GAS SYSTEM
SERIES 400 BIOGAS
480V / 60 Hz
NOx < 500 mg/Nm3
SYSTEM RATINGS
Gas genset with optional heat recovery
(90°/70°C heating water circuit)
Genset Engine Output Energy Efficiency Methane
Type Type Elect.1) Therm.2) Exhaust3) Low Temp. input4) Electr. Total number5)
kWel. kWth. kWth. (°C) kWth. (°C) kW nel. (%) ntot (%)
MTU 6R400 GS B3066 L8 175 139 94 (180) --- 491 35.6 83.0 ≥ 120
MTU 6R400 GS B3066 Z8 200 150 146 (180) 13 (50) 559 35.7 88.7 ≥ 120
MTU 12V400 GS B3042 Z7 350 239 226 (180) --- 951 36.8 85.7 ≥ 120
1) Rated power at nominal voltage, power factor = 1,0 and nominal frequency
2) Heat output from engine cooling with tolerance of ± 8%
3) Heat output from exhaust (exhaust cooling to 180°C) with tolerance of ± 8%
4) Performance data in accordance with ISO 3046/I-2002 with tolerance of 5%
5) Referenced methane number
Project specific data on request:
- different alternator voltage
- different flow-/return-temperatures, hot cooling, methane number, installation conditions etc.
- Container
DRAWINGS AND DIMENSIONS
H
M12*1.5
EMA 1
DS
TP65-230/2/50Hz
93.25114-0067
93.25114-0067
SS
L B
W
Note: This drawing is provided for reference only and should not be used for installation planning.
Genset Type Dimensions Genset (L x W x H) Cogeneration module (L x W x H)
MTU 6R400 GS (L8) --- 3680 x 1870 x 2140 mm
MTU 6R400 GS (Z8) 3370 x 1750 x 2100 mm 3680 x 1870 x 2140 mm
MTU 12V400 GS (Z7) 3940 x 1690 x 2130 mm 3820 x 1840 x 2260 mm
ENGINE DATA
3066 3042
Configuration in-line Configuration 90°V
No. of cylinders 6 No. of cylinders 12
Subject to change. | 3236771 | Edition 02/14 | ENC 2014-08 | Printed in Germany on chlorine-free bleached papaer.
Bore/Stroke 130/155 mm Bore/Stroke 130/142 mm
Cyl. displacement 2.06 lit. Cyl. displacement 1.88 lit.
Rated speed 1800 rpm Rated speed 1800 rpm
DESIGN AND EQUIPMENT (EXTRACT)
// Sliding gear starter 24V
// Gas supply with electronically controlled gas metering valve
// Electronic high-voltage capacitor ignition system with one ignition coil
per cylinder
// Electronic speed governor for speed and power output control with
automatic knocking control
Any specifications, descriptions, values, data or other information related to dimensions, power or other technical performance criteria of the goods as provided in
this general productinformation are to be understood as non-binding and may be subject to further changes such as but not limited to technical evolution at any time.
Version: 01.08.2014, materials and specifications subject to change without notice due to technical advances.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com