BSL-3 Design Resource
BSL-3 Design Resource
Design Resource
© Copyright 2003
Phoenix Controls Corporation
Copyright 2003, American Society of Heating, Refrigerating and Air-Conditioning, Engineers, Inc.
www.ashrae.org. Reprinted by permission from ASHRAE 2003 Handbook-Fundamentals.
Copyright 2004, NSF International, 789 N. Dixboro Road, PO Box 130140, Ann Arbor, MI 48113-0140, (734) 769-8010
(phone), (734) 769-0109 (fax), [email protected], http://www.nsf.org.
The material in this paper is for information purposes only and is subject to change without notice. Phoenix Controls
Corporation assumes no responsibility for any errors or for consequential damages that may result from the use,
misrepresentation, or translation of any of the material in this publication.
Printed in USA
Phoenix Controls BSL-3 Laboratory Design Resource
Characteristics of Biological
Containment Facilities (BSL-3) .....................................................3
Characteristics of Biological
This chapter presents an overview of the features Laboratories, 4
and categories of biocontainment laboratories, • Biosafety Cabinets, 5
along with a brief discussion of the types of
biosafety cabinets used in these labs.
BSL-3
BSL-2
BSL-1
The National Sanitation Foundation (NSF) defines a Class II cabinet as: “A ventilated
cabinet for personnel, product, and environmental protection having an open front with
inward airflow for personnel protection, downward HEPA filtered laminar airflow for
product protection, and HEPA filtered exhausted air for environmental protection.”2
Class II cabinets are further subdivided into types A and B, depending on how exhaust is
handled. Type A cabinets, which are designed for working in the absence of toxic or
volatile chemicals, may exhaust HEPA-filtered air back into the laboratory, or thimbles
(canopies) may be connected to the building exhaust system to distribute air back to
the environment. “It is possible to duct the exhaust from a Type A cabinet out of the
building,” according to the Centers for Disease Control (CDC). “However, it must be
done in a manner that does not alter the balance of the cabinet exhaust system, and
thereby disturbing the internal cabinet air flow. The typical method of ducting a Type A
cabinet is to use a ‘thimble’, or canopy hood, which maintains a small opening (usually 1
inch) around the cabinet exhaust filter housing. The volume of the exhaust must be
sufficient to maintain the flow of room air into the space between the thimble unit and
the filter housing. The thimble must be removable or be designed to allow for opera-
tional testing of the cabinet. The performance of a cabinet with this exhaust configura-
tion can be affected by fluctuations in the building exhaust system.”3
Type A cabinets should never be hard connected to an exhaust system. “‘Hard-ducting’
(i.e., direct connection) of Class II Type A cabinets to the building exhaust system is not
recommended unless a dedicated exhaust fan system with a dynamic flow balancing
mechanism is provided. The building exhaust system must be precisely matched to the
airflow from the cabinet in both volume and static pressure. However, fluctuations in air
volume and pressure that are common to all building exhaust systems make it difficult
to match the airflow requirements of the cabinet. A competent in-house maintenance
and engineering staff is required to achieve this.”4
Type B cabinets are to be hard ducted to the building exhaust system and vented outside
the building without recirculation. For this reason, low levels of volatile chemicals are
permitted in Type B cabinets.
When sizing exhaust fans, the NSF recommends allowing 2" WC (500 Pa) for a dirty HEPA
filter, in addition to the amount needed to produce the exhaust flow specified by the
2
National Sanitation Foundation/American cabinet manufacturer. The table below summarizes the requirements for the four types
National Standards Institute (NSF/ANSI),
Class II (laminar flow) biosafety cabinetry, of Class II biosafety cabinets.
NSF/ANSI 49-2004a, p. 4.
3
Centers for Disease Control (CDC),
Primary Containment for Biohazards,
Section III, http://www.cdc.gov/od/ohs/
biosfty/bsc/BSC2000sec3.htm.
4
Ibid.
Figure 1-4. Exhaust system for Guidelines for the Placement of Biosafety Cabinets
a Class II biosafety cabinet. • Isolate from other work areas
• Not in high traffic areas
• Away from airflow ducts, cross drafts
• Away from laboratory entry doors
Ventilation Requirements
Pressurization
Ventilation controls for critical laboratory environments function on multiple levels. For
Requirements
Ventilation
example, device level controls may be applied to BSCs, fume hoods or ventilated cage
systems (animal facilities), while room level controls ensure containment through direc-
tional airflow. At this level, you are likely to also find space temperature and humidity
controls. Finally, building-wide systems work to integrate the critical space controls with
the rest of the facility, which may contain areas in which pressurization control is not
needed. While these non-critical spaces still have control requirements, these are driven
primarily by comfort.
