TEST REPORT FOR DIFFERENTIAL PTD/7UM62
PROTECTION RELAY 7UM62
Page 1 of 8
TEST REPORT
RELAY TYPE: GENERATOR PROTECTION RELAY (GR1)
PANEL REF: GRP 1
MLFB: 7UM6225-5EB22-3CB0 VERSION: 4.62
Sr.No :
RATED CURRENT: 5 AMPS RATED VOLTAGE: 220 V DC
CT TERMINALS:
PT TERMINALS:
1) NEGATIVE SEQUENCE TEST
TRIP TIME: T= K/(I2/IN)2 K= MACHINE CONSTANT=6.7 , In= 5 A
FOR 1 PHASE FAULT
CURVE CHARACTERISTIC TEST
SET % OF In=Ir I calculated=3 times Ir=I I TRIP (AMPS) SET TIME (S) OPTD TIME (S)
injected=Ix
20
40
50
55
DEFINITE TIME TEST
SET TRIP TIME = AS PER GIVEN DATA.
SET % OF I calculated=3 times Ir=I I TRIP (AMPS) SET TIME (S) OPTD TIME
In=Ir injected = Ix (S)
6.6
53
Remarks:
2) BACK UP IMPEDENCE TEST
ZONE 1
VOLTS APPLIED CURRENT SET OPTD SET TIME OPTD
VOLTS(V) INJECTED VALUE VALUE (s) TRIP TIME(s)
(A) (Z=V/I) (Z=V/I)
IN IN
Vr-n 32.50
Vy-n 32.5-120
Vb-n 32.5+120
TEST REPORT FOR DIFFERENTIAL PTD/7UM62
PROTECTION RELAY 7UM62
Page 2 of 8
ZONE 2
VOLTS APPLIED CURRENT SET OPTD SET TIME OPTD
VOLTS(V) INJECTED VALUE VALUE (s) TRIP TIME(s)
(A) (Z=V/I) (Z=V/I)
IN IN
Vr-n 32.50
Vy-n 32.5-120
Vb-n 32.5+120
Remarks:
3) OVERVOLTAGE TEST
STAGE 1
VOLTS APPLIED SET VALUE OPTD VALUE SET TIME OPTD TRIP
IN (VOLTS) (s) TIME(s)
VOLTS
Vr-n 76.70
Vy-n 76.7-120
Vb-n 76.7+120
STAGE 2
VOLTS APPLIED SET VALUE OPTD VALUE SET TIME OPTD TRIP
IN (VOLTS) (s) TIME(s)
VOLTS
Vr-n 86.060
Vy-n 86.06-120
Vb-n 86.06+120
Remarks:
4) UNDER FREQUENCY TEST
STAGE 1
VOLTAGE APPLIED SET OPTD VALUE SET TIME OPTD
IN VALUE (HZ) (s) TIME(s)
VOLTS AT @HZ IN HZ
Vr-n 63.50
Vy-n 63.5-120
Vb-n 63.5+120
TEST REPORT FOR DIFFERENTIAL PTD/7UM62
PROTECTION RELAY 7UM62
Page 3 of 8
STAGE 2
VOLTAGE APPLIED SET OPTD VALUE SET TIME OPTD
IN VALUE (HZ) (s) TIME(s)
VOLTS AT @HZ IN HZ
Vr-n 63.50
Vy-n 63.5-120
Vb-n 63.5+120
Remarks:
5) OVERFLUX TEST
V/F110VOLTS/50HZ (NORMAL)
2.2=1 P.U
FOR 1.10 P.U V/F=2.2*1.1=2.42.CORRESPONDING PH-PH VOLTS=2.42*50=121 VOLTS
STAGE 1
VOLTAGE APPLIED CALC VALUE IN SET VALUE OPTD SET TIME OPTD
IN VOLTS AT @ 50HZ VOLTS IN V/F VALUE (s) TIME(s)
PH-N V/F
(IN EACH PHASE
SEPARATELY)
121/√3=69.85
STAGE 2
VOLTAGE APPLIED CALC VALUE IN SET VALUE OPTD SET TIME OPTD
IN VOLTS AT @ 50HZ VOLTS IN V/F VALUE (s) TIME(s)
PH-N V/F
(IN EACH PHASE
SEPARATELY)
88.5
CHARACTERISTIC CURVE
VOLTAGE APPLIED SET OPTD SET TIME (s) OPTD
IN VALUE VALUE TIME(s)
VOLTS AT @ 50HZ IN V/F V/F
PH-N
88.9
85.7
82.56
79.4
76.3
6) STATOR EARTH FAULT (95%)
PT TERMINALS
In TB no TB1 18, 20
TEST REPORT FOR DIFFERENTIAL PTD/7UM62
PROTECTION RELAY 7UM62
Page 4 of 8
SETTINGS
Uo--------4.8 VOLTS
Vn--------Neutral Transformer connected.
