Comments Resolution Sheet
Comments Resolution Sheet
REVISION NO. 1
Sl. No. M/S MRPL COMMENTS JASH REPLY DATED 02.09.2019 Wabag Reply
1 Include tag no( FD3902AB) of the motor. Noted, Please refer revised documents. Point Closed.
2 Include the no of poles. Noted, Please refer revised documents. Point Closed.
8
Bearing DE/ODE type of lubrication whether re lubrication Noted, Please refer revised documents
should be possible as contract.
11 Variation of voltage and frequency shall be mentioned. Noted, Please refer revised documents.
12
Only 415V shall be supplied from WABAG end. Other voltage 415 V required for Motor and 230 V single phase required for space
shall be internally derived. heater.
13 F (Temp. rise limited to class 'B') Noted, Please refer revised documents.
This is an outdoor application and hence IP 66 Protection is a must
14 Motor enclosure IP55 and better than IP 55
17
The frame of the motor shall be provide with two separate Noted and Confirmed.
and distinct grounding pads with complete other asseccories.
18
Sound Pressure Level(dB) shall be mentioned and shall be in As per IEC 60034-9
accordance to IS 12065
20
Mention the value of current in Amps at start,100%load,75% 1.69 A at 100 % , 1.44 A at 75 % ,1.26 A at 50% . All currents at 415 V
load &50%load. Y,50 Hz connection.
22 Mention the value of PF during staring condition. 0.74 assuming 100 % Load.
23
Terminal Box position shall be at the top. Also all highlighted Noted. Please refer revised datasheet.
points in attachment 01 shall be fulfilled
25
Maxmimum and minimum torque and speed at minimum Motor fitted with gear unit and hence this data may not be relevant
torque shall be mentioned. to us.
REVISION NO. 1
6
7
10
11
ESOLUTION SHEET
RS for ANNEXURE-1
point closed.
OK. Noted
point closed.
point closed.
There is no separate TB for space heater. It will be available in the
same TB as motor power connections
There is no separate TB for temperature detector (SEW provides point closed.
thermostat in the motor). It will be available in the same TB as motor
power connections.
noted
noted
Noise level as per IEC 60034-9 and vibration level as per IEC 60034-14