For the BSL-3 laboratory, air is drawn into the space from the surrounding areas to
maintain a negative pressure relationship. Airflow movement should always be in the
direction of increasing biological hazard or from “clean” to “dirty.” The ventilation sys-
tem shall be:
• Single-pass
• Non-recirculating
• Directional
• A ducted exhaust system
BSL-3
BSL-2
Airlock
Active Pressure
Monitor
Requirements
Ventilation
Architectural Tightness
Due to the need for gaseous decontamination, BSL-3 labs must be designed as “tight”
spaces. Air treatment systems for fumigation require that penetrations in walls, ceilings,
and floors be sealed. For the ventilation system, accommodation must be made to seal
the duct or reduce the airflow through the space, depending on the decontamination
agent. Specifically, significantly reduced airflows or conventional shut-off devices may be
required. For certain decontamination agents or other emergency conditions, bubble-
tight dampers may be installed.
Leaktight is a term that may also be used in reference to the duct system, which is
typically outside the containment barrier (room) and before any HEPA filtration or
ultraviolet (UV) decontamination. In the event the exhaust side becomes positively
pressurized, the concern exists that potentially contaminated air may leak into sur-
rounding areas. In this scenario, the definition of “leaktight” or “airtight” is based on a
given loss of pressure over a stated time period.
Please note that none of the leaktight definitions referring to outside the containment
barrier are required to be 100% leaktight. In any conversations using the word, “leaktight,”
it is highly recommended to clarify whether the reference is to the space or to the
ductwork/control device outside the space.
Ventilation Rates
While none of the guidelines indicate a specific room air change rate for higher level
biocontainment facilities, the Handbook of Laboratory Safety suggests a minimum of 6
air changes per hour (ACH) with a range from 10-20 air changes per hour for higher risk
laboratories.10 Designs for 10-12 air changes per hour for BSL-3 facilities appear to be
common and this may be lowered to 6 ACH at night when the lab is unoccupied. The air
change rate will likely be determined by equipment exhaust requirements.
10
Furr, A. Keith. CRC Handbook of Labora-
tory Safety, 5th Edition, 2000, p. 90.
11
American Association of Heating, Refrig-
erating and Air-Conditioning Engineering,
Inc. (ASHRAE), ASHRAE Handbook: 2003
HVAC Applications, p. 14.17.
12
Centers for Disease Control/National In-
stitutes of Health (CDC/NIH), Biosafety in
Microbiological and Biomedical Laboratories,
4th edition preface, http://www.cdc.gov/od/
ohs/biosfty/bmbl4/bmbl4toc.htm.
13
World Health Organization (WHO), Labo-
ratory Biosafety Manual, Third Edition, p. 3.
1085
Airflow Control
160 cfm 675 cfm 675 cfm 50 cfm 375 cfm cfm 100 cfm
Solutions
200 cfm 1440 HEPA filter 1400 Tightly closing
HEPA HEPA cfm HEPA
filter cfm filter isolation damper filter
Thimble
Exhaust
HEPA filter Exhaust
HEPA filter
Lab A Lab B
Class II Type A cabinets Class II Type B cabinets
canopy and Phoenix valve hard connected
Assumptions:
Cabinets are nominally 6' wide with 10" sash openings.
On the next two pages are several options to consider when using Phoenix Controls
Accel® II valve for device and room-level control of BSL-3 laboratories. For more details
about the features and performance of this valve, see Chapter 4.
Purge Mode
Use two-state or variable valves to modulate between a “normal” supply/exhaust level and one
that is at much higher volumes to quickly purge the space following decontamination.
Door Switch
Use a door switch to trigger an increase in the supply air into the airlock when either airlock door
is opened. (Remember that both doors will not be opened at the same time.) In addition, the
appropriate exhaust valve, corridor or bio-containment space will increase the exhaust level.
This increase in flow through the door opening ensures containment of the space.
Multi-state Cabinet
Airflow Control
Use a two-state or variable valve to accommodate varying states of operation of the biosafety
Solutions
cabinet. In addition, multi-state valves on the general exhaust will compensate for cabinet
exhaust level changes.
Fan Failure
Two-state or variable valves can be used to react to exhaust or supply fan failures. For example,
in the event of exhaust fan failure, the supply valve can be driven to minimum flow and the
exhaust valve driven to maximum flow.
System Components
custom engineered springs were selected based on passing one million cycles of full-
deflection testing. The cone assembly adjusts the open area of the venturi to system
pressure as described below so that the flow set point is maintained continuously and
instantaneously.
When there is low static pressure, less force is applied to the cone, which causes the
spring within the cone to expand and pull the cone away from the venturi. The combina-
tion of low pressure and large open area provides the desired flow.
Valve Types
With the internal pressure independent cone assembly in operation, airflow can be
regulated by positioning the shaft/cone assembly. The following types of Accel II valves
are available:
• Constant Volume: The valve’s Pivot arm locked Position at
high pressure
shaft is locked into a specific
position, which provides the
scheduled airflow via factory
calibration.
