PIPE STANDARD SUPPORTS TS-COR-ENG-PIPSUPC-009-E
REV. 01
CBE1 SH. 1 OF 2 DATE NOV. 2015
BASE SUPPORT ON ELBOW FOR CRYOGENIC PIPE 2" - 68" NPS
Prepared Approved
M. D’Ambrosio P. Puzone
TUB PLENG
This document is the property of Saipem S.p.A. All rights reserved.
PIPE STANDARD SUPPORTS TS-COR-ENG-PIPSUPC-009-E
REV. 01
CBE1 SH. 2 OF 2 DATE NOV. 2015
BASE SUPPORT ON ELBOW FOR CRYOGENIC PIPE 2" - 68" NPS
LOAD
EXISTING TRUNNION
MATERIAL INCLUDED
T
IN PIPING ISOMETRIC
L M AX.= 850
L M IN.= 350
3T
MP2
DO NOT WELD
EXISTING PAVING
EXISTING STRUCTURE
FOR PAVING ONLY MP3/MP5
T = CRYOGENIC INSULATION THICKNESS
DIMENSIONS TABLE
MP3/MP5
NPS TRUNNION NPS MP2
TYPE
(inches) (inches) TYPE
(IF ANY)
2 - 3 2 MP2-100-10 MP3/MP5-250-10
4 - 6 3 MP2-120-10 MP3/MP5-300-15
8 - 14 6 MP2-200-10 MP3/MP5-400-15
16 - 24 12 MP2-350-10 MP3/MP5-600-15
26 - 30 18 MP2-500-15 MP3/MP5-750-15
32 - 48 24 MP2-650-15 MP3/MP5-900-15
52 - 68 30 MP2-800-15 MP3/MP5-1050-15
LOADS TABLE
MINIMUM PIPE NOMINAL LOAD MAX. LOAD
NPS
THICKNESS LOAD x L LOAD x L
(inches)
(mm) (daNm) (daNm)
2 - 3 200 500
2.5
4 - 6 500 1200
8 - 14 2500 6000
4
16 - 24 7000 12000
EXAMPLE SUPPORT TAG
26 - 30 5 13000 18000
CBE1-8
32 - 48 18000 24000
8
PIPE SIZE (NPS)
52 - 68 25000 38000
SUPPORT NAME
This document is the property of Saipem S.p.A. All rights reserved.