PanelView Standard The PanelView Standard terminals feature pixel graphics capabilities and
functionality in color, grayscale, and monochrome displays. These rugged
Terminals electronic operator interface solutions are available in a variety of sizes and
configurations to meet specific application requirements. All use common
development software to simplify programming and improve operator
productivity.
These terminals communicate with PLC and SLC controllers over EtherNet/IP,
DeviceNet, ControlNet, DH-485, DH+, and remote I/O networks, or by using
serial communication.
Other features supported by the PanelView Standard line include advanced alarm
handling, screen security, analog gauges, ATA memory card, universal language
support, and online printing for more intuitive operator control.
2 PanelView Standard Terminal Specifications
Environmental This table lists the environmental specifications for the family of PanelView
Standard terminals.
Specifications
Table 1 - Environmental Specifications- PanelView Standard Terminals
Attribute 2711 PanelView Standard 300, 300 Micro, 550, 1000
Temperature, operating 0…55 °C (32…131 °F)
600 color: 0…50 °C (32…122 °F)
Temperature, storage
550 -20…70 °C (-4…158 °F)
300 Micro -20…85 °C (-4…185 °F)
300, 600, 1000 -25…70 °C (-13…158 °F)
Heat dissipation
300 Micro 2.5 W (8.5 BTU/hr)
300 6 W (13 BTU/hr)
550 20 W (69 BTU/hr)
600 keypad 32 W (107 BTU/hr)
600 touch 17 W (577 BTU/hr)
1000 39 W (132 BTU/hr)
Relative humidity
300 Micro, 600 keypad, 1000 5...95% noncondensing at 0…55 °C (32…131 °F)
300, 550 5...95% noncondensing at 0…30 °C (32…86 °F)
600 touch 5...95% noncondensing at 0…40 °C (32…104 °F)
Enclosure ratings NEMA Type 12, 13, 4X (indoor use only), IEC IP54, IP65
Airborne contaminants ANSI/ISA S71.04 - 1985 Severity Level G3
300 conformal-coated only EN60654-4: 1998 Class 3
Certifications This table lists the certifications for the family of PanelView Standard terminals.
Table 2 - Certifications - PanelView Standard Terminals
300
Certification(1) Micro
300 550 600 1000
Technical Specifications Tables 3…6 summarize the technical specifications for PanelView Standard
terminals.
Dimension Drawings Figures 1…5 provide dimension drawings for the PanelView Standard family of
terminals.
111 mm
(4.38 in.)
35 mm 48 mm
(1.39 in.) (1.87 in.)
133 mm
(5.23 in.)
197 mm
(7.76 in.) 69 mm 82 mm
(2.73 in.) (3.21 in.)
140 mm
(5.53 in.)
167 mm 106 mm
(6.57 in.) 4.17 in.)
86 mm
(3.39 in.)
266 mm
(10.47 in.)
152 mm
82 mm
(6.00 in.)
3.20 in.)
64 mm
(2.54 in.)
185 mm
(7.28 in.)
192 mm
(7.55 in.)
91 mm 116 mm
(3.60 in.) 4.57 in.)
290 mm
(11.40 in.)
79 mm 96 mm
(3.12 in.) 3.80 in.)
152 mm
(6.00 in.)
185 mm
(7.28 in.)
282 mm
(11.11 in.)
90 mm 167 mm
(3.54 in.) 6.57 in.)
370 mm
(14.58 in.)
282 mm 90 mm 167 mm
(11.11 in.) (3.54 in.) 6.57 in.)
423 mm
(16.64 in.)
Product Selection Tables 7…11 provide a list of catalog numbers for the PanelView Standard
terminals.
(1) Terminals with a DH-485 communication port require application uploads and downloads through the communication port. The RS-232
printer port is only for printing only.
(2) K at the end of a catalog number means the terminal is conformal-coated.
(3) This terminal does not have an RS-232 printer port. Use the communication port to download or upload application files.
Accessories Tables 12… 19 list accessories available for PanelView Standard terminals.
Table 12 - ATA Memory Cards
Cat. No. Description
2711-NM13 2 MB flash memory card
2711-NM14 4 MB flash memory card
2711-NM15 10 MB flash memory card
2711-NM232 32 MB flash memory card
2711-NMCC Memory card retainer for PanelView Standard 550, 600, 1000 keypad, or
keypad and touch terminals
2711-NMCD Memory card retainer for PanelView Standard 550 touch-screen only
terminals
2711-NMCE Memory card retainer for PanelView Standard 300 and 600 touch-screen
only terminals
PanelBuilder32 Software PanelBuilder32 software supports the entire family of PanelView Standard
terminals, allowing for easy conversion and reuse of existing applications. This
32-bit software package runs on a Microsoft Windows 2000, ME, XP, or Vista
operating system.
