0% found this document useful (0 votes)
528 views2 pages

4090-9001 Manual Installation

panell

Uploaded by

Sergio Sergio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
528 views2 pages

4090-9001 Manual Installation

panell

Uploaded by

Sergio Sergio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

4090-9001 Supervised IAM Installation Instructions

Mechanically Installing the Supervised IAM Cautions, Warnings, and Regulatory Information
Install the Supervised IAM into a UL Listed single-gang, 4-inch square, or 4-inch octagonal electrical box (not supplied) using Figure 4 as a reference.
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
Mount the Supervised IAM to the electrical box as follows:
this product and associated equipment. Product operation and reliability depend upon proper installation.
1. Insert the Supervised IAM into the electrical box; the attached field wiring holds the Supervised IAM in place inside the electrical box.
2. Secure the cover to the back box using the two #6/32 flathead screws. DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents
of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.

ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.

STATIC HAZARD Static electricity can damage components. Handle as follows:


• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.

TEMPERATURE RANGE -32° to 158°F (0° to 70°C)

Introduction
IDNet™
The 4090-9001 Supervised Individual Addressable Module (IAM) provide four-state status information (NORMAL, OPEN, CURRENT-LIMITED, and
SHORT) to the 4010ES, 4100U, and 4100ES Fire Alarm Control Panel (FACP) via the IDNet channel. The IDNet channel provides the communication
link between Supervised IAM and the FACP and powers the entire IAM circuitry. A typical application for this module would be to monitor a water-
flow switch.
MAPNET II™
The 4090-9001 Supervised IAM provides three-state status information (NORMAL, OPEN, and ALARM) to the host FACP via the MAPNET II channel.
Applications that require current limit sensing are not compatible with MAPNET II channels (Tamper/Waterflow on the same IAM, Manual release/
abort, etc.). The MAPNET II channel provides the communication link between the Supervised IAM and host 4100, or 4120, or 4020 FACP and pow-
ers the entire IAM circuitry.

Installation
Supervised IAM installation consists of the following:
1. Setting the Supervised IAMs address
2. Making electrical connections to the Supervised IAM
3. Mechanically installing the Supervised IAM
Figure 4: Supervised IAM Back Box Installation
Note: The LED flashes approximately once every three seconds to indicate valid communications with the FACP.
Note: Simplex offers semi-flush and surface covers (ordered separately) with a light pipe. The cover(s) with light pipe allow viewing of the communi-
cations LED without taking the cover off. Installation of the 4090-9806 semi-flush cover and 4090-9807 surface cover are detailed in publication 4090
IDNet Semi-Flush/Surface Covers and IAM Bracket Installation Instruction 574-796 .

Figure 1: Supervised IAM Installation

© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® 574-331 Rev H
product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and
National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).

574-331 Rev H *0574331H*


4090-9001 Supervised IAM Installation Instructions 4090-9001 Supervised IAM Installation Instructions

Setting the Supervised IAM Address Making Electrical Connections to the Supervised IAM
Input and output signals connect to the Supervised IAM via the terminals (1-4) as illustrated in Figure 1. Terminal connections for the IAM are
Note: The IDNet channel (4010, 4010ES, 4100U, and 4100ES) supports address codes 1 through 250. The 4008 supports address codes 1 through
illustrated in Figure 1.
200. The MAPNET II channel (4100, or 4120, or 4020 FACP) supports address codes 1 through 127.
Note: Do not loop wire under terminals. Break wire runs to provide supervision.
Each Supervised IAM has a unique address. The address of the IAM is set via an eight position DIP switch (Figure 1), DIP switch position 1 is the least
significant bit (LSB) and position 8 is the most significant bit (MSB). Set the IAMs address using Figure 2 as reference. Use a small screwdriver or
pen to set the switches. The device address for the Supervised IAM should be written on the re-sealable label, this information provides an aid in
troubleshooting the system.

Note: DIP switch in “1” position is “ON” while DIP switch in “0” position is “OFF.”

Figure 3: Supervised IAM Connections

Note:
1. When connecting two wires to one terminal, position one wire on each side of the terminal screw.
2. IDNet and MAPNET II lines are 18 AWG twisted pair (shield recommended).
3. Maximum allowable run from FACP to farthest device not to exceed 2500 feet. Maximum total wire (including all T-Taps) from FACP is 10000
feet.
4. Maximum wire length is 400 feet, #18 AWG.
5. Refer to Field Wiring Diagram 842-073 for further information on wiring Supervised IAMs to IDNet. Refer to Field Wiring Diagrams 841-804 or
841-996 for further information on wiring Supervised IAMs to MAPNET II. IDNet and MAPNET II wiring are supervised and power-limited.

Figure 2: Supervised IAM Address Chart

Note: MAPNET II supports address codes 1 through 127 only.

4008 FACP (IDNet Channel)


Configure the Supervised IAM to the host 4008 FACP using the 4008 Fire Alarm Installation, Programming and Operating Instructions 579-716 .
4010 FACP (IDNet Channel)
Configure the Supervised IAM to the 4010 panel using 4010 Fire Alarm - Installation and Programming 574-187 and 4010 Fire Alarm - Installing,
Operating, and Programming Instructions (574-052). Refer to 4010 panel label 526-444 for appropriate revision of the instructions to be used.
4100U, 4100ES, and 4010ES FACP (IDNet Channel)
Configure the Supervised IAM using the ES Panel Programmer’s Manual 574-849.
4100/4120/4020 FACP (MAPNET II Channel)
Configure the Supervised IAM to the host FACP using the 4100, 4120, or 4020 Programmer’s Report. The Supervised IAM address and location must
match up with the address listed in the specification sheets of the 4100, 4120, or 4020 Programmer’s Report.

Note: Refer to the FACP label for appropriate revision of instructions.

page 2 574-331 Rev H page 3 574-331 Rev H

You might also like