.................................................................. 11
7.2. RADIATED EMISSION MEASUREMENT...................................................................... 19
8 IMMUNITY TEST ............................................................................................................ 27
8.1. GENERAL DESCRIPTION ................................................................................................ 27
8.2. GENERAL PERFORMANCE CRITERIA DESCRIPTION .............................................. 28
8.3. ELECTROSTATIC DISCHARGE (ESD)........................................................................... 29
8.4. RADIATED, RADIO-FREQUENCY, ELECTROMAGNETIC FIELD (RS) ................... 35
8.5. ELECTRICAL FAST TRANSIENT (EFT) ........................................................................ 39
8.6. SURGE IMMUNITY TEST ................................................................................................ 42
8.7. CONDUCTED RADIO FREQUENCY DISTURBANCES (CS) ...................................... 46
8.8. POWER FREQUENCY MAGNETIC FIELD .................................................................... 50
8.9. LOW-FREQUENCY CONDUCTED DISTURBANCES .................................................. 53
9 PHOTOGRAPHS OF THE TEST CONFIGURATION ............................................... 55

Page 3
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

2 TEST RESULT SUMMARY


EMISSION
Standard Item Result Remarks
Conducted (Main Port) PASS Meet category C2
EN 62040-2:2006 Conducted (Telecom port) N/A None
Radiated PASS Meet category C2

Standard Item Result Remarks


Meets the requirements of
IEC 61000-4-2: 1995+A1:1998+A2:2000 ESD PASS Performance Criterion B
Meets the requirements of
IEC 61000-4-3: 2006 RS PASS Performance Criterion A
Meets the requirements of
IEC 61000-4-4: 2004 EFT PASS Performance Criterion B
Meets the requirements of
IEC 61000-4-5:2005 Surge PASS Performance Criterion A
Meets the requirements of
IEC 61000-4-6:2007 CS PASS Performance Criterion A

Meets the requirements of


IEC 61000-4-8: 1993+A1:2000 PFMF PASS Performance Criterion A
Low-Frequency
Meets the requirements of
IEC 61000-2-2: 2002 Conducted PASS Performance Criterion A
Disturbances

NOTE: 1. The statements of test result on the above are decided by the request of test standard only; the
measurement uncertainties are not factored into this compliance determination.
2. The information of measurement uncertainty is available upon the customer’s request.

Page 5
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

3 EUT DESCRIPTION
Product U.P.S.
Model SRC10000UXI

Data Applies To SRC10000UXICH ; SRC8000UXI ; SRC8000UXICH

Brand Name APC


Applicant American Power Conversion Corp.
Manufacturer: Delta Electronics (Jiang Su), Ltd.
Housing material Metal
Serial Number N/A
Received Date August 19, 2009
Power Source AC I/P : 230V, 39A, 8888W, 50/60Hz
AC O/P : 230V, 35A, 8000W, 50/60Hz
RS-232 Cable Unshielded, 2.1 m, 1pcs
PARALLEL Cable Unshielded, 1.1 m, 1pcs
Note:
1. Client consigns only one model sample to test (Model Number: SRC10000UXI),
Therefore, the testing Lab. just guarantees the unit, which has been tested
2. The difference between of model numbers (list as below) are identical, just for marketing purpose only.

The difference model number

Output VA Charger Board


SRC10000UXI 10000 2 pcs
SRC10000UXICH 10000 1 pcs
SRC8000UXI 8000 2 pcs
SRC8000UXICH 8000 1 pcs

Page 6
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

4 TEST METHODOLOGY
4.1. DECISION OF FINAL TEST MODE

The EUT was tested together with the above additional components, and a configuration, which
produced the worst emission levels, was selected and recorded in this report.
The test configuration/ mode is as the following:

EMI Test Mode


1. AC Mode Full Load
2. DC Mode Half Load

EMS Test Mode


1. AC Mode Half Load

4.2. EUT SYSTEM OPERATION

1. Setup whole system for test completely as shown on setup diagram.


2. Turn on power.
3. Check the EUT function.
4. Start to test.

Page 7
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

5 SETUP OF EQUIPMENT UNDER TEST


5.1. DESCRIPTION OF SUPPORT UNITS

The EUT has been tested as an independent unit together with other necessary accessories or support
units. The following support units or accessories were used to form a representative test configuration
during the tests.

No. Product Manufacturer Model No. Certify No. Signal cable

1 PC HP d330uT DoC Power Cable, unshd, 1.5m


2 LCD Monitor BenQ FP731 DoC VGA Cable, shd, 1.8m
3 Keyboard HP KU-0316 DoC Keyboard Cable, shd, 1.9m
4 Mouse HP M-UV96 DoC Mouse Cable, shd, 1.8m
5 Battery N/A N/A DoC N/A
6 LOAD N/A N/A DoC N/A

No. Signal cable description

A Input Power Cable Unshielded, 2.0m, 1 pcs


B Output Power Cable Unshielded, 2.0m, 1 pcs, with two cores
C RS232 Cable Shielded, 2.1m, 1 pcs
D LAN Cable Unshielded, 1.0m, 1 pcs
E VGA Cable Shielded, 1.8m, 1 pcs, with two cores
F DC Cable Shielded, 1.1m, 1 pcs

Note:
1) All the equipment/cables were placed in the worst-case configuration to maximize the emission during the
test.
2) Grounding was established in accordance with the manufacturer’s requirements and conditions for the
intended use.

Page 8
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E
5.2. CONFIGURATION OF SYSTEM UNDER TEST

DE

C B

LCD PC EUT LOAD


Monitor
F
A
Battery
LOAD
Keyboard Mouse

AC Source

Page 9
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

6 FACILITIES AND ACCREDITATIONS


6.1. FACILITIES

All measurement facilities used to collect the measurement data are located at

No. 8, Jiu Cheng Ling, Jiaokeng Village,Sinhua Township, Tainan Hsien 712, Taiwan R.O.C.

The sites are constructed in conformance with the requirements of ANSI C63.4 and CISPR
Publication 22. All receiving equipment conforms to CISPR Publication 16-1, “Radio Interference
Measuring Apparatus and Measurement Methods.”

6.2. ACCREDITATIONS
Our laboratories are accredited and approved by the following approval agencies according to
ISO/IEC 17025.