Cables This table summarizes cables and interface modules used by the PanelView
Standard terminals.
Table 22 - Cables
Cat. No, Description Length
Personal computer interface converter - converts RS-232 signals to/from
1747-PIC —
DH-485 signals
1747-C10 1.8 m (6 ft)
RS-232 operating/program cable, 9-pin D-shell to 9-pin D-shell
1747-C11 0.3 m (1 ft)
2711-xxA2, 2711-xxA3, 2711-xxC2, 2711-xxG3
1747-C20 6 m (20 ft)
2706-NC13(1) RS-232 operating/program cable, 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
2711-NC13(1) RS-232 operating/program cable, 9-pin D-shell to 9-pin D-shell 5 m (16.4 ft)
2711-NC14(1) RS-232 operating/program cable, 9-pin D-shell to 9-pin D-shell 10 m (32.7 ft)
2711-NC17 Remote RS-232 cable assembly, 9-pin D-shell to 9-pin D-shell 3 m (10 ft)
Provides a 9-pin RS-232 port assembly for remote serial port access.
For PanelView Standard, PanelView 1000e/1400e series F and later
terminals.
2711-NC21(2) RS-232 operating cable, 9-pin D-shell to 8-pin mini DIN 5 m (16.4 ft)
2711-NC22 RS-232 operating cable, 9-pin D-shell to 8-pin mini DIN 15 m (49 ft)
2711-CBL-HM05 RS-232 operating cable, 8-pin mini DIN to 8-pin mini DIN 5 m (16.4 ft)
2711-CBL-HM10 PanelView 300 Micro to MicroLogix controller 10 m (32.7 ft)
2711-CBL-PM05 RS-232 operating/programming cable, 9-pin D-shell to 8-pin mini DIN 5 m (16.4 ft)
2711-CBL-PM10 PanelView 300 Micro to SLC or PLC controller 10 m (32.7 ft)
1761-CBL-AM00 RS-232 operating cable, 8-pin mini DIN to 8-pin mini DIN 0.5 m (1.5 ft)
1761-CBL-HM02 PanelView 300 Micro to MicroLogix controller 2 m (6.5 ft)
1761-CBL-AP00 RS-232 operating/programming cable, 9-pin D-shell to 8-pin mini DIN 0.5 m (1.5 ft)
1761-CBL-PM02 PanelView 300 Micro to SLC or PLC controller 2 m (6.5 ft)
(1) Cable used for operation/communication with PanelView Standard 2711-xxx5, 2711-xxx9, 2711-xxx16, 2711-xxx17 terminals.
Cable used for application file transfer or printing with 2711-xxx1, 2711-xxx3, 2711-xxx8, 2711-xxx9, 2711-xxx10, 2711-xxx15,
2711-xxx16, 2711-xxx17, 2711-xxx20.
(2) Null-modem not required.
SLC 500, 5/01, 5/02 SLC 5/03, 5/04, 5/05 SLC 5/03
PanelView Standard SLC 5/04 SLC 5/05
Protocol Comm Port CH1 RJ45 CH0 (9-pin RS-232) CH1 (RJ45) CH1 (DH+) CH1 (ENET)
(DH-485) (DF1 or DH-485) (DH-485)
DF1 RS-232 (DF1) port (8-pin mini DIN) 1761-CBL-AP00 (0.5 m/1.5)
PanelView 300 Micro — 1761-CBL-PM02 (2 m/6.5)
2711-CBL-PM05 (5 m/16 ft)
— — —
2711-xxx18
2711-CBL-PM10 (10 m/32 ft)
DH-485 port (RJ45) 1747-C10 (2 m/6 ft) Use AIC+ module 1747-C10 (2 m/6 ft)
PanelView 300 to 1400 1747-C11 (0.3 m/1 ft) (1761-NET-AIC) 1747-C11 (0.3 m/1 ft) — —
2711-xxx2, 2711-xxx3 1747-C20 (6 m/20 ft) to connect to port 3 1747-C20 (6 m/20 ft)
ControlNet port
ControlNet PanelView 550T to 1400 — PanelView termina does not support SLC ControlNet configurations
2711-xxx15
(1) EtherNet/IP direct connection from the terminal to an SLC 5/05 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable.
