EDS Engg QC Note-1

This document provides an example line calculation according to IEC 60364 for a switchboard with line 8 carrying a load. It includes calculations for: - Load characteristics such as power, voltage, current - Cable sizing factors for ambient temperature and cable grouping - Cable ampacity and voltage drop calculations to ensure cable is appropriately sized - Short circuit withstand calculations to ensure protection devices will operate properly

Uploaded by

shrikanth5singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
97 views3 pages

EDS Engg QC Note-1

This document provides an example line calculation according to IEC 60364 for a switchboard with line 8 carrying a load. It includes calculations for: - Load characteristics such as power, voltage, current - Cable sizing factors for ambient temperature and cable grouping - Cable ampacity and voltage drop calculations to ensure cable is appropriately sized - Short circuit withstand calculations to ensure protection devices will operate properly

Uploaded by

shrikanth5singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

DT 18.07.

19
Zamil EDS Engg QC note-1

Note: for ease & simplified, refer to manufacture catalog for Vd factor instead of k (Rcos fi + x sing fi) values.

Encl: EXMAPLE AS PER IEC 60364


EXAMPLE

Line analytical calculations according to IEC 60364


Switchboard - Working voltage DB2 , Switchboard , 3~400V 50Hz
Line No 8 , LOAD 8
Load electrical characteristics
Number of phases / Rated voltage U 3~400 V
Installed power Pinst 50,00 kW
Simultaneity η 1,00
Absorbed power P 50,00 kW
Power factor cosφ 0,85
Load type Sockets
Design current Ib=P/(1.732·U·cosφ) 84,9 A

Circuit protection device


Protection device nominal current In 100 A
Basic condition holds Ib < In < Iz 84,9 < 100 < 105,0

Installation Method, Correction factors


Number : 31 (Table A.52.3)
Multi-core cables on perforated tray run horizontally or vertically
Reference Method : E
Air temperature, Table B.52.14 = 35°C
Number of cable trays = 2
Number of cables per tray or ladder = 6
Cable trays are running horizontally
Cables are touching

Ambient temperature correction factor , Table B.52.14 k1 0,94


Grouping correction factor , Table B.52.20 k2 0,73

Cable cross-section sizing


Cable NYY-O 3X50+25 sm + NYY 1X25 re
Maximum permissible conductor temperature θcond,max 70,0 °C
Table with current rating of cables under reference conditions Table B.52.10 col. 3
Current rating of cable from the above table Ir 153,0 A
Current rating of cable under operation conditions Iz = Ir·k1·k2 105,0 A
Cable losses Ploss 8,4 W/m
Cable conductor temperature θcu 57,9 °C
Cable cross-section D 30,0 mm
Cable weight G 2.200,0 kg/km

Cable check to voltage drop


Direct current resistance at 20°C (IEC 60502-1) R20 0,387 Ω/km
Corrected direct current resistance at 70°C R 0,462 Ω/km
Cable inductive reactance (IEC 60502-1) X 0,111 Ω/km
Cable length L 15,0 m
Cable impedance Z = L·(R·cosφ + X·sinφ) 0,007 Ω
Cable voltage drop ΔU = 1.732·Ib·Z 0,99 V
Cable voltage drop % ΔU% = (ΔU·100)/U 0,25 %
Cable permissible voltage drop ΔUmax% 2,00 %
Voltage drop % from the beginning of the installation ΔUtotal 0,66 %

Short-circuit endurance
Prospective short circuit current on switchboard busbars Ik 10,04 kA
Conductor cross-section q 50,0 mm²
Material coefficient for copper conductors k 115 A/mm²

30/7/2016 Page 1
TiSoft ElectricalDesign LineDetailedCalculationIEC60364
Line analytical calculations according to IEC 60364

Short-circuit permissible cut time t 5 s


Minimum conductor cross-section qmin mm²

Tripping check
Protection device characteristic curve MCB B
Instantaneous element operation current I5 500 A
Source impedance r = U/Ik 0,02291 Ohms
Short-circuit current at the end of the line Io = U/(r+Z) 7.752 A
Basic condition holds I5 < Io 500 < 7.752

Page 2 30/7/2016
LineDetailedCalculationIEC60364 TiSoft ElectricalDesign