Tier 3
Tier 3
UptimeInstitute
Tier Classification Objectives
• Basic Capacity
• Redundant Capacity Component & distribution paths
• Maintenance opportunity
• Failure response
Tier Classifications
Summary
• Non-redundant capacity components ("N" only)
• Single distribution path
Summary
• Redundant capacity components (N+R)
(Engine generators, UPS modules, IT and UPS cooling)
• Single distribution path
Summary
• Redundant capacity components and independent distribution paths (transformers and transfer switches are
path elements).
• Dual distribution path.
• Elements of a distribution path may be inactive.
• No runtime limits on engine-generator capacity at design load.
• Tier IV requires physical isolation (compartment) to prevent a single event from simultaneously impacting more
Continous Cooling:
• Continuous Cooling is the capability to maintain steady state in the critical environments during a UPS
Automatic Control :
Summary
• Redundant capacity components & Redundant active distribution paths
• Compartmentalization of both capacity components and distribution paths.
• "N" after any failure..
• Continuous Cooling for critical IT and UPS systems.
• No runtime limits on engine-generator capacity at design load
• Each and Every capacity component and distribution path element can sustain a failure, error, planned, or
unplanned event without impacting the Critical Environment or IT processes
Tier Classifications Table Summary
TIER I TIER II TIER III TIER IV
1 active and 1
Distribution Path 1 1 2 Simultaneously Active
alternate
Compartmentalization No No No Yes
• Tier topology requires that the load capacity of engine generators bearing one of the three main ISO 8528-1
ratings (Continuous, Prime, Standby) must be considered differently, based on the specific rating.
a) Continuous-rated engine generators can be run for an unlimited number of hours at the rated kW.
b) Prime-rated engine generators can be run for a limited number of hours at the rated kW. As stated in ISO 8528-1, the
capacity of a Prime-rated engine generator must be reduced to 70% (derated) to operate on an unlimited basis.
c) Standby engine generators are, by definition, held to an annual run-hour limitation. Some manufactures state a
different, reduced capacity at which the engine generator can operate on an unlimited basis either in the product
EG Fuel System
• Tier I - 12 hours fuel storage for engine generator(s)
Tier ? ….
Tier ? ….
Ancilliary Systems (2)
Building Automation
• Includes SCADA, BAS/BMS, EPO.
• Tier Ill requires that Critical Environment must remain stable with
any control element out of service for calibration, repair, or
replacement on a scheduled basis.
• Backup on-site makeup water storage is required for sites using evaporative
cooling
• The makeup water system must meet applicable topology criteria by Tier to point
of delivery for a minimum duration of 12 hours.
Make Up Water
Illustration
Ancilliary Systems (4)
•q
Q&A