Position at
low pressure
Corporation
END VIEW
System Components
Corrosion protection
To accommodate the decontamination needs of BSL-3 spaces, Accel II valves may be protected from chemical
corrosion with a baked phenolic coating. Hydrogen peroxide fumes, tested at 30% concentration and room
temperature, had no effect on the Heresite coating. Immersion in a 5% formaldehyde solution produced an “A”
rating, meaning it had no effect.
ACTUATOR
T
COVER TAB
DO NOT BLOCK
• Constant volume (CVV series) for maintaining an airflow setpoint under variable static Access required after installation
20 PSI
END VIEW Phoenix Controls
Corporation
Newton, MA 02158 USA
PATENT NOS. 5,304,093 / 5,251,665 AND PATENTS PENDING
pressure conditions
• Two-position (PEV/PSV series) for high/low flow control (pneumatic only)
• Base upgradable (BEV/BSV series) for pneumatic flow control with feedback option (pneumatic only)
• VAV (EXV/MAV series) with VAV closed-loop feedback control (pneumatic or electric) with pneumatic for fume hood
applications or low-speed electric actuation for tracking pair applications.
• When networked with a twisted pair cable, Celeris valves form a room-level control system, providing ventilation,
volumetric offset, temperature, humidity, occupancy and emergency control.
Specifications
Construction • Available in flows from 35-6000 CFM I/O available for connecting field devices:
• 16 ga. spun aluminum valve body with (60-10,000 m3/hr)** • 3 universal inputs. Accepts volt, mA,
continuous welded seam • Response time to change in command ohms or NTC 2 or 3 thermistor signals.
• Valve bodies available as uncoated signal: • 1 digital input
aluminum or with corrosion-resistant • < 1 second (control type M and N) • 2 analog outputs. Provides volt or mA
baked phenolic coatings • < 1 minute (control type L) signals.
• Composite Teflon® shaft bearings • Response time to change in duct static • 1 digital output (Type C, 1 amp @ 24 Vac/
• Spring grade stainless steel spring and pressure: < 1 second Vdc)
PPS slider assembly Pneumatic Actuation Agency compliance:
• Supply valves* insulated with 3/8" (9.5 • CE
• Only applicable to PEV, PSV, BEV/BSV
mm) flexible closed-cell polyethylene. • UL 916 listed
and EXV/MAV-N (pneumatic control type)
Flame/smoke rating 25/50. Density is • FCC Part 15, Subpart J, Class A
• 20 psi (-0/+2 psi) with a 20 micron filter
2.0 lb/ft3 (32.0 kg/m3).
main air required (except for CVV) Room-level communcations:
Operating Range • Compressor sizing: Accel II valves are not FTT-10, 78 KB, bus topology, LonTalk™
• 32-122 °F (0-50 °C) ambient continuous air-consuming devices. For network
• 10-90% non-condensing RH compressor sizing, use: Building-level communications:
Sound • single and dual valves: 10 scim TP-1250, 1.2 MB, bus topology, LonTalk™
• triple and quad valves: 20 scim network
Designed for low sound power levels to
meet or exceed ASHRAE noise guidelines. VAV Controller
Performance Power:
• Pressure independent over a 0.6"-3.0" 24 Vac (±15%) @ 60 Hz
wc (150-750 Pa) drop across valve * Not applicable to CVV series.
Power Consumption:
• Volume control accurate to ±5% of ** Celeris triples and quads represent 2
Control Type Single Dual
airflow command signal L (low-speed electric) 13 VA 17 VA nodes on the system (main and booster).
• No additional straight duct runs needed N (pneumatic) 11 VA 11 VA
Teflon is a registered trademark of DuPont Co.
before or after valve M (high-speed electric) 48 VA 48 VA
LONWORKS is a registered trademark of Echelon Corp.
All valves include pressure independent, factory-calibrated position controllers, and are available in flows from 35-6000 CFM (60-10,000 m3/hr).**
†Accel II valves are designed to reduce sound over all frequencies, but significantly target the lower bands (125-500 Hz) to help eliminate the need for silencers.
