Interfacing Deif A.V.R y Speed Control
Interfacing Deif A.V.R y Speed Control
DEIF A/S, Frisenborgvej 33 Tel.: +45 9614 9614, Fax: +45 9614 9615
DK-7800 Skive, Denmark E-mail: [email protected], URL: www.deif.com
Interfacing DEIF equipment to governors and AVRs Application Notes
Table of contents
General purpose
This document includes application notes for interfacing DEIF’s equipment of the uni-line, multi-
line 2 and Delomatic series to governors and AVRs. It mainly includes examples of different
applications suitable for the unit.
The general purpose of the Application Notes is to offer the designer information about suitable
applications interfacing to governors and AVRs.
Please make sure to read the relevant documentation before working with the
DEIF equipment and the gen-set to be controlled. Failure to do this could
result in damage to the equipment or human injury.
Intended users
The Application Notes is mainly intended for the person responsible for designing systems. In most
cases, this would be a panel builder designer. Naturally, other users might also find useful
information in this document.
Contents/overall structure
The Application Notes is divided into chapters, and in order to make the structure of the
document simple and easy to use, each chapter will begin from the top of a new page.
Safety issues
Installing the DEIF equipment implies work with dangerous currents and voltages. Therefore, the
installation should only be carried out by authorised personnel who understand the risks involved in
working with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.
Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these
are noticed, they will be highlighted in order to separate them from the general text.
Notes
The notes provide general information which will be helpful for the reader to bear
in mind.
Warnings
The following abbreviations and names are used for DEIF units:
5. Commissioning
Since the DEIF units all contain frequency as well as power control facilities and
use these for control simultaneously, the resulting system will be isochronous
(without speed droop), even though the governors are adjusted with droop.
Even though speed droop is recommended, the DEIF units AGC, BGC, PPU and
GPC can control isochronous speed governors (without droop) when using
analogue/PWM output for speed control. Delomatic 3 and uni-line always require
droop.
This means that the generator AVR must have a voltage droop of 3-4% (voltage dropping 3-
4% from no load to full load when the DEIF equipment has no control). To ensure equal var
sharing on parallel running generators, the voltage droop must be the same for all generators.
Since the DEIF units all have options for voltage as well as reactive power/power
factor control facilities and use these for control simultaneously, the resulting
system, if the option is selected, will be with fixed voltage (without voltage droop)
even though the AVRs are adjusted with droop.
As especially governors are sensitive to the external circuit impedance, it is essential that the initial
settings of speed governor/AVR are done with the Delomatic connected and live, but disabled (set
the Delomatic in "switchboard mode" by deactivating the AUTO input on the module SCM-1
(terminals 26-28)). This will "disable" the control outputs, but the generator protection is still active.
If you fail to do this, you may experience control problems later on. After this:
As especially governors are sensitive to the external circuit impedance, it is essential that the
initial settings of speed governor/AVR are done with the PPU/GPC/AGC/BGC connected and
live, but disabled (set the PPU/GPC in "manual mode" by deactivating the "start sync./contr."
input on terminals 25 (input)-28 (com.)). This will "disable" the control outputs, but the generator
protection is still active. If you fail to do this, you may experience control problems later on. After
this:
After this you can activate the "start sync./contr." input again/set the AGC/BGC back in AUTO.
®
With multi-line 2 PPU/GPC/AGC PWM output for Caterpillar
Since the PWM initial setting has an influence on the start-up speed of the engine, the first thing to
do is to set this (setting 2272 for multi-line, 2662 for AGC):
Adjusting PI (Proportional Integral) step regulators (with relay outputs) and PID (Proportional
Integral Differential) (with analogue outputs) controllers is not easy. The following is a short cut,
giving you an acceptable result (maybe not perfect, but acceptable).
Delomatic/PPU/GPC/AGC/BGC
The equipment is delivered with a factory setting, which will be acceptable in 90% of the cases.
Start the generator and test it. The worst thing that can happen is a generator trip, in which case
a new attempt must be made.
Analogue output PI
The analogue speed output can be used for engines with electronic governors.
Both Delomatic and PPU/GPC/AGC/BGC accept push-button inputs for manual speed control
and can be connected directly, even if manual running is required.
The analogue voltage output can be used for generators with electronic AVRs.
Both Delomatic and PPU/GPC/AGC/BGC accept push-button inputs for manual voltage control
and can be connected directly, even if manual running is required.
1) The integral time (the time to compensate for deviations from set point) should be as short
as possible, but to avoid hunting the setting is recommended to give a fairly long integral
time, so, as a beginning, the integral time (Ki factor in multi-line) can remain as factory
setting.
2) The gain is now adjusted. Increase the value until the speed governor/AVR becomes
unstable, and decrease until it stabilises again.
