Modbus TCP Client RTU Slave MN67510 ENG
Modbus TCP Client RTU Slave MN67510 ENG
User Manual
Revision 1.001
English
Gateway / Bridge
Modbus TCP Client to Modbus RTU Slave
to connect a Modbus TCP Server HD67510 HD67510M
(Order Code: HD67510 – HD67510M)
INDEX:
UPDATED DOCUMENTATION:
Dear customer, we thank you for your attention and we remind you that you
Page
need to check that the following document is:
INDEX 2
Updated
UPDATED DOCUMENTATION 2
Related to the product you own
REVISION LIST 2
WARNING 2 To obtain the most recently updated document, note the “document code” that
TRADEMARKS 2 appears at the top right-hand corner of each page of this document.
CONNECTION SCHEME 3
With this “Document Code” go to web page www.adfweb.com/download/ and
CHARACTERISTICS 5
search for the corresponding code on the page. Click on the proper “Document
POWER SUPPLY 5 Code” and download the updates.
CONFIGURATION 6
USE OF COMPOSITOR SW67510 6 To obtain the updated documentation for the product that you own, note the
NEW PROJECT / OPEN PROJECT 7 “Document Code” (Abbreviated written "Doc. Code" on the label on the product)
and download the updated from our web site www.adfweb.com/download/
GENERAL PARAMETER 8
PING DEVICE 9
TRANSLATE TABLE 9 REVISION LIST:
UPDATE VIA TCP 11
UPDATE VIA SERIAL 12 Revision Date Author Chapter Description
CHARACTERISTICS OF THE CABLES 13 1.000 06/02/2009 Fl All First release version
MECHANICAL DIMENSIONS 14 1.001 06/05/2010 Ml Dp All Revision
ORDER CODE 14
ACCESSORIES 14
WARRANTIES AND TECHNICAL SUPPORT 15
RETURN POLICY 15 WARNING:
PRODUCTS AND RELATED DOCUMENTS 15
ADFweb.com reserves the right to change information in this manual about our
product without warning.
ADFweb.com is not responsible for any error this manual may contain.
TRADEMARKS:
CONNECTION SCHEME:
CHARACTERISTICS:
The Modbus TCP to Modbus RTU Gateway allows the following characteristics:
POWER SUPPLY:
24v 12v
VDC VAC
8v 35v 8v 19v
HD67510 HD67510M
CONFIGURATION:
To configure the Gateway, use the available software that runs with
Windows, called SW67510. It is downloadable on the site
www.adfweb.com and its operation is described in this document.
When launching the SW67510 the following window appears (Fig. 3).
The “New Project” button creates the folder which contains the entire device configuration.
To clone the configurations of the Gateway in order to configure another Gateway device in the same manner, it is necessary to
maintain the folder and all its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to duplicate the project folder with another name
and open the new folder with the “Open Project” button.
GENERAL PARAMETER:
By pressing the “General Parameter” button from the main window for
SW67510 (Fig. 3) the window “General Parameter” appears (Fig. 4).
This window is divided in two sections, one for the Modbus TCP and the other
for the Modbus RTU.
The means of the fields for “Modbus TCP” are:
In the field “IP Address” insert the IP address that you want to give to
HD67510 Gateway;
In the field “Subnet Mask” insert the SubNet Mask;
In the field “Port” insert the number of the port;
If the field “Don’t disconnect the socket” is checked, when the gateway
receives the TCP response it does not disconnect the opened socket
(open the socket only at the first RTU request and then the socket
remains opened); otherwise for every RTU requests the gateway opens
the socket and when it receives the TCP response it closes it;
If the field “Normal Mode (Translate Table)” is checked, the address of
RTU request is compared with the list of compositor;
If the field “Work with Fix IP” is checked, the gateway does not see the
“Translate Table” but it sends every request to a fixed IP defined in the Figure 4: “General Parameter” window
field below.
PING DEVICE:
If it is necessary to do a Ping on the net, before pressing the “Ping Device” button insert a value in the field on the right and then press the
button. In order to do this, the gateway must be in RUN mode. To use this feature in Vista and 7 you have to open the software with
Administrator right.
TRANSLATE TABLE:
Example 1:
Address 192.168.2.16;
Through Gateway WORD 151 (Address TCP);
Address RTU 101.
From the side of the MODBUS TCP: Step 1: Request to the gateway from “Holding Register” in address 101;
Step 2: Request by the gateway from “Holding Register” in address 151 to the
Address of the device to interrogate; device with 192.168.2.16 ID;
Address of data to read on device. Step 3: Response to the gateway from “Holding register” in address 151;
Step 4: Response to the RTU Master of the device with 192.168.2.16 ID.
If the TCP slave responds with an exception, that exception code will be transmitted to the RTU master. If the TCP slave does not respond
within the estimated time defined by the Timeout parameter, an exception response will be given: error code $36.
Ethernet cable:
The connection with the Ethernet socket must be made with a Ethernet cable with a RJ45 plug.
RS232 cable:
The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a NULL MODEM cable (a
serial cable where the pins 2 and 3 are crossed).
It is recommended that the RS232C Cable not exceed 15 meters.
MECHANICAL DIMENSIONS:
Figure 10: Mechanical dimensions scheme for HD67510 Figure 11: Mechanical dimensions scheme for HD67510M
ORDER CODE:
Order Code: HD67510 - Gateway – Modbus TCP Client to Modbus RTU Slave
Order Code: HD67510M - Gateway – Modbus TCP Client to Modbus RTU Slave (different enclosure)
ACCESSORIES:
Order Code: AC34107 - Null Modem Cable Fem/Fem DSub 9 Pin 1,5 m
For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]
RETURN POLICY:
If while using your product you have any problem and you wish to exchange or repair it, please do the following:
1) Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to provide detailed information
about the problem.
2) Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be accepted).
If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no longer under warranty,
you will receive a repair estimate.