Tan Delta Test For Power Transformers

The document describes procedures for performing a tan delta test on power transformers to measure insulation dissipation factor. Key steps include short-circuiting all windings, ensuring proper temperature and cleaning of bushings, and properly grounding the transformer. Tan delta is then tested between the high voltage winding to earth, low voltage winding to earth, and between the high and low voltage windings. Test results for a 100MVA 33kV/220kV transformer are provided, showing tan delta values between 0.2616 and 0.4983 for the different winding combinations tested.

Uploaded by

Sreenivasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
522 views

Tan Delta Test For Power Transformers

The document describes procedures for performing a tan delta test on power transformers to measure insulation dissipation factor. Key steps include short-circuiting all windings, ensuring proper temperature and cleaning of bushings, and properly grounding the transformer. Tan delta is then tested between the high voltage winding to earth, low voltage winding to earth, and between the high and low voltage windings. Test results for a 100MVA 33kV/220kV transformer are provided, showing tan delta values between 0.2616 and 0.4983 for the different winding combinations tested.

Uploaded by

Sreenivasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

TAN DELTA TEST FOR POWER

TRANSFORMERS
TAN DELTA(INSULATION DISSIPATION FACTOR)
 Tan delta is the insulation power factor & is equal to
the ratio of power dissipated in the insulation in
watts to the product of effective voltage & current in
volt ampere when tested under sinusoidal voltage.
PROCEDURE
 All windings immersed in insulating liquid.
 All windings shortcircuited using bare braided
jumper such that jumper shall not be allowed to sag.
 All bushings in place.
 Temperature of winding & insulation liquid near to
the reference temperature(27 degree).
 All bushings cleaned properly.
 Transformer earthed properly.
 Neutral,star point of 3 phase winding connected to
other bushing of that winding by means of short
jumper.
 Tan delta is then tested between below
combinations,
a. HV to EARTH
b. LV to EARTH
c. HV to LV.
TEST SETUP
 TRANSFORMER SPECIFICATONS
RATING-100 MVA
VOLTAGE CLASS-33KV/220KV
Yyn-0
COOLING-OFAF

 INSTRUMENT MAKE-OMICRON

 APPLIED VOLTAGE-10KV
LV TO EARTH TESTING
HV TO EARTH TESTING
LV-HV TESTING
TAN-DELTA TEST RESULTS
WINDING TAN-DELTA
LV TO EARTH 0.4702
HV TO EARTH 0.4983
LV TO HV 0.2616