Compensators: G (S) G (S)
Compensators: G (S) G (S)
Compensators
To improve the performance of a given plant or system Gf(s) it may be necessary to
use a compensator or controller Gc(s).
Compensator Plant
Gc (s) Gf (s)
If the given plant does not satisfy 2 or 3 conditions specified from the above, a
compensator circuit may be necessary to modify the overall plant characteristics (i.e
of Gc(s) Gf(s)) to satisfy the given specifications.
Gc = = with = Zc / P c
1
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
Lead compensator can be realized with electrical or mechanical components
Gc(s)
or tan Ф = 1 / 1
√
or log Gc(ω =10 log , db
is the gain contribution by compensator at the
mean frequency.
2
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
Design of Compensator for a system
Design can be carried on in frequency domain or in time domain using Root-locus
Both methods are explained – for lead & lag compensator cases.
Let us consider Frequency domain approach first in each case.
Lead Compensator :
Design procedure – steps
For the given plant – determine Kv or Ka based on specification
Draw Bode Plot and check whether adequate Ф is provided
If is specified, find the required phase margin from approx relation
0.01 Ф margin
Or Ф margin = 100 - becomes the specified phase margin
Determine the phase lead to be introduced by controller from Ф e = Ф s – Ф uc +
Where Ф s is the specified phase margin, Ф uc - phase margin of
uncompensated system, and to account for shift of cross-over frequency.
Ф
Let Ф m = Ф l , then determine from
Ф
(If Øm is more than 60 , it is desirable to provide two identical networks each
0
3
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
Chose 12 to 140 as gain slope in high.
4
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
Lag Compensator can be realized as shown
(also 1)
Øc which is – ve as >1
Hence the contribution to phase angle of Gf(c) is negative
Note: Relations for Ф max (at the geometric mean of = & = ) etc. are similar to lead
compensator. However, lag (or decreasing the phase difference further is
undesirable).
The characteristic taken advantage is high frequency gain attenuation (reduction –
by 20log decibels) with very little decrease in phase.
5
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
Lag Compensator Design procedure
This can be used only when there is a range of Ф more than -1800 in Gf(s), since
phase lag increases due to lag compensator. The Compensator relies on reducing
the gain of the compensated plant in the critical region to make it adequately
stable.
Find the open-loop gain necessary to satisfy the required condition
Find the frequency ωc2 when uncompensated system makes
Ø2 =Øs + where is 50 to 150 to account for phase lag due to network
Measure the gain of UC system at ωc2, and equate it to 20 log and find .
Choose upper corner frequency ω2 (= 1/ ) of network one octave or decade
below ωc2,
(ω2 = ωc2 /2 ie. Octave or ωc2 /10 for decade)
Knowing & , ω 2 (= 1/ ); w1 (= 1/ ); Gc = (
6
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
Frequency where Ф = -1300 is 0.6 rad/sec (ωc2 ) choose ω 2 at 2 octaves less than
ωc2
ω2 = 0.6/22 = 0.15 rad/sec
Also the gain at A has to be brought down to 0 when Ф = -1300
Hence 20 log = 19, or = 8.91
1 = 1/ = 0.15/8.91 = 0.0168
Hence the compensator to be implemented is
.
Gc(s) = ( =
. .
-------------------------------------------------------------------
Translate the desired specifications into a dominant pair of complex poles in the
Root Locus. (complex plane). If the given system Gf(s) is such that
Gf(s) 1800 at Sd then a compensator needs to be designed
such that
Gf(s) Gc(s) 1800 at Sd or Gc(s)d 1800 - Gf(s)d = Φ ------ (A)
ie. the pole-zero pair of compensator
have to contribute Φ.
From the above figure, we have from
properties of ∆s,
zc / n= and pc/ n=
Φ
Φ
Φ
So that zc /pc =
Φ
Φ and d /d = zc /p = sin
7
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
(to reduce the effect of gain due to compensator, it is desirable to have large ).
which leads to =½( Φ --------(B)
Thus after locating Sd in the complex plane, knowing = Cos-1 ξ, and Ø from (A),
locate zc from (B), as well as pc
Knowing zc and pc , the compensator is (s+zc)/(s+pc)
Solution: Given the damping ratio ξ = 0.5(=Cos-1 ) and n of the dominant complex
pole pair, the point Sd to pass through the root locus of the compensated plant is
Sd= - ξ n j n 1 ξ2) = -1 j 1.73
= Cos-1 0.5 = 600
Φ = -180 – Gf(Sd)
= -1800 – (120-90-60) = 600
ν= ½ ( Φ) = ( 60 60 /2= 300
8
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
Lag Compensator – Time Domain
Method: Lag compensator is designed when the steady – state response needs
improvement, while transient performance is satisfactory.
As the transient performance is satisfactory, the technique lies in ensuring that the
root locus passes through the same Sd as for the uncompensated system while the
error constant is improved.
Therefore pole P is chosen close to origin and zero to its left so that β =Zc /Pc >1
where Φ = PSZ is 2 to 50
and OSZ < 100,
We can establish value of β using the following
reasoning:
Gain of UC system at Sd
| | .| |.| |…..
= Kuc (Sd) =
| |.| |…
| | .| |.| |…..
Similarly Kc (Sd) =
| |.| |…
X
= Kuc (Sd) x
Ke uc .
Hence β = = Ke c /Ke uc
Thus β can be chosen as the ratio of the expected Error Constant to the Error
Constant of the given system
9
Dr.PA Sastry- Lecture Notes- Control Systems –for BE (Prod/Mech)
Example: Design a lag compensator for the system
Gf (s) = to meet the following specs:
= 5/0.666 = 7.5
Say β = 10 to counter the effect of negative
phase difference due to lag compensator.
Now to locate the pole and zero,
Draw a line from S to Zc so that OSZc = 60 . (small value)
Determine OZe = 0.1 (measure)
Since β = Zc/Pc, Pc = Z/10 = 0.1/10 = 0.01
Also as the gain compensated system may be treated as the same as of UC system
– in which case
. .
Gf Gc = , which is the Compensated plant transfer function
.
** ** **
10