Concrete Equipment Pads (2 of 2) : I0330-056b.dgn 1/24/2009 I0330-056b.dgn 1/24/2009

This document provides specifications for concrete equipment pads, including: - Pad thickness shall be a minimum of 6 inches, unless otherwise noted on plans. Edges shall have a 3/4 inch chamfer. - Anchor bolts shall be determined by the equipment manufacturer and approved by the engineer. Sleeves shall provide 1/2 inch movement and be filled with non-shrink grout. - Pads shall be level unless otherwise indicated. Wedges, shims or leveling nuts shall be used and hidden from view. - Pad height shall be the minimum to keep anchor bolts above the supporting slab, as shown in a table of minimum heights by anchor bolt diameter.

Uploaded by

hakim2020
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
802 views1 page

Concrete Equipment Pads (2 of 2) : I0330-056b.dgn 1/24/2009 I0330-056b.dgn 1/24/2009

This document provides specifications for concrete equipment pads, including: - Pad thickness shall be a minimum of 6 inches, unless otherwise noted on plans. Edges shall have a 3/4 inch chamfer. - Anchor bolts shall be determined by the equipment manufacturer and approved by the engineer. Sleeves shall provide 1/2 inch movement and be filled with non-shrink grout. - Pads shall be level unless otherwise indicated. Wedges, shims or leveling nuts shall be used and hidden from view. - Pad height shall be the minimum to keep anchor bolts above the supporting slab, as shown in a table of minimum heights by anchor bolt diameter.

Uploaded by

hakim2020
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

i0330-056B.

dgn 1/24/2009

6" MIN, TYP UNLESS


NOTED OTHERWISE EQUIPMENT NOTES:
ON PLANS 1. PAD SIZE SHALL BE MINIMUM INDICATED OR AS SHOWN ON THE PLANS OR AS
CONCRETE
ANCHORS, INDICATED BY THE MANUFACTURER AND APPROVED BY THE ENGINEER.
SEE NOTE 2. THE SIZE, NUMBER, TYPE, LOCATION, AND THREAD PROJECTION OF THE ANCHOR
3/4" BOLTS SHALL BE DETERMINED BY THE EQUIPMENT MANUFACTURER AND AS
FINISH
CHAMFER, APPROVED BY THE ENGINEER. ANCHOR BOLTS SHALL BE HELD IN POSITION WITH
GRADE
TYP A TEMPLATE OR OTHER ACCEPTABLE MEANS, MATCHING THE BASE PLATE, WHILE
PAD IS BEING PLACED.
3. ANCHOR BOLT SLEEVES SHALL BE USED TO PROVIDE MINIMUM ANCHOR BOLT
MOVEMENT OF 1/2" IN ALL HORIZONTAL DIRECTIONS. THE MINIMUM SLEEVE LENGTH
1 SHALL BE 8 TIMES THE BOLT DIAMETER.
1.5 4. ANCHOR BOLT SLEEVES SHALL HAVE A MINIMUM INTERNAL DIAMETER 1" GREATER
#5 CONT
THICKENED 6" THAN BOLT DIAMETER AND A MAXIMUM INTERNAL DIAMETER 3" GREATER THAN
EDGE OF SLAB MIN ANCHOR BOLT DIAMETER. SLEEVES SHALL BE FILLED WITH NON-SHRINK GROUT
ALL AROUND AFTER BOLTS ARE ALIGNED. SEE0330-057 .
NOTE: 5. EQUIPMENT BASES SHALL BE INSTALLED LEVEL UNLESS INDICATED OTHERWISE.
#5@12" EW AT 2"
CLR FROM TOP SURFACE WHEN ANCHORAGE OF EQUIPMENT 6. WEDGES, SHIMS, OR LEVELING NUTS SHALL BE USED TO SUPPORT THE BASE WHILE
TO PAD IS REQUIRED, USE CONCRETE THE NON-SHRINK GROUT IS PLACED. WEDGES OR SHIMS THAT ARE LEFT IN PLACE
ANCHORS SPECIFIED. SHALL NOT BE EXPOSED TO VIEW.
7. HEIGHT OF PADS SHALL BE MINIMUM REQUIRED FOR ANCHOR BOLT CLEARANCE TO
TYPE G
KEEP ANCHOR BOLT ABOVE SUPPORTING SLAB (SEE TABLE BELOW). WHERE
EQUIPMENT OR PIPING ELEVATION REQUIRE A PAD HEIGHT LESS THAN THE
6" MIN, TYP UNLESS MINIMUM SHOWN, USE TYPE "B" EQUIPMENT PAD WITH BLOCKOUT.
NOTED OTHERWISE EQUIPMENT
ON PLANS 8. AT CONTRACTOR’S OPTION, CONCRETE ANCHORS MAY BE USED IN LIEU
CONCRETE
OF CAST-IN-PLACE ANCHOR BOLTS FOR EQUIPMENT ANCHOR BOLTS LESS
ANCHORS,
THAN 3/4" DIAMETER WHEN APPROVED BY THE EQUIPMENT MANUFACTURER
SEE NOTE
AND APPROVED BY THE ENGINEER. ANCHORS SHALL BE INSTALLED WITH
3/4"
FINISH 4" MINIMUM EDGE DISTANCE IN EACH DIRECTION.
CHAMFER,
GRADE
TYP

AB DIA (IN.) 1/2 5/8 3/4 7/8 1 1 1/4 1 3/8 1 1/2 1 3/4 2
MIN PAD HT (IN.) 7 8 1/2 10 11 12 1/2 15 16 1/2 18 21 24

1
1.5
THICKENED 6" 2 - #5 CONT
EDGE OF SLAB MIN
ALL AROUND
NOTE:
#5@12" EW T&B
WHEN ANCHORAGE OF EQUIPMENT
TO PAD IS REQUIRED, USE CONCRETE
ANCHORS SPECIFIED.

TYPE H

CONCRETE EQUIPMENT PADS (2 OF 2)


NTS
DETAIL 2 OF 2