USA FCC

Japan VCCI

Canada INDUSTRY CANADA

Taiwan TAF, BSMI

Europe TÜV NORD

Copies of granted accreditation certificates are available for downloading from our web site,
http://www.ccsemc.com.tw

6.3. MEASUREMENT UNCERTAINTY

Where relevant, the following measurement uncertainty levels have been estimated for tests
performed on the EUT as specified in CISPR 16-4-2:

Measurement Frequency Uncertainty

Conducted emissions 9kHz~30MHz ± 2.05 dB

Radiated emissions 30MHz ~1000MHz ± 2.39 dB

This uncertainty represents an expanded uncertainty expressed at approximately the 95%


confidence level using a coverage factor of k=2.

Page 10
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

7 EMISSION TEST
7.1. CONDUCTED EMISSION MEASUREMENT

7.1.1. LIMITS

(a) UPS of category C1 and C2


Table 1 – Limits of mains terminal interference voltage frequency range 0.15 MHz to 30 MHz for
category C1 UPS and category C2 UPS equipment.
Limits dB(μV)
Frequency range
Category C1 UPS Category C2 UPS
(MHz)
Quasi-peak Average Quasi-peak Average
0.15 to 0.50 66 to 56a 56 to 46a 79 66

0.50 -5b 56 46 73 60

5 to 30 60 50 73 60
a The limit decreases linearly with the logarlthm of the frequency.

b The lower limit shall apply at the transition frequency.

(b) UPS of category C3


Table 2 – Limits of mains terminal interference voltage frequency range 0.15 MHz to 30 MHz for
category C3 UPS equipment.
UPS rated output Limits dB(μV)
Frequency range
current
(MHz)
A Quasi-peak Average

0.15 to 0.50b 100 90

> 16-100 0.50 to 5.0b 86 76

5.0 to 30.0 90 to 70a 80 to 60a

0.15 to 0.50b 130 120

>100 0.50 to 5.0b 125 115

5.0 to 30.0 115 105


a The limit decreases linearly with the logarlthm of the frequency.

b The lower limit shall apply at the transition frequency.

Page 11
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

7.1.2. TEST INSTRUMENTS

Conducted Emission room


Name of Equipment Manufacturer Model Serial Number Calibration Due

NNLK NOV. 19, 2009


SCHWARZBECK 8121-446
L.I.S.N. 8121 For Insertion loss

Rohde & Schwarz ESH 3-Z5 840062/021 OCT. 05, 2009


TEST RECEIVER Rohde & Schwarz ESCS 30 100348 JUL. 13, 2010
BNC COAXIAL
CCS BNC50 11 JAN. 14, 2010
CABLE
e-3 (5.04211c)
Test S/W
R&S (2.27)

NOTE: The calibration interval of the above test instruments is 12 months and the calibrations are traceable
to NML/ROC and NIST/USA.

Page 12
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

7.1.3. TEST PROCEDURES


Procedure of Preliminary Test
z The EUT was set up as per the test configuration to simulate typical usage per the user’s manual.
When the EUT is a tabletop system, a wooden table with a height of 0.8 meters is used and is
placed on the ground plane as per EN 62040 (see Test Facility for the dimensions of the ground
plane used). When the EUT is a floor-standing equipment, it is placed on the ground plane which
has a 3-12 mm non-conductive covering to insulate the EUT from the ground plane.
z Support equipment, if needed, was placed as per EN 62040.
z All I/O cables were positioned to simulate typical actual usage as per EN 62040.
z The test equipment EUT installed received main power, 230V/50Hz, through a Line Impedance
Stabilization Network (LISN), which supplied power source and was grounded to the ground
plane.
z All support equipment received power from a second LISN.
z The EUT test program was started. Emissions were measured on each current carrying line of the
EUT using an EMI Test Receiver connected to the LISN powering the EUT.
z The Receiver scanned from 150kHz to 30MHz for emissions in each of the test modes.
z During the above scans, the emissions were maximized by cable manipulation.
z The test mode(s) described in Item 4.1 were scanned during the preliminary test.
z After the preliminary scan, we found the test mode described in Item 4.1 producing the highest
emission level.
z The EUT configuration and cable configuration of the above highest emission level were recorded
for reference of the final test.
Procedure of Final Test
z EUT and support equipment were set up on the test bench as per the configuration with highest
emission level in the preliminary test.
z A scan was taken on both power lines, Line 1 and Line 2, recording at least the six highest
emissions. Emission frequency and amplitude were recorded into a computer in which correction
factors were used to calculate the emission level and compare reading to the applicable limit. If
EUT emission level was less –2dB to the Average limit in Q.P. mode, then the emission signal was
re-checked using an Average detector.
z The test data of the worst-case condition(s) was recorded.

Page 13
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

7.1.4. TEST SETUP

Vert. reference plane

EMI receiver

40cm
EUT

80cm

LISN Reference ground plane

z For the actual test configuration, please refer to the related item – Photographs of the Test
Configuration.

7.1.5. DATA SAMPL

LISN Cable Meter Measured Over


Freq. Limits
Factor Loss Reading Level Limits Detector
(MHz) (dBuV)
(dB) (dB) (dBuV) (dBuV) (dBuV)
x.xx 9.6 0.1 15.7 25.4 46 -20.6 QP

REMARKS: 1. Level (dBuV) = Read Level (dBuV) + LISN Factor (dB) + Cable Loss (dB)
2. Over Limit value (dB) = Level (dBuV) – Limit Line (dBuV)

Page 14
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

7.1.6. TEST RESULTS

Resolution
Model No. SRC10000UXI 9 kHz
Bandwidth
Environmental
26 deg.C, 60 %RH Test Mode AC Mode Full Load
Conditions
Tested by Taiyu Cyu

LINE

REMARKS: 1. Level (dBuV) = Read Level (dBuV) + LISN Factor (dB) + Cable Loss (dB)
2. Over Limit value (dB) = Level (dBuV) – Limit Line (dBuV)

Page 15
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

Resolution
Model No. SRC10000UXI 9 kHz
Bandwidth
Environmental
26 deg.C, 60 %RH Test Mode AC Mode Full Load
Conditions
Tested by Taiyu Cyu

