0% found this document useful (0 votes)
191 views2 pages

Base Support On Elbow For Cryogenic Pipe 2" - 68" Nps

This document provides specifications for cryogenic pipe base supports between 2" and 68" nominal pipe size (NPS). It includes dimensions for trunnion sizes, support components, and load ratings. The document contains tables specifying trunnion and support component sizes based on pipe size, minimum pipe thicknesses, nominal and maximum load ratings, and an example of how to tag a pipe support.

Uploaded by

Mainuddin Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
191 views2 pages

Base Support On Elbow For Cryogenic Pipe 2" - 68" Nps

This document provides specifications for cryogenic pipe base supports between 2" and 68" nominal pipe size (NPS). It includes dimensions for trunnion sizes, support components, and load ratings. The document contains tables specifying trunnion and support component sizes based on pipe size, minimum pipe thicknesses, nominal and maximum load ratings, and an example of how to tag a pipe support.

Uploaded by

Mainuddin Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PIPE STANDARD SUPPORTS TS-COR-ENG-PIPSUPC-009-E

REV. 01

CBE1 SH. 1 OF 2 DATE NOV. 2015

BASE SUPPORT ON ELBOW FOR CRYOGENIC PIPE 2" - 68" NPS

Prepared Approved
M. D’Ambrosio P. Puzone
TUB PLENG

This document is the property of Saipem S.p.A. All rights reserved.


PIPE STANDARD SUPPORTS TS-COR-ENG-PIPSUPC-009-E

REV. 01

CBE1 SH. 2 OF 2 DATE NOV. 2015

BASE SUPPORT ON ELBOW FOR CRYOGENIC PIPE 2" - 68" NPS

LOAD

EXISTING TRUNNION

MATERIAL INCLUDED
T

IN PIPING ISOMETRIC
L M AX.= 850
L M IN.= 350

3T

MP2
DO NOT WELD

EXISTING PAVING
EXISTING STRUCTURE

FOR PAVING ONLY MP3/MP5

T = CRYOGENIC INSULATION THICKNESS

DIMENSIONS TABLE

MP3/MP5
NPS TRUNNION NPS MP2
TYPE
(inches) (inches) TYPE
(IF ANY)

2 - 3 2 MP2-100-10 MP3/MP5-250-10

4 - 6 3 MP2-120-10 MP3/MP5-300-15

8 - 14 6 MP2-200-10 MP3/MP5-400-15

16 - 24 12 MP2-350-10 MP3/MP5-600-15

26 - 30 18 MP2-500-15 MP3/MP5-750-15

32 - 48 24 MP2-650-15 MP3/MP5-900-15

52 - 68 30 MP2-800-15 MP3/MP5-1050-15

LOADS TABLE

MINIMUM PIPE NOMINAL LOAD MAX. LOAD


NPS
THICKNESS LOAD x L LOAD x L
(inches)
(mm) (daNm) (daNm)

2 - 3 200 500
2.5
4 - 6 500 1200

8 - 14 2500 6000
4
16 - 24 7000 12000
EXAMPLE SUPPORT TAG
26 - 30 5 13000 18000
CBE1-8
32 - 48 18000 24000
8
PIPE SIZE (NPS)
52 - 68 25000 38000
SUPPORT NAME

This document is the property of Saipem S.p.A. All rights reserved.