3) Repeat 2), but this time by lowering the integral time (increase Ki in multi-line, decrease Tn
in Delomatic) until instability, and increase the integral time again until stability is reached.
4) The easiest way to test is to use (if possible) a load bank, applying "jumps" in generator
load and thereby testing the speed/AVR control.
There are 2 settings: Time pulse, which is the shortest relay "ON" signal time.
Gain Kp, which is the amplification factor for the proportional part.
The shortest acceptable time pulse time is dependent on the reaction of the governor/AVR and
connection type. Slow reaction => long time pulse.
Multi-line:
Apart from the Kp (proportional gain) and Ki (integrator gain) there are settings for:
Electronic potentiometer:
If an electronic potentiometer is being used to convert the relay signals into analogue value, both
the time pulse and the gain factory setting can be used. In this case the adjustments are easiest
done on the electronic potentiometer, gain = a combination of ∆Uo (full scale output) and TIME
(sec.). Higher ∆Uo/shorter TIME = higher gain.
After finding the proper time pulse length, the gain Kp is adjusted. Increase the value until the
speed becomes unstable, and decrease until it stabilises again.
After finding the proper time pulse length, the gain Kp is adjusted. Increase the value until the
voltage becomes unstable, and decrease until it stabilises again.
Time
As it can be seen, 2-3 "overshoots" before stabilising after a sudden change are OK. If more
"overshoots" are present, decrease the gain (= increase TIME on the electronic potentiometer) and
try again.
Time
If there are no "overshoots", the time to get to nominal value may be too long.
Time
The shortest Tn is dependent on the reaction of the governor/AVR and connection type. Slow
reaction => longer Tn.
Electronic potentiometer:
If an electronic potentiometer is being used to convert the relay signals into analogue value, both
the time pulse and the gain potentiometer centre position can be used. In this case the adjustments
are done on the electronic potentiometer, gain = a combination of ∆Uo (full scale output) and TIME
(sec.). Increase ∆Uo/decrease TIME = increase gain.
After finding the proper time pulse length, the gain Xp is adjusted. Increase the value until the
speed becomes unstable, and decrease until it stabilises again.
After finding the proper time pulse length, the gain Kp is adjusted. Increase the value until the
voltage becomes unstable, and decrease until it stabilises again.
On the uni-line synchroniser FAS-115DG the voltage control relay output settings
are fixed and cannot be adjusted. This is done under the assumption that the
outputs are used for an electronic AVR or an electronic potentiometer, where
adjustments can be made.
For resulting speed/voltage curves please refer to the chapter Resulting speed/voltage curve upon
load change.
As it can be seen, 2-3 "overshoots" before stabilising after a sudden change are OK. If more
"overshoots" are present, decrease the gain (increase TIME on the electronic potentiometer) and
try again.
The following contains indications of resistor values. These values are for
guidance only, and you may have to change the resistors to obtain proper
control. Generally, choosing too big resistors across the +/- 20mA outputs from
DEIF units will result in unstable control, choosing too small resistors will result
in the system being unable to control the generator in the full operating range (0-
100% load).
GOVERNOR
IN 2
The advantage of this solution is the possibility to do basic speed settings with the potentiometer
and thereafter let the DEIF unit take over.
GOVERNOR
IN 1 (+)
Pot
DEIF equipment terminals
IN 2 (0) EP-Q96 EPN-110DN
R1 9 (┴) 24 (┴)
IN 3 (signal) 10 (+) 23 (+)
7. Governor interfaces
This chapter refers to the chapter 6 diagrams for terminals and resistor values
unless otherwise stated.
Barber-Colman DYNA 1
DYNA I is intended for a potentiometer connected to terminal D (+8V DC), H (wiper) and F (+4V
DC). When moving the wiper towards terminal D, the speed increases. Both direct and
combined control circuits can be used:
The EP-Q/EPN electronic potentiometers must be set to lowest range, +/- 300 mV
~ +/- 3Hz.
1) Use the speed increase (term. 15)/decrease (term. 16) binary inputs and relay outputs from
the DEIF equipment. Inputs activate when connected to terminal 1 (+9…30V DC).
2) Replace the remote speed potentiometer.
BARBER-
COLMAN
DYN1 350KΩ
11
DEIF equipment terminals
10 EP-Q96 EPN-110DN
10KΩ 10KΩ 10 (+) 23 (+)
12
9 (┴) 24 (┴)
BARBER-
COLMAN
DYN1 350KΩ
11 DELO- PPU/
MATIC GPC/
100Ω SCM-1 AGC BGC
10
10KΩ 10KΩ 29 (+) 66 (+) 66 (+)
12
30 (┴) 67 (┴) 65 (┴)
68
94
BATTERY -
If DROOP is not needed, the connection can be removed.