NEUTRAL

REMARKS: 1. Level (dBuV) = Read Level (dBuV) + LISN Factor (dB) + Cable Loss (dB)
2. Over Limit value (dB) = Level (dBuV) – Limit Line (dBuV)

Page 16
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

Resolution
Model No. SRC10000UXI 9 kHz
Bandwidth
Environmental
26 deg.C, 60 %RH Test Mode DC Mode Half Load
Conditions
Tested by Taiyu Cyu

LINE

REMARKS: 1. Level (dBuV) = Read Level (dBuV) + LISN Factor (dB) + Cable Loss (dB)
2. Over Limit value (dB) = Level (dBuV) – Limit Line (dBuV)

Page 17
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

Resolution
Model No. SRC10000UXI 9 kHz
Bandwidth
Environmental
26 deg.C, 60 %RH Test Mode DC Mode Half Load
Conditions
Tested by Taiyu Cyu

NEUTRAL

REMARKS: 1. Level (dBuV) = Read Level (dBuV) + LISN Factor (dB) + Cable Loss (dB)
2. Over Limit value (dB) = Level (dBuV) – Limit Line (dBuV)

Page 18
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

7.2. RADIATED EMISSION MEASUREMENT

7.2.1. LIMITS

Table 3 - Limits of radiated emission in the frequency range 30MHz to 1000 MHz
dBuV/m (At 10m)
FREQUENCY (MHz)
Category C1 UPS Category C2 UPS Category C3 UPS

30 to 230 30 40 50

230 to 1000 37 47 60

7.2.2. TEST INSTRUMENTS

Open Area Test Site # 5


Name of Equipment Manufacturer Model Serial Number Calibration Due

TEST RECEIVER Rohde & Schwarz ESCS 30 100294 FEB. 05, 2010

TYPE N COAXIAL
SUHNER CHA9513 5 AUG. 26, 2009
CABLE

BILOG ANTENNA Sunol sciences JB1 A070506-1 SEP. 16, 2009

Test Software EMI e-3 / AUDIX (5.04211c)

NOTE: The calibration interval of the above test instruments is 12 months and the calibrations are traceable
to NML/ROC and NIST/USA.

Page 19
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

7.2.3. TEST PROCEDURE


Procedure of Preliminary Test
z The equipment was set up as per the test configuration to simulate typical usage per the user’s
manual. When the EUT is a tabletop system, a wooden turntable with a height of 0.8 meters is
used which is placed on the ground plane. When the EUT is a floor-standing equipment, it is
placed on the ground plane which has a 3-12 mm non-conductive covering to insulate the EUT
from the ground plane.
z Support equipment, if needed, was placed as per EN 62040.
z All I/O cables were positioned to simulate typical usage as per EN 62040.
z The EUT received main power source from the outlet socket under the turntable. All support
equipment power received from another socket under the turntable.
z The antenna was placed at 10 meter away from the EUT as stated in EN 62040. The antenna
connected to the Spectrum Analyzer via a cable and at times a pre-amplifier would be used.
z The Analyzer / Receiver quickly scanned from 30MHz to 1000MHz. The EUT test program was
started. Emissions were scanned and measured rotating the EUT to 360 degrees and positioning
the antenna 1 to 4 meters above the ground plane, in both the vertical and the horizontal
polarization, to maximize the emission reading level.
z The test mode(s) described in Item 4.1 were scanned during the preliminary test:
z After the preliminary scan, we found the test mode described in Item 4.1 producing the highest
emission level.
z The EUT and cable configuration, antenna position, polarization and turntable position of the
above highest emission level were recorded for the final test.

Page 20
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E
Procedure of Final Test
z EUT and support equipment were set up on the turntable as per the configuration with highest
emission level in the preliminary test.
z The Analyzer / Receiver scanned from 30MHz to 1000MHz. Emissions were scanned and
measured rotating the EUT to 360 degrees, varying cable placement and positioning the antenna 1
to 4 meters above the ground plane, in both the vertical and the horizontal polarization, to
maximize the emission reading level.
z Recorded at least the six highest emissions. Emission frequency, amplitude, antenna position,
polarization and turntable position were recorded into a computer in which correction factors were
used to calculate the emission level and compare reading to the applicable limit and only Q.P.
reading is presented.
z The test data of the worst-case condition(s) was recorded.

Page 21
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

7.2.4. TEST SETUP

Test table &


Turntable
1m ~ 4m

EUT
Coaxial
Power 0.8 m Cable
Cable

10 m
Ground Plane
Filter
Filter
To Power Source
EMI
Receiver

z For the actual test configuration, please refer to the related item – Photographs of the Test
Configuration.

7.2.5. DATA SAMPL

Reading Antenna Cable Measure Over


Freq. Limit
Level Factor Loss Level Limit
(MHz) (dBuV/m)
(dBuV) (dB/m) (dB) (dBuV/m) (dBuV/m)
xx.xx 14.00 12 0.2 26.2 30 -3.80

REMARKS: 1.Level (dBuV/m) = Read Level (dBuV) + Antenna Factor (dB/m) + Cable loss (dB)
2.Over Limit value (dB) = Level (dBuV/m)-Limit Line(dBuV/m)

Page 22
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E
7.2.6. TEST RESULTS

Model No. SRC10000UXI Test Mode AC Mode Full Load


Environmental Resolution
29.8 deg.C, 50 % RH 120 kHz
Conditions Bandwidth
Antenna Pole Vertical Antenna Distance 10m
Detector Function Quasi-peak. Tested by Rock Kuo

REMARKS: 1.Level (dBuV/m) = Read Level (dBuV) + Antenna Factor (dB/m) + Cable loss (dB)
2.Over Limit value (dB) = Level (dBuV/m)-Limit Line(dBuV/m)

Page 23
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

Model No. SRC10000UXI Test Mode AC Mode Full Load


Environmental Resolution
29.8 deg.C, 50 % RH 120 kHz
Conditions Bandwidth
Antenna Pole Horizontal Antenna Distance 10m
Detector Function: Quasi-peak. Tested by: Rock Kuo

REMARKS: 1.Level (dBuV/m) = Read Level (dBuV) + Antenna Factor (dB/m) + Cable loss (dB)
2.Over Limit value (dB) = Level (dBuV/m)-Limit Line(dBuV/m)

