Modes Of Operation
SMCS - 4490; 7451
Table 1
Display Area Functions When In ormal Mode, Alarm Mode Or Shutdown Mode (1)
Item Of Alarm Mode
Display ormal Mode Shutdown Mode
Area
Upper AC Data Shown AC Data Shown (2) Fault Code Shown
Display
Lower Engine Data And Relay Engine Data And Relay Engine Data And Relay
Display Status Shown Status Shown Status Shown
Shutdown All Off All Off Flashing
Indicators
Fault Alarm Off Flashing (2) Off
Indicators
Key Function Normal Mode Alarm Mode Shutdown Mode
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 31/08/2010
Pesquisa de Mídia - RENR1200 - Electronic Modular Control Panel II+ (EMCP II+... Página 2 de 3
Service Enters The GSC Into Enters The GSC Into No Function
Mode Key Service Mode Service Mode
(1) For a description of the display area functions when in service mode, see the topic Service Mode.
(2) When an alarm fault is present, the fault code is shown on the upper display when the alarm codes key is pressed.
(3) This key only functions when in service mode, see the topic Service Mode.
Illustration 1 g00474240
Display Area Of Generator Set Control (GSC)
(6) Keypad
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 31/08/2010
Pesquisa de Mídia - RENR1200 - Electronic Modular Control Panel II+ (EMCP II+... Página 3 de 3
The GSC has four modes of operation. A brief description of each mode follows this paragraph. See
the individual topic for more detailed information.
ormal Mode - The GSC uses normal mode for the normal operation of the generator set. The
operator can identify the normal mode by observing the display area. When the GSC is in the normal
mode, all dedicated shutdown indicators are OFF. The fault shutdown indicator is OFF. The fault
alarm indicator is OFF and "SERV "is NOT SHOWING on the upper display.
Alarm Mode - If there is an alarm fault, the GSC will automatically go into alarm mode in order to
alert the operator. The operator can identify the alarm mode by observing the display area. When the
GSC is in alarm mode, the fault alarm indicator is FLASHING. When the alarm code key is pressed,
the fault code will be shown.
Shutdown Mode - If there is a shutdown fault, the GSC will automatically go into shutdown mode
in order to alert the operator. The operator can identify the shutdown mode by observing the display
area. When the GSC is in shutdown mode, a dedicated shutdown indicator is FLASHING, or the
fault shutdown indicator is FLASHING.
Service Mode - The GSC goes into service mode when the operator presses the service mode key on
the keypad. The operator can use service mode for the following purposes.
The operator can identify service mode by observing the display area. When the generator set is in
service mode, "SERV" is SHOWN on the upper display.
ote: Service mode can not be entered when the ECS is in the AUTO position.