SET VALUE OF OPTD VALUE SET TIME (s) OPTD TRIP TIME
OF (s)
Uo Uo
11.1
Remarks:
7) STATOR EARTH FAULT 100%
SHORTED IN NGT TRIPPING SET TIME (s) OPTD TIME (S)
RESISTANCE 30 ohm
8) LOSS OF EXCITATION TEST
a) Characteristics 1 set value 0.41 at 80 deg & 10sec.
CURRENT
INJECTED
VOLTS APPLIED
IN RELAY PICK UP
IN REMARKS
AMPS ( ) @ 100 (char-1)
VOLTS
mA
Vr-n 63.50
Vy-n 63.5-120
Vb-n 63.5+120
b) Characteristics 2 set value 0.36 at 90 deg at 10 sec.
CURRENT
INJECTED
VOLTS APPLIED
IN RELAY PICK UP
IN REMARKS
AMPS ( ) @ 100 (char-2)
VOLTS
mA
Vr-n 63.50
Vy-n 63.5-120
Vb-n 63.5+120
c) Characteristics 3 set value 1.1 at 90 deg at 0.3.
VOLTS APPLIED CURRENT RELAY PICK UP REMARKS
IN INJECTED (char-3)
VOLTS IN
TEST REPORT FOR DIFFERENTIAL PTD/7UM62
PROTECTION RELAY 7UM62
Page 5 of 8
AMPS ( ) @ 100
mA
Vr-n 63.50
Vy-n 63.5-120
Vb-n 63.5+120
d) Loss of exitation + U/V
CURRENT VOLTAGE SET VOLTAGE
VOLTS APPLIED
INJECTED VALUE IN ACTUAL OPTD
IN REMARK
IN VOLTS @ 100 VALUE
VOLTS
AMPS mA
Vr-n 63.50
Vy-n 63.5-120
Vb-n 63.5+120
All Binary Inputs, Output and LEDs has been checked for all the 3 Characteristics.
9) LOW FORWARD POWER TEST
SET VALUE FOR REV POWER 0.5%
CALCULATED VALUE= (0.5/100) x 110 x 5 = 2.75MW (secondary value)
VOLTS APPLIED RELAY OPTD. AT SET OPTD SET OPTD
IN CURRENT VALUE VALUE TIME TRIP
VOLTS VALUE IN (REV P) (REV P) (ms) TIME(ms)
AMPS MW MW
Vr-n 63.50
Vy-n 63.5-120
Vb-n 63.5+120
Only for testing the relay operation
10) REVERSE POWER TEST
a) Without Turbine Trip Binary Input
VOLTS APPLIED RELAY OPTD. AT SET OPTD SET OPTD
IN CURRENT VALUE VALUE TIME TRIP
VOLTS VALUE IN (REV P) (REV P) (ms) TIME(ms)
AMPS MW MW
Vr-n 63.50 Ir 0.05180 5.5 5.5 10.0 10.31
Vy-n 63.5-120 Iy 0.05+60 5.5 5.5 10.0 10.31
Vb-n 63.5+120 Ib 0.05-60 5.5 5.5 10.0 10.31
TEST REPORT FOR DIFFERENTIAL PTD/7UM62
PROTECTION RELAY 7UM62
Page 6 of 8
b) With Turbine Trip Binary Input
VOLTS APPLIED RELAY OPTD. AT SET OPTD SET OPTD
IN CURRENT VALUE VALUE TIME TRIP
VOLTS VALUE IN (REV P) (REV P) (ms) TIME(ms)
AMPS MW MW
Vr-n 63.50
Vy-n 63.5-120
Vb-n 63.5+120
All Binary Inputs, Outputs and LEDs has been checked.