Page 24
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

Model No. SRC10000UXI Test Mode DC Mode Half Load


Environmental Resolution
29.8 deg.C, 50 % RH 120 kHz
Conditions Bandwidth
Antenna Pole Vertical Antenna Distance 10m
Detector Function Quasi-peak. Tested by Rock Kuo

REMARKS: 1.Level (dBuV/m) = Read Level (dBuV) + Antenna Factor (dB/m) + Cable loss (dB)
2.Over Limit value (dB) = Level (dBuV/m)-Limit Line(dBuV/m)

Page 25
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

Model No. SRC10000UXI Test Mode DC Mode Half Load


Environmental Resolution
29.8 deg.C, 50 % RH 120 kHz
Conditions Bandwidth
Antenna Pole Horizontal Antenna Distance 10m
Detector Function Quasi-peak. Tested by Rock Kuo

REMARKS: 1.Level (dBuV/m) = Read Level (dBuV) + Antenna Factor (dB/m) + Cable loss (dB)
2.Over Limit value (dB) = Level (dBuV/m)-Limit Line(dBuV/m)

Page 26
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8 IMMUNITY TEST
8.1. GENERAL DESCRIPTION

Product Standard Test Type Minimum Requirement


IEC 61000-4-2 Electrostatic Discharge – ESD:
4,8,15 kV air discharge; 2,4,8 kV Contact discharge,
Performance Criterion B
IEC 61000-4-3 Radio-Frequency Electromagnetic Field
Susceptibility Test – RS:
10 V/m for 80~1000MHz;
Performance Criterion A
IEC 61000-4-4 Electrical Fast Transient/Burst - EFT,
Power line: 4kV , Signal line: 2kV,
Performance Criterion B
Basic Standard,
Specification, and IEC 61000-4-5 Combination Wave
Performance 1.2/50 us Open Circuit Voltage
Criterion 8/20 us Short Circuit Current
required Power line ~ line to line: 2 kV
line to ground: 4 Kv
Performance Criterion B
IEC 61000-4-6 Conducted Radio Frequency Disturbances Test –CS:
0.15 ~ 80 MHz, 10Vrms, 80% AM, 1kHz,
Performance Criterion A
IEC 61000-4-8 Power frequency magnetic field immunity test
50Hz, 30A/m
Performance Criterion A
IEC 61000-2-2 Low-Frequency Conducted Disturbances
140~360Hz,10V
Performance Criterion A

Page 27
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.2. GENERAL PERFORMANCE CRITERIA DESCRIPTION

Criteria A: The apparatus shell continues to operate as intended without operator intervention. No
degradation of performance or loss of function is allowed below a performance level
specified by the manufacturer, when the apparatus is used as intended. The performance
level may be replaced by a permissible loss of performance. If the manufacturer does not
specify the minimum performance level or the permissible performance loss, then either of
these may be derived from the product description and documentation, and by what the
user may reasonably expect from the equipment if used as intended.
Criteria B: After test, the apparatus shell continues to operate as intended without operator
intervention. No degradation of performance or loss of function is allowed, after the
application of the phenomenon below a performance level specified by the manufacturer,
when the apparatus is used as intended. The performance level may be replaced by a
permissible loss of performance.
During the test, degradation of performance is however allowed. However, no change of
operating state if stored data is allowed to persist after the test. If the manufacturer does
not specify the minimum performance level or the permissible performance loss, then
either of these may be derived from the product description and documentation, and by
what the user may reasonably expect from the equipment if used as intended.
Criteria C: Temporary loss of function is allowed, provided the functions is self-recoverable or can be
restored by the operation of controls by the user in accordance with the manufacturer
instructions.
Functions, and/or information stored in non-volatile memory, or protected by a battery
backup, shall not be lost.

Page 28
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.3. ELECTROSTATIC DISCHARGE (ESD)

8.3.1. TEST SPECIFICATION

Basic Standard: EN 61000-4-2

Discharge Impedance: 330 ohm / 150 pF


Discharge Voltage: Air Discharge: 4; 8; 15 kV (Direct)
Contact Discharge: 2 ; 4 ; 8 kV (Direct/Indirect)
Polarity: Positive & Negative

Number of Discharge: Minimum 10 times at each test point


Discharge Mode: Single Discharge
1 second minimum

8.3.2. TEST INSTRUMENT

IMMUNITY SHIELDED ROOM


Name of Equipment Manufacturer Model Serial Number Calibration Due
ESD Simulator NoiseKen ESS-2002 ESS0523940 AUG. 20, 2009

NOTE: The calibration interval of the above test instruments is 12 months and the calibrations are traceable to
NML/ROC and NIST/USA.

Page 29
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.3.3. TEST PROCEDURE

The discharges shall be applied in two ways:

a) Contact discharges to the conductive surfaces and coupling planes:


The EUT shall be exposed to at least 200 discharges, 100 each at negative and positive polarity, at
a minimum of four test points. One of the test points shall be subjected to at least 50 indirect
discharges to the center of the front edge of the Horizontal Coupling Plane (HCP). The remaining
three test points shall each receive at least 50 direct contact discharges. If no direct contact test
points are available, then at least 200 indirect discharges shall be applied in the indirect mode.
Test shall be performed at a maximum repetition rate of one discharge per second.
b) Air discharges at slots and apertures and insulating surfaces:
On those parts of the EUT where it is not possible to perform contact discharge testing, the
equipment should be investigated to identify user accessible points where breakdown may occur.
Such points are tested using the air discharge method. This investigation should be restricted to
those area normally handled by the user. A minimum of 10 single air discharges shall be applied
to the selected test point for each such area.