COVER TAB
DO NOT BLOCK
Access required after installation
20 PSI
E
PATENT NOS. 5,304,093 / 5,251,665 AND PATENTS PENDING
D
E
B
B
C
F
F C A
Triple Quad
(Make-up Air (Constant Volume
Valve shown) Valve shown)
G
E B
D D
A
F C A F C
Valve Dimensions
A* B* C D E** F G
inches mm inches mm inches mm inches mm inches mm inches mm inches mm
8 — — 7.88 200 23.50 597 — — 14.13 359 28.00 711 10.13 257
10 — — 9.67 246 21.75 552 — — 16.13 410 26.20 665 11.20 284
12 — — 11.84 301 26.81 681 — — 18.13 461 32.56 827 12.13 308
System Components
2-10 20.13 511 10.13 257 24.75 629 1.5 38 16.77 426 27.70 704 21.52 547
2-12 24.13 613 12.13 308 29.81 757 1.5 38 18.75 476 34.60 879 24.76 629
3-12 37.06 941 12.13 308 29.81 757 1.5 38 18.75 476 34.60 879 36.77 934
4-12 48.26 1226 12.13 308 29.81 757 1.5 38 18.75 476 34.60 879 48.65 1236
* outer dimension ** maximum of all valve types (some configurations may be smaller)
Operating Ranges
COVER TAB
DO NOT BLOCK
Access required after installation
20 PSI
Phoenix Controls
airflow control. These valves can be used in constant volume, two-position, or VAV applica-
END VIEW Corporation
Newton, MA 02158 USA
PATENT NOS. 5,304,093 / 5,251,665 AND PATENTS PENDING
tions—all designed to maximize flow performance while reducing related noise. Valves for
VAV applications may be either electrically or pneumatically actuated.
• Pressure-independent operation: All valve types include an immediate response me-
chanical assembly to maintain airflow set point as duct static pressure varies.
• Airflow control: By positioning the flow rate controller assembly, the airflow can be ad-
justed.
Accel II valves are available in:
• Constant volume (CVV series) for maintaining an airflow setpoint under variable static
pressure conditions
• Two-position (PEV/PSV series) for high/low flow control (pneumatic only)
• Base upgradable (BEV/BSV series) for pneumatic flow control with feedback option and
upgradability to VAV (pneumatic only)
• VAV (EXV/MAV series) with VAV closed-loop feedback control (pneumatic or electric)
Specifications
Construction Performance
• 16 ga. spun aluminum valve body with continuous • Pressure independent over a 0.6"-3.0" wc
welded seam (150-750 Pa) drop across valve
• Valve bodies available as uncoated aluminum or • Volume control accurate to ±5% of airflow
with corrosion-resistant baked phenolic coatings command signal
• Composite Teflon® shaft bearings • No additional straight duct runs needed before
• Spring grade stainless steel spring and PPS slider or after valve
assembly • Available in flows from 35-6000 CFM
• Supply valves* insulated with 3/8" (9.5 mm) (60-10,000 m3/hr)
flexible closed-cell polyethylene. Flame/smoke • Response time to change in command signal:
rating 25/50. Density is 2.0 lb/ft3 (32.0 kg/m3). < 1 second
• Response time to change in duct static
Operating Range
pressure: < 1 second
• 32-122 °F (0-50 °C) ambient
• 10-90% non-condensing RH VAV Controller
Sound Controller Power:
Designed for low sound power levels to meet • ±15 Vdc, ±5% @ 0.145 amp (pneumatic only)
or exceed ASHRAE noise guidelines. • 0-10 Vdc command signal
• 0-10 Vdc flow feedback signal
• 0-10 Vdc alarm signal
Constant Two-position Upgradable VAV VAV Pneumatic Actuation:
Feature/Option Volume (PEV/PSV) (BEV/BSV) (EXV/MAV) (EXV/MAV) • Only applicable to PEV, PSV, BEV/BSV and
(CVV) Pneumatic Pneumatic Pneumatic Electric EXV/MAV-N (pneumatic control type)
• 20 psi (-0/+2 psi) with a 20 micron filter main
air required (except for CVV)
C P B A A
• Compressor sizing: Accel II valves are not
Control type Constant Pneumatic Base Analog Analog
continuous air-consuming devices. For
Volume Upgradable
compressor sizing, use:
Flow feedback signal — — Option 9 9 • single and dual valves: 10 scim
Failsafe Fixed NO/NC NO/NC NO/NC NO/NC or • triple and quad valves: 20 scim
Last Posit. Electric Actuation:
• 24 Vac (±15%) @ 60 Hz
Factory-insulated
• single and dual valves: 48 VA
valve body (supply) Option 9 9 9 9
• triple and quad valves: 96 VA
Field-adjustable flow 9 9 9 9 9
Flow alarm via
feedback circuit — — — 9 9
Flow alarm via * Not applicable to CVV series.
pressure switch Option Option Option Option Option
Teflon is a registered trademark of DuPont Co.
Low-noise diffuser
construction† 9 9 9 9 9
All valves include pressure independent controllers, factory-calibrated position controllers, and are
available in flows from 35-6000 CFM (60-10,000 m3/hr).
†Accel II valves are designed to reduce sound over all frequencies, but significantly target the lower bands
(125-500 Hz) to help eliminate the need for silencers.