11) UNDER VOLTAGE TEST
STAGE 1
VOLTS APPLIED SET VALUE OPTD VALUE SET TIME OPTD TRIP
IN (VOLTS) (s) TIME(s)
VOLTS
Vr-n 44.40
Vy-n 44.4-120
Vb-n 44.4+120
STAGE 2
VOLTS APPLIED SET VALUE OPTD VALUE SET TIME OPTD TRIP
IN (VOLTS) (s) TIME(s)
VOLTS
Vr-n 37.50
Vy-n 37.5-120
Vb-n 37.5+120
12) ROTOR EARTH FAULT TEST
TB’S TO BE SHORTED FOR ABOVE: GRP1/TB1-31,32
SET VALUE OF OPTD VALUE OF SET TIME (S) OPTD TIME (S)
ROTOR RESISTANCE ROTOR RESISTANCE
IN K IN K
ALARM ----- 40 TESTED BY
TRIP-------10 SHORTING ABOVE
TB’S
Remarks:
13) INADVERTENT ENERGIZATION
CURRENT INJ SET OPTD SET VALUE FOR OPTD SET OPTD
IN PHASE VALUE VALUE RESET VALUE TIME TRIP
IN (AMPS) THRESHOLD (AMPS) (ms) TIME(ms
AMPS (VOLTS) )
TEST REPORT FOR DIFFERENTIAL PTD/7UM62
PROTECTION RELAY 7UM62
Page 7 of 8
R-N 4.20
Y-N 4.2-120
B-N 4.2+120
Remarks:
14) OUT OF STEP/POLE SLIP TEST
KEEPING CURRENT CONSTANT ,VOLTAGE ANGLE IS VARIED FROM 0 TO 180 OR 180 TO 0
TO ACHIEVE POLE SLIP.
CHARACTERISTIC - 1
VOLTS APPLIED CURRENT SET OPTD SET OPTD
IN INJECTED VALUE VALUE TIME (s) TRIP TIME(s)
VOLTS IN (Z=V/I) (Z=V/I)
AMPS IN IN
Vr-n 10.0+140
Vy-n 10.0+20
Vb-n 10.0260
CHARACTERISTIC - 1
VOLTS APPLIED CURRENT SET OPTD SET OPTD
IN INJECTED VALUE VALUE TIME (s) TRIP TIME(s)
VOLTS IN (Z=V/I) (Z=V/I)
AMPS IN IN
Vr-n 14.050
Vy-n 14.0290
Vb-n 14.0170
All Binary Inputs, Outputs and LEDs has been checked.
15) DIFFERENTIAL PROTECTION
M1 ( GROUND SIDE )
CURRENT INJ IN PHASE SET VALUE CALCULATED OPTD SET TIME OPTD TRIP
IN I/In diff > VALUE VALUE (ms) TIME(ms)
AMPS (AMPS) (AMPS)
R
Y
B
M2 ( TRANSFORMER SIDE )
CURRENT INJ IN PHASE SET VALUE CALCULATED OPTD SET TIME OPTD TRIP
IN I /In diff > VALUE VALUE (ms) TIME(ms)
AMPS (AMPS) (AMPS)
TEST REPORT FOR DIFFERENTIAL PTD/7UM62
PROTECTION RELAY 7UM62
Page 8 of 8
R
Y
B
2) DIFFERENTIAL PROTECTION ( I DIFF>>)
M1 ( GROUND SIDE)
CURRENT INJ IN SET VALUE CALCULATED OPTD SET TIME OPTD TRIP
PHASE I/In diff > VALUE VALUE (ms) TIME(ms)
(AMPS) (AMPS)
R
Y
B
M1 ( TRANSFORMER SIDE)
CURRENT INJ IN SET VALUE CALCULATED OPTD VALUE SET OPTD TRIP
PHASE I diff > VALUE (AMPS) TIME TIME(ms)
IN (AMPS) (ms)
AMPS
R
Y
B
STABILITY ALSO CHECKED
Remarks :
RELAY FOUND HEALTHY :
TESTED BY : ______________________________________
CHECKED BY : ______________________________________
APPROVED BY : ______________________________________