The basic test procedure was in accordance with IEC 61000-4-2:


a) The EUT was located 0.1 m minimum from all side of the HCP (dimensions 1.6m x 0.8m).
b) The support units were located another table 30 cm away from the EUT, but direct support unit
was/were located at same location as EUT on the HCP and keep at a distance of 10 cm with EUT.
c) The time interval between two successive single discharges was at least 1 second.
d) Contact discharges were applied to the non-insulating coating, with the pointed tip of the
generator penetrating the coating and contacting the conducting substrate.
e) Air discharges were applied with the round discharge tip of the discharge electrode approaching
the EUT as fast as possible (without causing mechanical damage) to touch the EUT. After each
discharge, the ESD generator was removed from the EUT and re-triggered for a new single
discharge. The test was repeated until all discharges were complete.
f) At least ten single discharges (in the most sensitive polarity) were applied at the front edge of each
HCP opposite the center point of each unit of the EUT and 0.1 meters from the front of the EUT.
The long axis of the discharge electrode was in the plane of the HCP and perpendicular to its front
edge during the discharge.
g) At least ten single discharges (in the most sensitive polarity) were applied to the center of one
vertical edge of the Vertical Coupling Plane (VCP) in sufficiently different positions that the four
faces of the EUT were completely illuminated. The VCP (dimensions 0.5m x 0.5m) was placed
vertically to and 0.1 meters from the EUT.

Page 30
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.3.4. TEST SETUP

10 cm VCP

0.5 mm Thick
Support Insulator EUT
470 kΩ
units

30 cm

Wooden Table
470 kΩ HCP Wooden Table 470 kΩ 0.8 m

Ground

z For the actual test configuration, please refer to the related item – Photographs of the Test
Configuration.

NOTE:
TABLE-TOP EQUIPMENT
The configuration consisted of a wooden table 0.8 meters high standing on the Ground Reference Plane.
The GRP consisted of a sheet of aluminum at least 0.25 mm thick, and 2.5 meters square connected to the
protective grounding system. A Horizontal Coupling Plane (1.6m x 0.8m) was placed on the table and
attached to the GRP by means of a cable with 940k ohm total impedance. The equipment under test, was
installed in a representative system as described in section 7 of EN 61000-4-2, and its cables were placed
on the HCP and isolated by an insulating support of 0.5 mm thickness. A distance of 1 meter minimum
was provided between the EUT and the walls of the laboratory and any other metallic structure.

FLOOR-STANDING EQUIPMENT
The equipment under test was installed in a representative system as described in section 7 of IEC
61000-4-2, and its cables were isolated from the Ground Reference Plane by an insulating support of 0.1
meter thickness. The GRP consisted of a sheet of aluminum that is at least 0.25 mm thick, and 2.5 meters
square connected to the protective grounding system and extended at least 0.5 meters from the EUT on all
sides.

Page 31
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.3.5. TEST RESULTS

Temperature 24 oC Humidity 40 % RH
Pressure 1018 mbar Tested By Agun Huang
Required Passing Performance Criterion B

Air Discharge
Test Levels Results
Test Points Performance
± 4 kV ± 8 kV ± 15 kV Pass Fail Criterion
Observation
Front A B C Note 1 2 3

Contact Discharge
Test Levels Results
Test Points Performance
± 2 kV ± 4 kV ± 8 kV Pass Fail Criterion
Observation
Front A B C Note 1 2 3
Back A B C Note 1 2 3
Left A B C Note 1 2 3
Right A B C Note 1 2 3
Top A B C Note 1 2 3
Please refer to ESD test photo on next page for detail discharge point

Discharge To Horizontal Coupling Plane


Test Levels Results
Side of EUT Performance
± 2 kV ± 4 kV ±8 kV Pass Fail Criterion
Observation
Front A B C Note 1 2 3
Back A B C Note 1 2 3
Left A B C Note 1 2 3
Right A B C Note 1 2 3

Discharge To Vertical Coupling Plane


Test Levels Results
Side of EUT Performance
± 2 kV ± 4 kV ±8kV Pass Fail Criterion
Observation
Front A B C Note 1 2 3
Back A B C Note 1 2 3
Left A B C Note 1 2 3
Right A B C Note 1 2 3

NOTE:
1. Performance criteria A for immunity tests with phenomena of a continuous nature.
2. Performance criteria B for immunity test with phenomena of a transient nature.
3. Performance criteria C for immunity test with power interruptions, function loss and voltage dips
exceeding a certain period of time.

Page 32
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

The Photo for Discharge Points of EUT

Page 33
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

Page 34
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.4. RADIATED, RADIO-FREQUENCY, ELECTROMAGNETIC FIELD (RS)

8.4.1. TEST SPECIFICATION

Basic Standard: EN 61000-4-3

Frequency Range: 80 MHz ~1000 MHz,

Field Strength: 800~1000MHz; 10 V/m with 80% AM. 1kHz Modulation.

Modulation: 1kHz Sine Wave, 80%, AM Modulation

Frequency Step: 1 % of preceding frequency value

Polarity of Antenna: Horizontal and Vertical

Test Distance: 3m

Antenna Height: 1.5m

8.4.2. TEST INSTRUMENT

RS Chamber
Name of Equipment Manufacturer Model Serial Number Calibration Due
Computer SYNNEX BTO -LMIW300 - GB A41202-0031 N.C.R.
ETL13071994430236
LCD Monitor Acer AL1715sm N.C.R.
6RH01
Keyboard SYNNEX 5211A G4430091266 N.C.R.
Amplifier
Freq. Range :80MHz ~ AR 150W1000M3 310037 DEC. 04 , 2009
1GHz
Amplifier
Freq. Range :0.8MHz ~ AR 60S1G3M3 310102 DEC. 04 , 2009
3GHz
RF TEST Controller
AR SC1000M1 310126 DEC. 05 , 2009
Freq. Range :~18GHz
Digital SIGNAL
HP ESG-D3000A US36260655 DEC. 29, 2009
GENERATOR
RF
BOONTON 4232A-01-02 122202 DEC. 30, 2009
Power Meter
Log – Periodic Antenna AR AT5080 309817 N.C.R.
RF Communications test
HP 8920A 3412A04298 DEC. 22, 2009
set
Test S/W RS SW1005 R1_4

NOTE: 1.The calibration interval of the above test instruments is 12 months and the calibrations are traceable
to NML/ROC and NIST/USA.
2. N.C.R.= No Calibration Required.