COVER TAB
DO NOT BLOCK
Access required after installation
20 PSI
E
PATENT NOS. 5,304,093 / 5,251,665 AND PATENTS PENDING
D
E
B
B
C
F
F C A
Triple Quad
(Make-up Air (Constant Volume
Valve shown) Valve shown)
G
E B
D D
A
F C A F C
Valve Dimensions
A* B* C D E** F G
inches mm inches mm inches mm inches mm inches mm inches mm inches mm
8 — — 7.88 200 23.50 597 — — 14.13 359 28.00 711 10.13 257
10 — — 9.67 246 21.75 552 — — 16.13 410 26.20 665 11.20 284
12 — — 11.84 301 26.81 681 — — 18.13 461 32.56 827 12.13 308
System Components
2-10 20.13 511 10.13 257 24.75 629 1.5 38 16.77 426 27.70 704 21.52 547
2-12 24.13 613 12.13 308 29.81 757 1.5 38 18.75 476 34.60 879 24.76 629
3-12 37.06 941 12.13 308 29.81 757 1.5 38 18.75 476 34.60 879 36.77 934
4-12 48.26 1226 12.13 308 29.81 757 1.5 38 18.75 476 34.60 879 48.65 1236
* outer dimension ** maximum of all valve types (some configurations may be smaller)
Operating Ranges
the room pressure alarm set point from a dry contact and
Mute
to provide flow alarming when used with Phoenix Con-
trols Accel® airflow control valves, verifying both pressure
and volumetric flow requirements are being met.
Phoenix Controls
Specifications Corporation
Temperature:
77º F
Phoenix Controls Local Display Unit (LDU) is a networked-based user interface panel
Humidity:
Status:
55% intended to display data and/or edit set point variables for vivariums, biocontainment or
Occupied
Total Supply:
800 CFM
laboratory spaces maintained by the Celeris® Environmental Control System. The LDU may be
Total Exhaust:
1000 CFM
flush or surface mounted on a variety of electrical enclosures. It is intended to be installed in
corridors outside of critical environments to provide users with information related to oper-
ating conditions inside the space. Using a 128 x 128 pixel graphical display, the LDU can
display up to five parameters simultaneously. Each parameter includes a 16-character user
Local Display Unit (LDU). defined description and the present value, including units of measure.
The LDU connects to the Celeris room-level network and may be used to display flow,
temperature, humidity, control or set point variables available on the Celeris network.
Specifications
Power Battery
Voltage CR 2032 Lithium battery; retains clock time
24 Vdc/Vac; ±15%, 50/60 Hz for 1 year with no power applied
Consumption Communication
8 VA (13 VA maximum) LonTalk ® protocol
Protection Transceiver
1.5 amp auto reset fuse TP/FT-10, 78 kbps
Environmental Enclosure
• Material: ABS resin
Operating Temperature • Color: Off-white
32-158 °F (0-70 °C) • Dimensions:
Storage Temperature • Flush mount: 6" x 6" x 1.5"
-4-158 °F (-20-70 °C) (151 x 151 x 38 mm)
Temperature Relative Humidity • Din rail mount: 4.5" x 4.5" x 1.5"
0-90%, non-condensing (113 x 113 x 38 mm)
• Weight: 0.73 lbs (0.33 kg)
General
Display
Processor • Type: Backlit LCD
Neuron® 3158, 8 bits, 10 MHz • Definition:
Memory • 128 x 128 pixels
Flash 64 K (APB applications) • 10 lines (5 variables) x 13 characters
Flash 64 K (storage) • Display area: 2.1" x 2.1 (5.5 cm x 5.5 cm)
Clock
Real-time clock chip, accurate to ±1 minute
System Components
per month
Specifications
Construction Operating Range VAV Controller
• 16 ga. spun aluminum valve • 32-125 °F (0-50 °C) ambient I/O:
body with continuous welded • 10-90% non-condensing RH • 3 universal inputs. Accepts
seam Performance volt, mA, ohms or NTC 2 or 3
• Valve bodies available as • Pressure independent over a thermistor signals.
uncoated aluminum or with 0.6"-3.0" wc (150-750 Pa) • 1 digital input
corrosion-resistant baked drop across valve • 2 analog outputs. Provides
phenolic coatings • Volume control accurate to volt or mA signals.
