0% found this document useful (0 votes)
219 views2 pages

MP 128 4a

The document provides submittal data for a synchronous AC generator including its model, ratings, test results, and performance curves. It includes the generator's technical specifications, parameters, and test values based on military standards.

Uploaded by

Richel Genabe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
219 views2 pages

MP 128 4a

The document provides submittal data for a synchronous AC generator including its model, ratings, test results, and performance curves. It includes the generator's technical specifications, parameters, and test values based on military standards.

Uploaded by

Richel Genabe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

MARATHON ELECTRIC

SYNCHRONOUS AC GENERATOR
TYPICAL SUBMITTAL DATA
Model MP-128-4A
Basic Model: 431CSL6202/431PSL6202 Date: 3/28/13

Kilowatt ratings at 1500 RPM 60 Hertz 12 Leads

kW (kVA) 3 Phase 0.8 Power Factor Dripproof or Open Enclosure


Class B Class F Class H
105º C † 105º C  125º C †
80º C  90º C  95º C  British Continuou 130º C  British 125º C  150º C 
Voltage* Continuous Lloyds ABS Standard s Standby Standard Continuous Standby
240/480 125 (156) 131 (164) 135 (169) 142 (178) 142 (178) 155 (194) 145 (181) 151 (189) 160 (200)
230/460 125 (156) 132 (165) 136 (170) 143 (179) 143 (179) 155 (194) 145 (181) 152 (190) 160 (200)
220/440 125 (156) 132 (165) 136 (170) 143 (179) 143 (179) 153 (191) 145 (181) 151 (189) 160 (200)
208/416 125 (156) 130 (163) 133 (166) 140 (175) 140 (175) 151 (189) 141 (176) 147 (184) 155 (194)
190/380 115 (144) 120 (150) 123 (154) 130 (163) 130 (163) 140 (175) 132 (165) 135 (169) 145 (181)
Rise by resistance method, Mil-Std-705, Method 680.1b. †Rating per BS 5000.

Submittal Data: 240/480 Volts*, 194 kVA, 1800 RPM, 60 Hz, 3 Phase
Mil-Std-705B Mil-Std-705B
Method Description Value Method Description Value
301.1b Insulation Resistance > 1.5 Meg 505.3b Overspeed 2250 RPM
302.1a High Potential Test 507.1c Phase Sequence CCW-ODE ABC
Main Stator 2000 Volts 508.1c Voltage Balance, L-L or L-N 0.2%
Main Rotor 1500 Volts 601.4a L-L Harmonic Maximum - Total 5.0%
Exciter Stator 1500 Volts (Distortion Factor)
Exciter Rotor 1500 Volts 601.4a L-L Harmonic Maximum - Single 3.0%
PMG Stator 1500 Volts** 601.1c Deviation Factor 5.0%
401.1a Stator Resistance, Line to Line --- TIF (1960 Weightings) <50
High Wye Connection 0.0718 Ohms 625.1c Mechanical Strength (High Wye
Rotor Resistance 0.598 Ohms Connection, Sustained 3 Phase
Exciter Stator 18.5 Ohms Short Circuit Current) (3) < 300%
Exciter Rotor 0.116 Ohms 652.1a Shaft Current < 0.1 ma
PMG Stator 2.1 Ohms** 652.1a Main Stator Capacitance to
410.1a No Load Exciter Field Amps Ground 0.015 mfd
at 480 Volts Line to Line 0.6 A DC
420.1a Short Circuit Ratio 0.405 Additional Prototype Mil-Std Methods
421.1a Xd Synchronous Reactance 3.195 pu are Available on Request.
422.1a X2 Negative Sequence
Reactance 0.268 pu -- Generator Frame 431
423.1a X0 Zero Sequence Reactance 0.05 pu -- Type Ext. Voltage Regulated, Brushless
425.1a X'd Transient Reactance 0.19 pu -- Insulation Class H
426.1a X''d Subtransient Reactance 0.182 pu -- Coupling - Single Bearing Flexible
-- Xq Quadrature Synchronous -- Amortisseur Windings Full
Reactance 1.478 pu -- Cooling Air Volume 1280 CFM
427.1a T'd Transient Short Circuit -- Exciter Rotating
Time Constant 0.048 sec. -- Voltage Regulator SE350***
428.1a T''d Subtransient Short Circuit -- Voltage Regulation 1%***
Time Constant 0.005 sec. -- Sensing 1 Phase***
430.1a T'do Transient Open Circuit
Time Constant 1.34 sec.
432.1a Ta Short Circuit Time
Constant of Armature Winding 0.014 sec.
(3)
Excitation support system or PMG required to sustain short circuit currents. www.marathonelectric.com
* Voltage refers to wye (star) connection, unless otherwise specified.
**Not supplied as standard equipment.
***DVR®2000E+ voltage regulator supplied with PMG option. DVR®2000E+ voltage regulation 1/4%, 1 or 3 Phase sensing.
MARATHON ELECTRIC
SYNCHRONOUS AC GENERATOR
TYPICAL SUBMITTAL DATA

Basic Model: 431CSL6202/431PSL6202 Date: 3/28/13


60 HERTZ

Time (Sec.)
Time (Sec.)

Recovery
Recovery

1 1
208/416V 208/416V

240/480V 240/480V
0 0
LOAD APPLICATION LOAD REJECTION
30 30
240V DELTA

% Voltage Rise
% Voltage Dip

240V DELTA
20 280/416V 20 280/416V

10 10
240/480V 240/480V

0 0
0 50 100 150 200 0 50 100 150 200
kW at 0.8 Power Factor kW at 0.8 Power Factor

TYPICAL MOTOR STARTING CHARACTERISTICS


40

240V DELTA
208/416V
30
% Voltage Dip

20 240/480V

10 SE350
DVR®2000E+

0
0 100 200 300 400 500 600 700
Locked Rotor kVA
TYPICAL GENERATOR EFFICIENCY
100 100
416 V 480 V
95 95 1.0 pf
1.0 pf
% Efficiency
% Efficiency

90 90

85 0.8 pf 85 0.8 pf

80 80
0 50 100 150 200 250 0 50 100 150 200 250
kW Output kW Output

Voltage refers to wye (star) connection, unless otherwise specified. www.marathonelectric.com