Table 25 - Runtime Communication Cables: PanelView Standard Terminals to PLC-5 and MicroLogix Controllers
MicroLogix 1500LRP
MicroLogix 1000, 1100, 1200,
PLC-5, PLC-5C, PLC-5E CH1 (9-pin RS-232)
Protocol PanelView Standard Comm Port 1400, 1500LSP MicroLogix 1100, 1400
CH0 (25-pin RS-232) MicroLogix 1400
CH0 (8-pin Mini DIN) Ethernet
(DF1) CH2 (9-pin RS-232)
(DF1 or DH-485)
(DF1 or DH-485)
DF1 RS-232 (DF1) port (8-pin mini DIN) 1761-CBL-AP00 (0.5 m/1.5)
1761-CBL-AP00 (0.5 m/1.5) 1761-CBL-AM00 (0.5 m/1.5)
PanelView 300 Micro 1761-CBL-PM02 (2 m/6.5)
1761-CBL-PM02 (2 m/6.5) 1761-CBL-HM02 (2 m/6.5) —
2711-xxx18 2711-CBL-PM05 (5 m/16 ft)
2711-CBL-PM10 (10 m/32 ft) 2711-CBL-PM05 (5 m/16 ft) 2711-CBL-HM05 (5 m/16 ft)
Use 9-pin to 25-pin adapter 2711-CBL-PM10 (10 m/32 ft) 2711-CBL-HM10 (10 m/32 ft) (2)
(1) For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable.
(2) AIC+ module recommended for isolation when PanelView terminal and controller are not using same power supply.
DF1 RS-232 (DF1) port (8-pin mini DIN) 1761-CBL-AP00 (0.5 m/1.5) 1761-CBL-AP00 (0.5 m/1.5)
PanelView 300 Micro 1761-CBL-PM02 (2 m/6.5) 1761-CBL-PM02 (2 m/6.5)
2711-xxx18 2711-CBL-PM05 (5 m/16 ft) 2711-CBL-PM05 (5 m/16 ft)
2711-CBL-PM10 (10 m/32 ft) 2711-CBL-PM10 (10 m/32 ft)
RS-232 (DF1) port (9-pin) 2711-NC13 (5 m/16 ft) 2711-NC13 (5 m/16 ft)
PanelView 300 to 1400
2711-xxx16, 2711-xxx17 2711-NC14 (10 m/32 ft) 2711-NC14 (10 m/32 ft)
(1) For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable.
DF1 RS-232 (DF1) port 1761-CBL-AP00 (0.5 m/1.5) 1761-CBL-AM00 (0.5 m) 1761-CBL-AM00 (0.5 m)
(8-pin mini DIN) — 1761-CBL-PM02 (2 m/6.5) 1761-CBL-HM02 (2 m) 1761-CBL-HM02 (2 m)
PanelView 300 Micro 2711-CBL-PM05 (5 m/16 ft) 2711-CBL-HM05 (5 m) — 2711-CBL-HM05 (5 m)
2711-xxx18 2711-CBL-PM10 (10 m/32 ft) 2711-CBL-HM10 (10 m) 2711-CBL-HM10 (10 m)
(1) Series A cables, cat. no. 2711-NC21, 2711-NC22, for direct connection to 1761-NET-AIC module only. Do not use series A cables on a network of AIC+ modules connected
to Belden cables.
Additional Resources These documents contain additional information concerning related Rockwell
Automation products.
Resource Description
PanelView Standard Operator Terminals User Provides information on installing, configuring,
Manual, publication 2711-UM014 operating, and troubleshooting PanelView
Standard terminals.
PanelView 300 Keypad Terminals Installation Provides information on installing the PanelView
Instructions, publication 2711-IN027 300 keypad terminals in a panel.
PanelView 300 Micro Terminals Installation Provides information on installing the PanelView
Instructions, publication 2711-IN008 300 Micro terminals in a panel.
PanelView 550 Keypad and Keypad/Touch Provides information on installing the PanelView
Installation Instructions, publication 2711-IN009 550 keypad and keypad/touch-screen terminals
in a panel.
PanelView 550/600 Touch-screen Terminal Provides information on installing the PanelView
Installation Instructions, publication 2711-IN034 550/600 touch-screen terminals in a panel.
PanelView 600 Keypad and Provides information on installing the PanelView
Keypad/Touch-screen Terminals Installation 600 keypad/touch-screen terminals in a panel.
Instructions, publication 2711-IN010
PanelView 1000 Keypad and Touch-screen Provides information on installing the PanelView
Terminals Installation Instructions, publication 1000 terminals in a panel.
2711-IN036
Industrial Automation Wiring and Grounding Provides general guidelines for installing a
Guidelines, publication 1770-4.1 Rockwell Automation industrial system.
Product Certifications website, Provides declarations of conformity, certificates,
http://www.ab.com and other certification details.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, SLC 500, SLC 5/03, DH+, MicroLogix, PanelView 300, PanelView 300 Micro, PanelView 550, PanelView 1000, PanelBuilder32, SLC, CompactLogix, ControlLogix,
Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 2711-TD007A-EN-P - October 2010 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.