PRIMARY 67 +
THROTTLE (9)
68
DROOP (3) 95 +
94
BATTERY - (19)
If screened cable is used, the screen must be connected to ECM terminal 19 only.
Cummins Power Command Control (PCC) load sharing system and multi-line 2
Since the multi-line 2 (ML-2) uses a 0…5V DC load sharing line, which is not compatible with the
PCC load sharing line, a conversion must be made.
As the same problem occurs with other manufacturers’ systems (Barber-Colman (BC)/Wood-
ward/GAC), Cummins has made an interface unit called "Isochronous Load Sharing (ILSI) kit",
Cummins part no. 300-5456, which is the one to be used for ML-2 connection to PCC.
The load sharing is for power load sharing only, Kvar load sharing must be made using different
units.
Following the Cummins instruction sheet C-604 11-01, the procedure is as follows:
It is important that the "Calibration Switch" is moved back to normal position before starting the
generators. Failure to do this will provoke reverse power trips.
TB2: 6 5 4 3 2 1
ILSI unit
TB1: 1 2
A higher voltage range can be used (200 Ω to give 4V DC). In this case the EMR
frequency setting must be checked to be 49-51Hz.
GAC 5xxx
G
J
K DEIF equipment terminals
L EP-Q96 EPN-110DN
10 (+) 23 (+)
P
9 (┴) 24 (┴)
10kΩ
E(0V) 75Ω
GAC 5xxx
G
J
DELO- PPU/
K MATIC GPC/
L SCM-1 AGC BGC
29 (+) 66 (+) 66 (+)
P
30 (┴) 67 (┴) 65 (┴)
10kΩ
E(0V) 75Ω
For EP-Q/EPN the "up" input will result in a decreasing speed, and the "down" input will result in an
increasing speed.
For Delomatic/multi-line the output signal must be set to give -10.0mA on power up. Since the
connections are reversed, the ESD 5500 will see a +2.5V DC across the 250 Ω resistor, and
increase/decrease will work properly.
On the ESD 5500 terminal J can be used instead of N. The J input has a lower
impedance (5 KΩ) than N (1 MΩ). The G terminal on the ESD 5500 is connected to
battery -.
ESD 5500
DEIF equipment terminals
EP-Q96 EPN-110DN
N(Input) 10 (+) 23 (+)
G(Gnd) 9 (┴) 24 (┴)
DELO- PPU/
ESD 5500
MATIC GPC/
SCM-1 AGC BGC
G(Gnd) 29 (+) 66 (+) 66 (+)
30 (┴) 67 (┴) 65 (┴)
250Ω
N(Input)
GAC 5xxx
G
J
K DEIF equipment terminals
L EP-Q96 EPN-110DN
10 (+) 23 (+)
P
9 (┴) 24 (┴)
10kΩ
E(0V) 75Ω
GAC 5xxx
G
J
DELO- PPU/
K MATIC GPC/
L SCM-1 AGC BGC
29 (+) 66 (+) 66 (+)
P
30 (┴) 67 (┴) 65 (┴)
10kΩ
E(0V) 75Ω
E1-D/F
Heinzmann type E6, E6V, E10, E16 and E30 speed governor
The E6...E30 series is intended for a 5K speed trim potentiometer. The DEIF equipment giving a
voltage output can be connected in series with the wiper of the potentiometer:
Heinzmann KG 6 - 04 to KG10 - 04
The Heinzmann KG series accepts voltage signals (1…5V DC) directly connected:
Speed raise: X1-EE (cable wire 4) to gnd, X1-FF (cable wire 3) to +24V DC.
Speed lower: X1-u (cable wire 14) to gnd, X1-v (cable wire 13) to +24V DC.
Set the multi-line analogue governor offset to 50% to compensate the MTU speed
internal offset.
ECM
J1/59(Lower)
J1/7(Raise)
J1/18(-)
The ECM terminal numbers refer to the ECM module connectors. The equivalent
Customer interface connector P3 connectors are:
ECM P3
J1/59 29
J1/7 28
J1/18 12
The diodes are to prevent negative signals to the EMS2 which it cannot accept.
EMS2 1KΩ
C (+5V) Gn/Sb
DEIF equipment terminals
B (Input) Gn/Or EP-Q96 EPN-110DN
250Ω 10 (+) 23 (+)
A (0V) Gn/Y 9 (┴) 24 (┴)
A (0V) Gn/Y
Abbreviations for wire colours on EMS2: Gn/Sb: Green/black, Gn/Or: Green/orange, Gn/Y:
Green/yellow.
Binary signals:
701A
11(Lower)
+24V DC
12(Raise)
8(-) 0V DC
Due to the internal circuits, the standard DEIF way of doing the connections cannot be used.