Page 35
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.4.3. TEST PROCEDURE

The test procedure was in accordance with EN 61000-4-3


a) The testing was performed in a fully anechoic chamber. The transmit antenna was located at a
distance of 3 meters from the EUT.
b) The frequency range is swept from 80 MHz to 1000 MHz, with the signal 80% amplitude
modulated with a 1kHz sine-wave. The rate of sweep did not exceed 1.5 x 10 -3 decade/s, where
the frequency range is swept incrementally, the step size was 1% of preceding frequency value.
c) The dwell time at each frequency shall be not less than the time necessary for the EUT to be able
to respond.
e) The test was performed with the EUT exposed to both vertically and horizontally polarized fields
on each of the four sides.

Page 36
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.4.4. TEST SETUP

3 meter
9x6x6
EUT & Support
Units

1.5 meter
0.8m

Signal EUT Monitoring by


Power Amp
Generator using a camera

PC Controller to
control S.G. & PA as
well as forward
power Control Room

z For the actual test configuration, please refer to the related item – Photographs of the Test
Configuration.

NOTE:
TABLETOP EQUIPMENT
The EUT installed in a representative system as described in section 7 of EN 61000-4-3 was placed on a
non-conductive table 0.8 meters in height. The system under test was connected to the power and signal
wire according to relevant installation instructions.

FLOOR STANDING EQUIPMENT


The EUT installed in a representative system as described in section 7 of IEC 61000-4-3 was placed on a
non-conductive wood support 0.1 meters in height. The system under test was connected to the power and
signal wire according to relevant installation instructions.

Page 37
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.4.5. TEST RESULTS

Temperature 24 oC Humidity 42% RH


Pressure 1032 mbar Tested By Agun Huang
Dwell Time 3 sec.
Required Passing Performance Criterion A

Field
Frequency
Polarity Azimuth Strength Observation Result
(MHz)
(V/m)
80 ~ 1000 V&H 0 10 Note 1 2 3 A PASS
80 ~ 1000 V&H 90 10 Note 1 2 3 A PASS
80 ~ 1000 V&H 180 10 Note 1 2 3 A PASS
80 ~ 1000 V&H 270 10 Note 1 2 3 A PASS

NOTE:
1. Performance criteria A for immunity tests with phenomena of a continuous nature.
2. Performance criteria B for immunity test with phenomena of a transient nature.
3. Performance criteria C for immunity test with power interruptions, function loss and voltage dips
exceeding a certain period of time.

Page 38
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.5. ELECTRICAL FAST TRANSIENT (EFT)

8.5.1. TEST SPECIFICATION

Basic Standard: EN 61000-4-4

Test Voltage: Power Line: 4 kV


Signal/Control Line: 2 kV
Polarity: Positive & Negative

Repetition Rate: 5 kHz

Impulse Wave-shape: 5/50 ns

Burst Duration: 15 ms

Burst Period: 300 ms

Test Duration: Not less than 1 min.

8.5.2. TEST INSTRUMENT

Immunity Shield Room

Name of Equipment Manufacturer Model Serial Number Calibration Due

Computer IBM M/T 8183 - ICV 99BG137 N.C.R.


VGA Monitor Acer 1555 917160230584200572P5C431 N.C.R.
Keyboard HP KB - 0133 B69360MGAPEOK5 N.C.R.
EMC Pro
IMMUNITY TEST KeyTek EMCpro 0312231 DEC. 28, 2009
SYSTEM
Test S/W CE Ware 3.00b

NOTE: 1. The calibration interval of the above test instruments is 12 months and the calibrations are traceable
to NML/ROC and NIST/USA.
2. N.C.R.= No Calibration Required.

8.5.3. TEST PROCEDURE


a) Both positive and negative polarity discharges were applied.
b) The length of the “hot wire” from the coaxial output of the EFT generator to the terminals on the
EUT should not exceed 1 meter.
c) The duration time of each test sequential was 1 minute.
d) The transient/burst waveform was in accordance with EN 61000-4-4, 5/50ns.

Page 39
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.5.4. TEST SETUP

z For the actual test configuration, please refer to the related item – Photographs of the Test
Configuration.

NOTE:
TABLETOP EQUIPMENT
The configuration consisted of a wooden table (0.8 m high) standing on the Ground Reference Plane. The
GRP consisted of a sheet of aluminum (at least 0.25 mm thick and 2.5 m square) connected to the protective
grounding system. A minimum distance of 0.5m was provided between the EUT and the walls of the
laboratory or any other metallic structure.

FLOOR STANDING EQUIPMENT


The EUT installed in a representative system as described in section 7 of IEC 61000-4-4 and its cables, were
isolated from the Ground Reference Plane by an insulating support that is 0.1 meter thick. The GRP
consisted of a sheet of aluminum (at least 0.25 mm thick and 2.5 m square) connected to the protective
grounding system.

Page 40
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.5.5. TEST RESULTS

Temperature 24 oC Humidity 42% RH


Pressure 1032 mbar Tested By Agun Huang
Required Passing Performance Criterion B

POWER
Test Level Performance
Test Point Polarity Observation Result
(kV) Criterion
L +/- 4kV A B C Note 1 2 3 A PASS

N +/- 4kV A B C Note 1 2 3 A PASS

PE +/- 4kV A B C Note 1 2 3 A PASS

L+ N +/- 4kV A B C Note 1 2 3 A PASS

L + PE +/- 4kV A B C Note 1 2 3 A PASS

N + PE +/- 4kV A B C Note 1 2 3 A PASS

L+ N + PE +/- 4kV A B C Note 1 2 3 A PASS

SIGNAL
Test Level Performance
Test Point Polarity Observation Result
(kV) Criterion
Ethernet Cable +/- 2kV A B C Note 1 2 3 A PASS

Characteristics of the fast transient/burst generator


Burst Burst Repetition
Rise time Duration
duration Period Rate
+ + + +
15 ms_ 20% 300 ms _ 20% 5 kHz 5 ns _ 30% 50 ns _ 30%

NOTE:
1. Performance criteria A for immunity tests with phenomena of a continuous nature.
2. Performance criteria B for immunity test with phenomena of a transient nature.
3. Performance criteria C for immunity test with power interruptions, function loss and voltage dips
exceeding a certain period of time.

