0% found this document useful (0 votes)
176 views

Surge

This document contains calculations for water hammer pressure in pipelines of different diameters and flow rates. It calculates parameters like wave velocity, water hammer pressure, maximum pressure, and hydraulic test pressure for pipelines with diameters of 1180mm, 1480mm, and 980mm carrying flows of 185 MLD, 114.22 MLD, and 93.5 MLD respectively. The water hammer pressure, maximum pressure, and hydraulic test pressure values are provided for each case.

Uploaded by

Srinivas Reddy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
176 views

Surge

This document contains calculations for water hammer pressure in pipelines of different diameters and flow rates. It calculates parameters like wave velocity, water hammer pressure, maximum pressure, and hydraulic test pressure for pipelines with diameters of 1180mm, 1480mm, and 980mm carrying flows of 185 MLD, 114.22 MLD, and 93.5 MLD respectively. The water hammer pressure, maximum pressure, and hydraulic test pressure values are provided for each case.

Uploaded by

Srinivas Reddy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Water Hammer calculations

Density 1030 kg/m3

Bulk modules of water (K) 2E+09 N/m2

Diamter of Pipe d 1180 mm

Pipe thickness t 10 mm

Elastic modules of pipe E 2.1E+11 N/m2

Wave velocity a 1/(

a 955.35 m/sec

Flowrate Q 185 MLD


185000 Cu.m/day
8043.47826 Cu.m/hr
2.23 Cu.m/Sec
Velocity V 2.04 m/sec

Water hammer pressure Hmax aV/g


199.068 MWC

RL at 1650mm Diameter starting point 484 RL (m)


Lowest point 458 RL
Static head diff (M) m 26.00 MWC

Maximum pressure encounter in Site Static head (M)+ Water hammer pressure

225.1 MWC
2.21 Mpa
0.00981
Hydraulic test pressure P 2ST/D
T PXD/(2XS) mm
9.23882172 mm

1.45548387 Mpa
148.367367 MWC 2.004964

0.86328 Mpa
14.23494
1.6
15.83494
0.711747
Water Hammer calculations

Density 1000 kg/m3

Bulk modules of water (K) 2150000000 N/m2

Diamter of Pipe d 1480 mm

Pipe thickness t 10 mm

Elastic modules of pipe E 2E+11 N/m2

Wave velocity a 1/(

a 910.15 m/sec

Flowrate Q 114.22 MLD


114220 Cu.m/day
4759.16667 Cu.m/hr
1.32 Cu.m/Sec
Velocity V 0.77 m/sec

Water hammer pressure Hmax aV/g


71.331 MWC

RL at 1650mm Diameter starting point 582 RL (m)


Lowest point 475 RL
Static head diff (M) m 107.00 MWC

Maximum pressure encounter in Site Static head (M)+ Water hammer pressure

178.3 MWC
1.75 Mpa

Hydraulic test pressure P 2ST/D


T PXD/(2XS) mm
9.18137965 mm
Pipe thickness provided 10 mm
Water Hammer calculations

Density 1000 kg/m3

Bulk modules of water (K) 2150000000 N/m2

Diamter of Pipe d 980 mm

Pipe thickness t 10 mm

Elastic modules of pipe E 2E+11 N/m2

Wave velocity a 1/(

a 1022.34 m/sec

Flowrate Q 93.5 MLD


93500 Cu.m/day
3895.83333 Cu.m/hr
1.08 Cu.m/Sec
Velocity V 1.44 m/sec

Water hammer pressure Hmax aV/g


149.591 MWC

RL at 1650mm Diameter starting point 582 RL (m)


Lowest point 477 RL
Static head diff (M) m 105.00 MWC

Maximum pressure encounter in Site Static head (M)+ Water hammer pressure

254.6 MWC
2.50 Mpa

Hydraulic test pressure P 2ST/D


T PXD/(2XS) mm
8.67937052 mm
Pipe thickness provided 10mm