Instead of connecting the outputs from the DEIF units to one side of the potentiometer and the
wiper input, connections must be made for ground and wiper. Because of this the usual way of
initial setting by switching off the DEIF unit during initial governor adjustment cannot be used. The
DEIF unit must be switched ON and the output adjusted to 0V DC when adjusting the governor.
After this normal procedure can be carried out. Note also that the output is "inverted", connect the +
output from the DEIF unit to the gnd on the load sensor. This is possible due to the fact that the
DEIF unit’s output is galvanically separated from the rest of the unit.
The Woodward load sensor has not yet been tried with a Delomatic/PPU/GPC/AGC/BGC system,
so the needed connections cannot be given at this stage.
The input can be configured to +/- 3V DC as well. Refer to Woodward for details.
The electronic potentiometers can be changed into giving 0-20mA outputs, but this is a special
version that has to be asked for. The Delomatic/PPU/GPC/AGC/BGC can connect directly:
UG8 Digital
DELO- PPU/
SPECIAL SPECIAL MATIC GPC/
EP-Q96 EPN-110DN SCM-1 AGC BGC
9(+) 10 (+) 23 (+) 29 (+) 66 (+) 66 (+)
10(-) 9 (┴) 24 (┴) 30 (┴) 67 (┴) 65 (┴)
The following contains indications of resistor values. These values are for
guidance only, and you may have to change the resistors to obtain proper
control. Generally, choosing too big resistors across the +/- 20mA outputs from
DEIF units will result in unstable control, choosing too small resistors will result
in the system being unable to control the generator in the full operating range
(maintaining voltage in the 0-100% load range).
AVR
IN 2
The advantage of this solution is the possibility to do basic speed settings with the potentiometer
and thereafter let the DEIF unit take over.
AVR
IN 1 (+)
Pot
DEIF equipment terminals
IN 2 (0) EP-Q96 EPN-110DN
R1 9 (┴) 24 (┴)
IN 3 (signal) 10 (+) 23 (+)
The advantage of this solution is the possibility to do basic speed settings with the potentiometer
and thereafter let the DEIF unit take over.
AVR
9. AVR interfaces
This chapter refers to the chapter 8 diagrams for terminals and resistor values
unless otherwise stated.
The COSIMAT has an auxiliary input for external equipment, which accepts 0…10V DC signals.
As the input only accepts positive signals, a diode is needed to prevent negative signals:
COSIMAT
Adjustment:
The diode mounted in the connection prevents positive voltages from being sent to the SSR unit.
As both EP-Q/EPN and Delomatic/PPU/GPC/AGC/BGC are using bipolar galvanically separated
outputs, this is not a problem.
When adjusting the generator voltage initially, adjust the (internal) idle voltage to 25% above
nominal. The DEIF units will then bring the voltage down to nominal level when activated:
SSR
Caterpillar® VR3
Set the EP-Q/EPN output to +/-5V DC.
Caterpillar® VR6
Set the EP-Q/EPN output to +/-5V DC.
Caterpillar® DVR
The DVR 2-wire input gives an increasing generator voltage with increasing resistance.
Caterpillar® CDVR
The CDVR accepts binary inputs for voltage up/down control or analogue signals.
Binary inputs:
CDVR
P9-4(Lower)
P9-5(Raise)
P9-6(common)
As the external control is 2-wire potentiometer, the following circuit must be used:
Spade con-
nectors
Bottom of AVR, as mounted in generator
470Ω
Using DEIF equipment:
Terminal strip ST 4
Spade con-
nectors
Bottom of AVR, as mounted in generator
Spade con-
nectors
Bottom of AVR, as mounted in generator
We recommend using "Digital pot U/P.F. Optional Card". When this card is fitted, terminals 35,
36 and 37 are used as follows:
Up 35
Down 36
Com. 37
Marelli M25FA502A
The M25FA502A requires a +/- 2.5V DC signal.
The signal must not exceed 3V DC in either direction. Set EP-Q/EPN range to 2.5V.
U.V.R.
DEIF equipment terminals
60Hz
EP-Q96 EPN-110DN
9 (┴) 24 (┴)
10 (+) 23 (+)
Output voltage range must be set to 9V. Since the offset required is -80%, a
special version of EP-Q/EPN is needed.
U.V.R.
DELO- PPU/
60Hz MATIC GPC/
SCM-1 AGC BGC
32 (┴) 71 (┴) 63 (┴)
31 (+) 70 (+) 64 (+)
470Ω
Stamford Newage type MA325, MA327, MX321, MX341, SR465, SX421 and SX440
These AVRs have an auxiliary input (terminal A1 and A2), which accepts voltage signals (+/-5V).
Therefore the DEIF equipment can usually be connected directly:
10. Troubleshooting