CTG Series Automatic Transfer Switch
CTG Series Automatic Transfer Switch
CTG SERIES
AUTOMATIC TRANSFER
SWITCH
The Cat® CTG Series Automatic Transfer Switches
(ATS) are pre-configured for applications requiring
the dependability and ease of operation found in a
full feature power contactor type transfer switch.
FEATURES
● Ratings 40 to 3000 amps (2, 3 or 4 poles) DESIGN AND CONSTRUCTION FEATURES
● UL 1008 listed at 480 VAC ● Close differential 3 phase under-voltage sensing
● CSA certified at 600 VAC (200-225 amp – 480V) of the normal source – factory standard setting
● IEC listed at 480 V 90% pickup, 80% dropout (adjustable);under
● Double throw, mechanically interlocked frequency sensing of the normal source factory
contactor mechanism setting 95% pickup (adjustable)
● Electrically operated, mechanically held ● Voltage and frequency sensing of the emergency
● Designed for emergency and standby source – factory standard setting 90% pickup
applications voltage, 95% pickup frequency (adjustable)
● Available in standard open transition (CTG) ● Test switch (fast test/load/no load) to simulate
or delayed transition (CTGD) models normal source failure – automatically bypassed
● Ringing wave immunity per IEEE 472 should the emergency source fail
(ANSI C37.90A) ● Type 1 enclosure is standard – also available in
● Conducted and Radiated Emissions per open style or Types 3R, 4, 4X, or 12.
EN55022 Class B (CISPR 11)
(Exceeds EN55011 & MILSTD 461 Class 3)
● ESD immunity test per EN61000-4-2 (Level 4)
● Radiated RF, electromagnetic field immunity
test per EN61000-4-3 (ENV50140) 10v/m
● Electrical fast transient/burst immunity test
per EN61000-4-4
● Radiated RF, electromagnetic field immunity
● Surge immunity test per EN61000-4-5
IEEE C62.41 (1.2 X 50 ms, 5 & 8 kV)
● Conducted immunity test per EN61000-4-6
(ENV50141)
● Voltage dips and interruption immunity
EN61000-4-11
● Seismic Compliance to IEEE-693-2005
and IBC-2003
LEXX0523-09 1
AUTOMATIC TRANSFER SWITCH
LEXX0523-09 2
AUTOMATIC TRANSFER SWITCH
OPTIONS (continued)
POWER MEASUREMENT METERS NOTE:
● M90 – EPM 2000 For applications requiring additional options or
Digital Power Meter with Display: other configurations, see the CTS Series fully
Amps, Volts, and Frequency configurable transfer switch.
● M91 – EPM 6000
Digital Meter with Display of Amps, Watts, Volts,
Frequency, plus THD capability with Ethernet
TESTING STANDARDS
UL, CSA and IEC listed UL 1008, CSA 22.2 No. 178, IEC 947-6-1
Ringing wave immunity IEEE 472 (ANSI C37.90A)
EN55022 Class B (CISPR 11)
Conducted and Radiated Emissions
(Exceeds EN55011 & MILSTD 461 Class 3)
ESD immunity test Class B EN61000-4-2 (Level 4)
Radiated RF, electromagnetic field immunity test EN61000-4-3 (ENV50140) 10v/m
Electrical fast, transient / burst immunity test EN61000-4-4
Surge immunity test EN61000-4-5 IEEE C62.41
Conducted immunity test EN61000-4-6 (ENV50141)
Voltage dips and interruption immunity EN61000-4-11
..
LEXX0523-09 3
AUTOMATIC TRANSFER SWITCH
LEXX0523-09 4
AUTOMATIC TRANSFER SWITCH
DIMENSIONAL SPECIFICATIONS
LEXX0523-09 5
AUTOMATIC TRANSFER SWITCH
Application Notes :
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate and
product identity used herein, are trademarks of Caterpillar and may not be used without permission.
www.Cat-ElectricPower.com
©2012 Caterpillar
All rights reserved
LEXX0523-09 (11/12)
LEXX0523-09 6