Page 41
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.6. SURGE IMMUNITY TEST


8.6.1. TEST SPECIFICATION

Basic Standard: EN 61000-4-5


Wave-Shape: Combination Wave
1.2/50 us Open Circuit Voltage
8/20 us Short Circuit Current
Test Voltage: Power line ~ line to line: 2 kV
line to ground: 4 kV
Generator Source Impedance: 2 ohm / 12 ohm
Polarity: Positive/Negative
Phase Angle: 0 / 90 / 180 / 270
Pulse Repetition Rate: 2 times / min. (minimum)
Number of Tests: 5 positive and 5 negative at selected points

8.6.2. TEST INSTRUMENT

Immunity Shield Room

Name of Equipment Manufacturer Model Serial Number Calibration Due

Computer IBM M/T 8183 - ICV 99BG137 N.C.R.


VGA Monitor Acer 1555 917160230584200572P5C431 N.C.R.
Keyboard HP KB - 0133 B69360MGAPEOK5 N.C.R.
EMC Pro
IMMUNITY TEST KeyTek EMCpro 0312231 DEC. 28, 2009
SYSTEM
Test S/W CE Ware 3.00b

NOTE: 1. The calibration interval of the above test instruments is 12 months and the calibrations are traceable
to NML/ROC and NIST/USA.
2. N.C.R.= No Calibration Required.

Page 42
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.6.3. TEST PROCEDURE

a) For EUT power supply:


The surge is applied to the EUT power supply terminals via the capacitive coupling network.
Decoupling networks are required in order to avoid possible adverse effects on equipment not
under test that may be powered by the same lines, and to provide sufficient decoupling impedance
to the surge wave. The power cord between the EUT and the coupling/decoupling networks was
shorter than 2 meters in length.
b) For test applied to unshielded un-symmetrically operated interconnection lines of EUT:
The surge was applied to the lines via the capacitive coupling. The coupling / decoupling
networks didn’t influence the specified functional conditions of the EUT. The interconnection line
between the EUT and the coupling/decoupling networks was shorter than 2 meters in length.
c) For test applied to unshielded symmetrically operated interconnection / telecommunication lines
of EUT:
The surge was applied to the lines via gas arrestors coupling. Test levels below the ignition point
of the coupling arrestor were not specified. The interconnection line between the EUT and the
coupling/decoupling networks was shorter than 2 meters in length.

Page 43
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.6.4. TEST SETUP

To AC
Surge Immunity EUT
Source
Test &
Support Units

0.8m

Controller Computer

z For the actual test configuration, please refer to the related item – Photographs of the Test
Configuration.

Page 44
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.6.5. TEST RESULTS

Temperature 24 oC Humidity 42% RH


Pressure 1032 mbar Tested By Agun Huang
Required Passing Performance Criterion B

AC
Test Level Performance
Test Point Polarity Observation Result
(kV) Criterion
L –N +/- 2kV A B C Note 1 2 3 A PASS

L – PE +/- 4kV A B C Note 1 2 3 A PASS

N – PE +/- 4kV A B C Note 1 2 3 A PASS

Repetition Waveform
Phase shifting Coupling Rate
Rate parameter
Combine Wave
1.2μs/50μs 5 times
0°、90°、180°、270° 30 sec 8μs /20μs
Impedance Each Angle
2 Ω / 12 Ω and Polarity

NOTE:
1. Performance criteria A for immunity tests with phenomena of a continuous nature.
2. Performance criteria B for immunity test with phenomena of a transient nature.
3. Performance criteria C for immunity test with power interruptions, function loss and voltage dips
exceeding a certain period of time.

Page 45
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.7. CONDUCTED RADIO FREQUENCY DISTURBANCES (CS)

8.7.1. TEST SPECIFICATION

Basic Standard: EN 61000-4-6

Frequency Range: 0.15 MHz ~ 80 MHz

Field Strength: 10 Vrms

Modulation: 1kHz Sine Wave, 80%, AM Modulation

Frequency Step: 1 % of preceding frequency value

Coupled cable: Power Mains, Unshielded

Coupling device: CDN-M3 (3 wires)

8.7.2. TEST INSTRUMENT

Immunity Shield Room

Name of Equipment Manufacturer Model Serial Number Calibration Due

Computer HP d330 uT SGH3480LTH N.C.R.


VGA Monitor NEC JC-1572VMA 6600645RA N.C.R.
Keyboard IBM KB - 8923 1021424 N.C.R.
CS Frankonia
EMVMess-System FRANKONIA CIT-10/75 102C3220 SEP. 23,2009
Gmbh
FCC Coupling
Decoupling Network
FRANKONIA CDN M2+M3 A3011095 JAN. 20, 2010
Freq. range :
150KHz~230MHz
FCC EM Injection
------------- F-203I-23mm 449 NOV. 30, 2009
Clamp
Test S/W CS-EN61000-4-6

NOTE: 1. The calibration interval of the above test instruments is 12 months and the calibrations are traceable
to NML/ROC and NIST/USA.
2. N.C.R.= No Calibration Required.

Page 46
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.7.3. TEST PROCEDURE

The EUT shall be tested within its intended operating and climatic conditions.

The test shell performed with the test generator connected to each of the coupling and decoupling
devices in turn, while the other non-excited RF input ports of the coupling devices are terminated by a
50-ohm load resistor.
The frequency range was swept from 150 kHz to 80 MHz, using the signal level established during
the setting process and with a disturbance signal of 80 % amplitude. The signal was modulated with a
1 kHz sine wave, pausing to adjust the RF signal level or the switch coupling devices as necessary.
The sweep rate was 1.5 x 10-3 decades/s. Where the frequency range is swept incrementally, the step
size was 1 % of preceding frequency value from 150 kHz to 80 MHz.
The dwell time at each frequency was less than the time necessary for the EUT to be exercised, and
able to respond. Sensitive frequencies such as clock frequency(ies) and harmonics or frequencies of
dominant interest, was analyzed separately.
Attempts was made to fully exercise the EUT during testing, and to fully interrogate all exercise
modes selected for susceptibility.

Page 47
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.7.4. TEST SETUP

Note: 1. The EUT is setup 0.1m above Ground Reference Plane


2. The CDNs and / or EM clamp used for real test depends on ports and cables configuration of EUT.

z For the actual test configuration, please refer to the related item – Photographs of the Test
Configuration.

NOTE:
TABLE-TOP AND FLOOR-STANDING EQUIPMENT
The equipment to be tested is placed on an insulating support of 0.1 meters height above a ground reference
plane. All relevant cables shall be provided with the appropriate coupling and decoupling devices at a distance
between 0.1 meters and 0.3 meters from the projected geometry of the EUT on the ground reference plane.