• Composite Teflon® shaft ±5% of airflow command • 1 digital output (Type C,
bearings signal throughout normal 1 amp @ 24 Vac/Vdc)
• Spring grade stainless steel operating range • Input accuracy
spring and polyester or PPS • No additional straight duct Voltage, current, resistance:
slider assembly runs needed before or after ±1% full scale
• Supply valves insulated with valve • Output accuracy
3/8" (9.5 mm) flexible closed- • Available in flows from 50- • 0 to 10 Vdc: ±1% full scale
cell polyethylene. Flame/ 2600 CFM (85-2888 m3/hr) into 10 kW minimum
smoke rating 25/50. Density • Shut-off leakage: See chart • 4 to 20 mA: ±1% full scale
2.0 lb/ft3 (32.0 kg/m 3). below. into 500 W +0/-50 W
Agency compliance:
Electric Actuation • CE
Response time: <1 minute • UL 916 listed
Shut-off Leakage Rates*
Power consumption: • FCC Part 15, Subpart J,
• 13 VA (single valves) Class A
Static Pressure
(in Pa)
• 17 VA (dual valves) Room-level communications:
249 498 747 996 1245 Power: FTT-10, 78 KB, bus topology,
6 10
9
24 Vac (±15%) @ 50/60 Hz LonTalk™ network
5 8
7 Building-level communications:
(in m3/hr)
Leakage
(in CFM)
4
Leakage
6
3 5
4
TP-1250, 1.2 MB, bus topology,
2 3
2
LonTalk™ network
1
1
0 0
1 2 3 4 5 Teflon is a registered trademark of DuPont Co.
Static Pressure
LONWORKS is a registered trademark of Echelon Corp.
(in inches wc)
* Leakage refers to expected airflow through the valve in the shut-off position.
LCD
Window
www.phoenixcontrols.com
Duct sensor.
Specifications
Temperature Humidity and Combination
System Components
Environmental 32 to 122 °F -40 to 212 °F 32 to 122 °F -22 to 150 °F -22 to 158 °F
Temperature Range (0 to 50 °C) (-40 to 100 °C) (0 to 50 °C) (-30 to 70 °C) (-30 to 70 °C)
Environmental 0 to 95% RH 0 to 100% RH 0 to 95% RH 0 to 100% RH 0 to 100% RH
Humidity Range (non-condensing) (non-condensing) (non-condensing)
Housing Material ABS plastic Steel ABS plastic Weatherproof Weatherproof
Cast Aluminum Cast Aluminum
Accuracy ±0.2 °C (0 to 70 °C) ±0.2 °C (0 to 70 °C) ±2% from 15 to ±2% from 15 to ±2% from 15 to
95% RH @ 25 °C 95% RH @ 25 °C 95% RH @ 25 °C
Dissipation Constant 3 mW/C 3 mW/C
Stability < 0.02 °C/year < 0.02 °C/year
Reference Resistance 10 kW @ 25 °C 10 kW @ 25 °C
Sensing Element Thermistor Thermistor Impedance Type
Humidity Sensor
Response Time 20 seconds for a 20 seconds for a
63% step 63% step
14
Centers for Disease Control/National Institutes of Health (CDC/NIH), Biosafety in Microbiological and Biomedical Laboratories, 4th edition preface, http://www.cdc.gov/od/ohs/biosfty/bmbl4/
bmbl4toc.htm.
15
Ibid.
16
National Sanitation Foundation/American National Standards Institute (NSF/ANSI), Class II (laminar flow) biosafety cabinetry, NSF/ANSI 49-2004a, p. iii.
17
Health Canada, Laboratory Biosafety Guidelines, 3rd Edition, first paragraph on home page, http://www.phac-aspc.gc.ca/ols-bsl/lbg-ldmbl/index.html.
18
United States Department of Agriculture (USDA), Agricultural Research Service (ARS), ARS Facilities Design Standards home page, http://www.afm.ars.usda.gov/ppweb/242-01m.htm.
Monitoring
2003 ASHRAE Applications Handbook, p. 14.17, Biosafety Level 3 section
“Audible alarms and visual monitoring devices are recommended to notify personnel if the laboratory pressure
relationship changes from a negative to a positive condition. The user may wish to have alarms reported to a remote
constantly monitored location.”
USDA ARS Facilities Design Standards, Section 9.4.3 Biosafety Level 3 (BSL-3), fifth sentence of item C.3
“A visual monitoring device should be provided at the space's entry to confirm the inward direction of the airflow.”
CDC/NIH Biosafety in Microbiological and Biomedical Laboratories, p. 34, D.9.
“Laboratory personnel must verify that the direction of the airflow (into the laboratory) is proper. It is recommended
that a visual monitoring device that indicates and confirms directional inward airflow be provided at the laboratory
entry.”
Health Canada Laboratory Biosafety Guidelines, p. 35, Matrix 3, items 2-3
“Visual pressure differential monitoring devices to be provided at entry to containment laboratory.
“Room pressure differential monitoring devices penetrating the containment barrier to be provided with filters of
efficiency equal to that of HEPA filtration.”
Health Canada Laboratory Biosafety Guidelines, p. 35, Matrix 3, item 5
“Alarm (visual or audible) to be provided in the laboratory and outside laboratory area (i.e., to warn others and
Standards & Guidelines
Leakage Factor
USDA ARS Facilities Design Standards, Section 9.4.3 Biosafety Level 3 (BSL-3), item C.6
“The BSL-3 space must be constructed with sealed finishes and penetrations and sealable doors to permit gaseous
biological decontamination. All furnishings and equipment must be able to be decontaminated by some proven means,
or be able to be disposed of. All utility pipe and duct penetrations, electrical conduits, utility access and other passages
through floors, walls and ceilings must be sealed to assure isolation of the space environment.”
