4 Units Apartment Electrical Short Circuit Study
4 Units Apartment Electrical Short Circuit Study
RESISTANCE PER
400 MCM THW / THHW or 2- WIRE GAUGE LENGTH(ft) RESISTANCE
10 m 2/0 THW /THHW FROM 1000 ft
UTILITY 2/0 0.097 SERVICE DROP 32.8 0.003182415
# 3 AWG 0.245 FEEDER CONDUCTOR 16.4 0.001591207
#1 AWG 0.154 MAIN TO FEEDER TAP 9.8 0.000954724
FEEDER TAP TO DP1 19.7 0.00303149
FEEDER TAP TO DP2 29.5 0.007234262
40 KAIC
VA base 100000 FEEDER TAP TO DP3 42.7 0.006568239
V base 230 FEEDER TAP TO DP4 52.5 0.008083984
5m 400 MCM THW / THHW or 2-
2/0 THW /THHW COMPUTE FOR FAULT AT MAIN (XFA)
PER UNIT Z OF CABLE
x FA
PU Z cable = VA base x Z cable x 2
40 KAIC
(V base)2
400 MCM THW / THHW or 2-
3 m 2/0 THW /THHW
x FB 30 KAIC Z cable 0.005728347
PU Z cable = 0.021657265
6m 9m 13m 16 m
SYMMETRICAL FAULT CURRENT AT PANEL BOARD
ISC = VA base
( V base x PU Z cable )
x F1 x F2 x F3 x F4
ISC = 20075.60073 A
COMPUTE FOR FAULT AT BUS BAR (XFB) COMPUTE FOR FAULT AT DP1 (XF1)
PER UNIT Z OF CABLE USING CURRENT DIVIDER
Rtotal = 0.00129
PU Z cable = VA base x Z cable x 2
(V base)2 XF1= XFB (Rtotal/WIRE Resistance to DP1)
8542.84 A
Z cable 0.005728 THEREFORE USE BREAKERS AT DP1 WITH AIC RATING ABOVE 8542.8 A
PU Z cable = 0.021657
COMPUTE FOR FAULT AT DP4 (XF4) COMPUTE FOR FAULT AT DP3 (XF3)
USING CURRENT DIVIDER USING CURRENT DIVIDER
Rtotal = 0.00129 Rtotal = 0.00129
XF1= XFB (Rtotal/WIRE Resistance to DP4) XF1= XFB (Rtotal/WIRE Resistance to DP3)
3203.56 A 3942.84 A
THEREFORE USE BREAKERS AT DP2 WITH AIC THEREFORE USE BREAKERS AT DP2 WITH AIC
RATING ABOVE 3203.56 A RATING ABOVE 3942.8 A
VD = (SERVICE DROP RESISTANCE + FEEDER CONDUCTOR RESISTANCE + MAIN TO FEEDER TAP RESISTANCE) X DEMAND CURRENT
3.648957 V
(SERVICE DROP RESISTANCE + FEEDER CONDUCTOR RESISTANCE + MAIN TO FEEDER TAP RESISTANCE+ SUBFEEDER RESISTANCE TO
VD =
DP1) X DEMAND CURRENT
0.774457 V
(SERVICE DROP RESISTANCE + FEEDER CONDUCTOR RESISTANCE + MAIN TO FEEDER TAP RESISTANCE+ SUBFEEDER RESISTANCE TO
VD =
DP2) X DEMAND CURRENT
1.146024 V
(SERVICE DROP RESISTANCE + FEEDER CONDUCTOR RESISTANCE + MAIN TO FEEDER TAP RESISTANCE+ SUBFEEDER RESISTANCE TO
VD =
DP3) X DEMAND CURRENT
1.087141 V
(SERVICE DROP RESISTANCE + FEEDER CONDUCTOR RESISTANCE + MAIN TO FEEDER TAP RESISTANCE+ SUBFEEDER RESISTANCE TO
VD =
DP3) X DEMAND CURRENT
1.221148 V