Page 48
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.7.5. TEST RESULTS

Temperature 24 oC Humidity 42% RH


Pressure 1032 mbar Tested By Agun Huang
Required Passing Performance Criterion A

POWER
Field
Frequency Injection Performance
Strength Cable Criterion
Observation Result
Band (MHz) Method
(Vrms)
CDN- M2
0.15 ~ 80 10 Power Cord A B C Note 1 2 3 A PASS
M3

SIGNAL
Field
Frequency Injection Performance
Strength Cable Criterion
Observation Result
Band (MHz) Method
(Vrms)
0.15 ~ 80 10 Ethernet cable Clamp A B C Note 1 2 3 A PASS

NOTE:
1. Performance criteria A for immunity tests with phenomena of a continuous nature.
2. Performance criteria B for immunity test with phenomena of a transient nature.
3. Performance criteria C for immunity test with power interruptions, function loss and voltage dips
exceeding a certain period of time.

Page 49
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.8. POWER FREQUENCY MAGNETIC FIELD

8.8.1. TEST SPECIFICATION

Basic Standard: EN 61000-4-8

Frequency Range: 50Hz

Field Strength: 30 A/m

Observation Time: 1 minute

Inductance Coil: Rectangular type, 1mx1m

8.8.2. TEST INSTRUMENT

Power Frequency Magnetic Field Immunity Test (IEC/EN 61000-4-8)

Name of Equipment Manufacturer Model Serial Number Calibration Due

Magnetic field generator Schaffner MFO 6501 154 JAN 19, 2010

Magnetic field loops Schaffner INA 702 158 OCT. 04, 2009

NOTE: The calibration interval of the above test instruments is 12 months and the calibrations are traceable to
NML/ROC and NIST/USA.

8.8.3. TEST PROCEDURE


a) The equipment is configured and connected to satisfy its functional requirements. It shall be
placed on the GRP with the interposition of a 0.1m-thick insulating support.
b) The equipment cabinets shall be connected to the safety earth directly on the GRP via the earth
terminal of the EUT.
c) The power supply, input and output circuits shall be connected to the sources of power supply,
control and signal.
d) The cables supplied or recommended by the equipment manufacturer shall be used. 1 meter of all
cables used shall be exposed to the magnetic field.

Page 50
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.8.4. TEST SETUP

Induction
Coil

1/2 Dimension
of EUT

EUT

Signal
Generator

To
Earth Ground

For the actual test configuration, please refer to the related item – Photographs of the Test
Configuration.

NOTE:
TABLETOP EQUIPMENT
The equipment shall be subjected to the test magnetic field by using the induction coil of standard dimension (1
m x 1 m). The induction coil shall then be rotated by 90 degrees in order to expose the EUT to the test field
with different orientations.

FLOOR-STANDING EQUIPMENT
The equipment shall be subjected to the test magnetic field by using induction coils of suitable dimensions. The
test shall be repeated by moving and shifting the induction coils, in order to test the whole volume of the EUT
for each orthogonal direction. The test shall be repeated with the coil shifted to different positions along the
side of the EUT, in steps corresponding to 50 % of the shortest side of the coil. The induction coil shall then be
rotated by 90 degrees in order to expose the EUT to the test field with different orientations.

Page 51
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.8.5. TEST RESULTS

Temperature: 24 oC Humidity 42 % RH
Pressure 1032 mbar Tested By Agun Huang
Required Passing Performance Criterion A

Power
50Hz
Frequency
Field Strength Performance
Direction Criterion
Observation Result
A/m
X axis 30 A B C Note 1 2 3 A PASS
Y axis 30 A B C Note 1 2 3 A PASS
Z axis 30 A B C Note 1 2 3 A PASS

NOTE:
1. Performance criteria A for immunity tests with phenomena of a continuous nature.
2. Performance criteria B for immunity test with phenomena of a transient nature.
3. Performance criteria C for immunity test with power interruptions, function loss and voltage dips
exceeding a certain period of time.

Page 52
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.9. LOW-FREQUENCY CONDUCTED DISTURBANCES

8.9.1. TEST SPECIFICATION

Basic Standard: EN 61000-2-2

Frequency Range: Single Sinusoidal : 140 - 360 Hz

Disturbing voltage : 10V (rms )

Test duration: 60 minutes

8.9.2. TEST INSTRUMENT

Immunity to Low Frequency Signals Measurement (IEC 61000-2-2)


Name of Equipment Manufacturer Model Serial Number Calibration Due
AC Power Source iDRC CF-2000T 978720 N.C.R.
Audio Isolation
SOLAR 6220-1A --------- N.C.R.
Transformer

NOTE: 1. The calibration interval of the above test instruments is 12 months and the calibrations are traceable
to NML/ROC and NIST/USA.
2. N.C.R.= No Calibration Required.

Page 53
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

8.9.3. TEST RESULTS

Temperature 24 oC Humidity 42% RH


Pressure 1032 mbar Tested By Agun Huang
Required Passing Performance Criterion A

Varied Disturbing Performance


Frequency Voltage
Insert Phase
Criterion
Observation Result

140Hz~360Hz 10 Vac L A B C Note 1 2 3 A PASS

NOTE:
1. Performance criteria A for immunity tests with phenomena of a continuous nature.
2. Performance criteria B for immunity test with phenomena of a transient nature.
3. Performance criteria C for immunity test with power interruptions, function loss and voltage dips
exceeding a certain period of time.

Page 54
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

9 PHOTOGRAPHS OF THE TEST CONFIGURATION

CONDUCTED EMISSION TEST

Page 55
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

RADIATED EMISSION TEST

Page 56
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

ESD TEST

RS TEST

Page 57
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

EFT TEST

Page 58
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

SURGE TEST

CS TEST

Page 59
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

POWER FREQUENCY MAGNETIC FIELD TEST

Page 60
This report shall not be reproduced except in full, without the written approval of Compliance Certification Services.
Reference No:90819401-E
Report No: T100201405-E

LOW-FREQUENCY CONDUCTED DISTURBANCES TEST

END OF REPORT

Page 61