2003 ASHRAE Applications Handbook, p. 14.17, Biosafety Level 3 section
“Gastight dampers are required in the supply and exhaust ductwork to allow decontamination of the laboratory. The
ductwork between these dampers and the laboratory must also be gastight. All penetrations of the Biosafety Level 3
laboratory envelope must be sealed for containment and to facilitate gaseous decontamination of the work area.”
CDC/NIH Biosafety in Microbiological and Biomedical Laboratories, p. 33, D.3.
“Penetrations in floors, walls, and ceiling surfaces are sealed. Opening such as around ducts and the spaces between
doors and frames are capable of being sealed to facilitate decontamination.”
Health Canada Laboratory Biosafety Guidelines, p. 38, Matrix 3, items 20-21
“Exhaust air ductwork that is outside the containment perimeter (e.g., between containment perimeter and HEPA
filter or bubble tight backdraft damper) to be sealed airtight in accordance with SMACNA Seal Class A.
“(CL3 laboratories manipulating organisms, such as HIV, that are not infectious via inhalation are not required to fulfil
this criterion.)
“Airflow control devices and duct sensors to be located downstream of the exhaust HEPA filter and upstream of the
supply bubble tight backdraft damper or HEPA filter, or if located upstream, duct penetrations to be sealed in accor-
dance with SMACNA Seal Class A.
“(CL3 laboratories manipulating organisms, such as HIV, that are not infectious via inhalation are not required to fulfil
this criterion.)”
Verification
CDC/NIH Biosafety in Microbiological and Biomedical Laboratories, p. 36, D.15.
“The Biosafety Level 3 facility design and operational procedures must be documented. The facility must be tested for
verification that the design and operational parameters have been met prior to operation. Facilities should be re-
verified, at least annually, against these procedures as modified by operational experience.”
Certification
Health Canada Laboratory Biosafety Guidelines, p. 46, section 5.1, Introduction
“’Certification’ is defined as the successful completion of commissioning and verification that the facility and opera-
tional protocols meet the requirements outlined in the current edition of the Laboratory Biosafety Guidelines. ‘Recer-
tification’ is verification that that facility continues to comply with the current edition of the Laboratory Biosafety
Guidelines and has undergone recommissioning process as outlined (in the guidelines).”
Health Canada Laboratory Biosafety Guidelines, p. 48, Matrix 6, item 1
“Integrity of containment surfaces to be tested visually and with a smoke pencil or other visual aid. Inspect floors, walls,
and ceiling for cracks, chips and wear. Verify integrity of wall/floor and wall/ceiling joints.
“Acceptance criteria: to confirm the integrity of all penetrations (i.e., equipment, services, etc.) and seals (i.e., around
doors, windows, autoclaves, etc.) on the containment barrier.”
Health Canada Laboratory Biosafety Guidelines, p. 51, Matrix 7, items 1-4
“Classes I and II BSCs to be tested in situ in accordance with NSF/ANSI 49-2002 or CSA Z316.3-95.
“Class III BSCs to be tested in situ in accordance with the Laboratory Safety Monograph, NIH 1979 and BS EN 12469-2000.
“Interlocks (i.e., Class II Type B2 BSC internal cabinet supply fan and exhaust fan) to be tested in accordance with NSF/
ANSI 49:2002 to ensure that internal supply fan shuts off whenever exhaust fan fails.
“Alarms to be tested for detection of BSC and/or exhaust fan failure by simulation of alarm conditions.” Standards & Guidelines
* Glove panels may be added and will increase face velocity to 150 lfpm; gloves may be added with an inlet air pressure release that will allow work with chemicals/
radionuclides.
NSF Class II (laminar flow) biosafety cabinetry, Class II (laminar flow) biohazard chemistry, p. 27
“6.10 Inflow velocity
6.10.1 The minimum directly measured and calculated inflow velocities of Type A1 cabinets shall be 75 ft/min
(0.38 m/s).
6.10.2 The minimum inflow quantity per 1 ft (0.3 m) of work area width of Type A1 cabinets shall be 45 ft3/min
(0.02 m3/s).
6.10.3 The minimum directly measured and calculated inflow velocities of Type A2 cabinets shall be 100 ft/min
(0.5 m/s).
6.10.4 The minimum inflow quantity per 1 ft (0.3 m) of work area width of Type A2 cabinets shall be 65 ft3/min
(0.03 m3/s).
6.10.5 The minimum directly measured and calculated inflow velocities of Type B1 and B2 cabinets shall be
100 ft/min (0.5 m/s).
