Piping Spec C Class
Piping Spec C Class
WC
Gate ½” – 1 ½” GA806 800# API SW 800# Socket weld, Bolted Bonnet, OS&Y
½” – 1 ½” GA807 800# API SW x NPT 800# SW x NPT, Bolted Bonnet, OS&Y
½” – 1 ½” GA808 800# API NPT 800# Screwed, Bolted Bonnet, OS&Y
2” – 6” GA600 600# Raised Face 600# RF, Bolted Bonnet, OS&Y
8” – 24” GA601 600# Raised Face 600#RF, Bolted Bonnet, OS&Y, Gear Operated
Globe ½” – 1 ½” GL806 800# API SW 800# Socket weld, Bolted Bonnet, OS&Y
½” – 1 ½” GL807 800# API SW x NPT 800# SW x NPT, Bolted Bonnet, OS&Y
½” – 1 ½” GL808 800# API NPT 800# Screwed, Bolted Bonnet, OS&Y
2” – 4” GL600 600# Raised Face 600# RF Bolted Bonnet, OS&Y
6” – 24” GL601 600# Raised Face 600# RF Bolted Bonnet, OS&Y, Gear Operated
Needle ¼”-3/4” NE1508 6000# NPT
Testing and Radiography: 10% of circumferential butt welds shall be 100% X-Rayed in compliance with ASME B31.3
Inspection Hydrotesting: Per ASME B31.3: Butt weld piping shall be tested at 1.5 x MAWP for a minimum of 10
minutes, small bore SW or threaded piping is leak tested to 100 psi with air.
Post Weld Heat Treatment: Not required below 14”
Additional testing as required by Client Specifications
Notes: 1. Valve body material to be A-105 or A-216,
2. Ball valves not recommended above 200°F, use gate valves.
3. Full port valves to be designated by FP after tag number.
4. See Table A-01 for piping system branch connection.