6.10.6 The minimum inflow quantity per 1 ft (0.3 m) of work area width of Type B1 and B2 cabinets shall be
65 ft3/min (0.03 m3/s).”
Also according to section 6.10, directly measured inflow velocities must be within ±5 ft/min of the nominal set point
velocities to meet acceptance criteria for either production or field use.
Exhaust
NSF Class II (laminar flow) biosafety cabinetry, p. E1, Annex E, E.1.2.1
“Type A1 and A2 cabinets are designed to return air to the laboratory and do not generally require external venting...
“When it is desirous to exhaust air to the atmosphere, it should be via a 100% exhaust system (i.e., a system that does
not recirculate its exhaust air into other parts of the building). The recommended exhaust system connection for
types A1 and A2 cabinets is an exhaust canopy connection…No type A cabinet should ever be hard connected to an
exhaust system.”
NSF Class II (laminar flow) biosafety cabinetry, p. E2, Annex E, E.1.2.2
“Types B1 and B2 cabinets are to be vented outside the building without recirculation. The venting system should
include a leak-tight duct, a damper in the duct near the cabinet to permit flow adjustment closure and decontamina-
tion, and an external exhaust fan as the final system component.”
2003 ASHRAE Applications Handbook, p. 14.17, Biosafety Level 3 section
“All procedures involving the manipulation of infectious materials are conducted inside biological safety cabinets. The
engineer must ensure that the connection of the cabinets to the exhaust system does not adversely affect the
performance of the biological safety cabinets or the exhaust system.”
2003 ASHRAE Applications Handbook, p. 14.7
“In Class II Type A2 cabinets, exhaust air delivered to the outlet of the cabinet by internal blowers must be handled by
Standards & Guidelines
the laboratory exhaust system. This arrangement requires a delicate balance between the cabinet and laboratory
exhaust system, and it may incorporate a thimble connection between the cabinet and the laboratory exhaust ductwork.
“Class II Type B1 and Type B2 cabinets rely on the building exhaust system to pull the air from the cabinet's work space
and through the exhaust HEPA filters. The pressure resistance that must be overcome by the building exhaust system
can be obtained from the cabinet manufacturer. Because containment in this type of cabinet depends on the building's
exhaust system, the exhaust fan(s) should have redundant backups.”
Bibliography
American Industrial Hygiene Association (AIHA). American National Standard for Laboratory Ventilation (ANSI/AIHA
Z9.5-2003). Fairfax, VA: AIHA, 2003.
American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE). ASHRAE Handbook: 2003
HVAC Applications (SI Edition). Atlanta, GA: ASHRAE, 2003.
Animal and Plant Health Directorate (APHD) of Agriculture and Agri-Food Canada (AAFC). Containment Standards
for Veterinary Facilities, October 15, 2000. Available online at http://www.inspection.gc.ca/english/sci/lab/convet/convet1-
2e.shtml.
Centers for Disease Control and Prevention (CDC) and National Institutes of Health (NIH). Biosafety in Microbiological
and Biomedical Laboratories, 4th edition (BMBL). Washington, DC: U.S. Government Printing Office, 1999. Also available
online at http://www.cdc.gov/od/ohs/biosfty/bmbl4/bmbl4toc.htm.
Centers for Disease Control and Prevention (CDC), The Office of Health and Safety Information System (Ohasis).
Primary Containment for Biohazards, Section III. Available online at http://www.cdc.gov/od/ohs/biosfty/bsc/
BSC2000sec3.htm.
Crane, Jonathan T. “Hot Zone Laboratories.” ASHRAE Journal, June 1999, pp. 28-31.
Furr, A. Keith. CRC Handbook of Laboratory Safety, 5th Edition. Boca Raton, FL: CRC Press LLC, 2000.
Health Canada. Laboratory Biosafety Guidelines, 3rd edition. Ottawa: Minister of Health Population and Public Health
Branch, Centre for Emergency Preparedness and Response, 2004. Also available online at http://www.phac-aspc.gc.ca/
ols-bsl/lbg-ldmbl/index.html.
National Institutes of Health (NIH). NIH GGuidelines for Research Involving Recombinant DNA Molecules. Available
online at http://www4.od.nih.gov/oba/rac/guidelines_02/NIH_Guidelines_Apr_02.htm.
National Sanitation Foundation/American National Standards Institute (ANSI). Class II (laminar flow) biosafety cabinetry,
NSF/ANSI 49-2004a. Ann Arbor, MI: NSF International, 2004.
United States Department of Agriculture, Agricultural Research Service (ARS). ARS Facilities Design Standards. Wash-
ington, DC: USDA, 2002. Available online at http://www.afm.ars.usda.gov/ppweb/242-01m.htm.
World Health Organization (WHO). Laboratory Biosafety Manual, Third Edition. Geneva: WHO, 2004.