Distance Protection
Ed Khan
August,2013
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Disclaimer
This material being presented is based on good engineering and industry practices. It also contains views and
engineering approach of the presenter based on his personal experiences as a practicing engineer.
Neither the presenter nor Quanta Technology is responsible for any damages, direct or consequential, that may
arise as a result of applying the knowledge gained from this course. Every application in the field needs specific
approach based on all the facts surrounding the application. The material presented is general and must be
applied after taking all facts and deviations into consideration.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Distance protection :
Backbone of transmission line protection
Sometimes used on distribution network
Can protect overhead lines and cables
Is much faster and more selective than overcurrent relaying
For zone 1 faults tripping time is approximately one to two
cycles.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Distance protection :
With communication channels the distance protection can
provide excellent coverage (100 % of the line)
Distance protection communication is a Go-No Go information.
Hence narrow bandwidth is sufficient
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Types of characteristics :
ZL
ZR
ZL
Quad
ZR
Mho
Lens
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Electromechanical distance relays use Induction Cup
design. The operating torque is developed by
interaction of fluxes produced by system voltage and
current.
In static and microprocessor relays we do not have
fluxes----Use angles to determine the logic for tripping
and non-tripping. This logic is used in static relays and
the principal is extended to microprocessor relays
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Unit Protection
Differential protection
• Transformer differential protection
Bus differential protection
• Generator differential protection
• Line differential protection
Pilot protection
• Transfer trip schemes
• Under/over reaching pilot protection with distance
protection
Non-Unit protection
Over Current protection
• Time over current or instantaneous protection
3 Zones of distance protection
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
TFR
Protection
Unit protection provides the protection if the
fault is inside the Zone of protection
It does not provide the protection if the fault
is outside the Zone of protection
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Protection works on impedance seen by the
protection
Impedance is directly proportional to
distance so it’s a distance protection
Requires inputs for voltage and current
Using CTs and PTs
Current is an operating force and voltage is
a restraining force
Normal load condition restraining force is higher
then the operating force
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Current Voltage
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
A B C D
Normal condition
Normal voltage & load current
69 Volts and 1 A load current
Fault condition
Depressed voltage & high
current
20 Volts & 10 A fault current
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
A B C D
Quick isolation of the faulted section
Reduces damage caused by the fault
Less stress on the electrical apparatus
Maintains the flow of electricity to healthy section
Quick and fast detection of the fault
condition
Fast operation of the distance protection
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Z3
Zopt
Zopt
Z2
Z1
Z4
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
X ZL
ZR
Reach
Load Blinder
R
Dir
KR
Four comparators used for detection of fault conditions
If all four comparators produces output: protection trips
Quad characteristic :good fault resistance coverage
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Directionality
ZL
X
ZR
Reach
Load Blinder
Dir
KR R
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Forward Fault
IX
IZ = Signal B True
If A lags B
By 00 – 1800
VF
IR
Dir line
VF <-900 = Signal A
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Reverse Fault
IX
IZ = Signal B True
If A lags B
By 00 – 1800
VF <-900 = Signal A
IR
VF
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
External Fault
IX VF - IZ = Signal A
If A lags B
By 00 – 1800
IZ
VF
I*Kr = Signal B IR
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Int. Fault
IX
VF - IZ = Signal A If A lags B
By 00 – 1800
IZ
VF
I*Kr = Signal B
IR
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
No Fault
IX
VF - IZ = Signal A
If A lags B
By 00 – 1800
IZ
VF
I*Kr = Signal B IR
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection-Quad Char: Facts
Quad char. better : short line and/or strong source
Good for Ph-G fault : Fault Res. Coverage
Reactance & Resistance Reach set independently
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Quad Char. : Reactance Line
Reactance line : not a straight
line parallel to R axis.
Top line has a tilt of approx 30
The tilt for security against
external fault
Without tilt : protection can
operate for an external fault
due to load on the line
How?
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Effect of Load : Quad Ch.
X Y
G Zs ZL Zs G
Vx <00 VY <-300
Ix Iy
21
Ix+Iy <-Ө
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Impedance Seen at Protection X
X Y
G Zs ZL Zs G
Vx <00 VY <-300
Ix Iy
21
Ix
Ix+Iy <-Ө
(Ix+Iy)*R
Ix + Iy
Iy
(Ix)*ZL
Tilt of the reactance line
Prevents tripping for the
External faults
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Effect of Load : Quad Ch.
X Y
G Zs ZL Zs G
Vx <00 VY <+300
Ix Iy
21
Ix+Iy <+Ө
Iy
Ix + Iy
Ix
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Impedance Seen at Protection X
G Zs ZL Zs G
Vx <00 VY <-300
Ix Iy
21
Ix+Iy <-Ө
(Ix+Iy)*R
(Ix)*ZL Tilt of the reactance line
Prevents operation for the
Internal faults
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Quad Characteristics : Ext. Fault
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Quad Characteristics : Int. Fault
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Quad Characteristics : Int. Fault
By polarizing the top line with –Ve or Zero
sequence current, it will adapt to load Condition
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
MHO or Quad : Pros and Cons
Simple and directional Good fault resistance
Less sensitive to coverage as char. can
power swings be set along R- Axis
Reach does not extend Good for short line and
as far along R-Axis strong source
Limited fault resistance Sensitive to power swing
coverage for short Characteristic extends on
lines R-Axis
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Set a replica impedance
IX IZ R
Replica of line impedance
V - IZ
Magnitude and angle : ZR pol R
Called reach of the Relay
Convert current I in to vector IZR Vpol
IR
Derive voltage of the system : V
Reference voltage V , Polarizing Voltage : Vpol
Calculate voltage vector Vpol - IZR
Measure the angle between Vpol and Vpol – IZR
Output if the angle is 90 deg or greater
This produces “MHO” Characteristic
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
IZ
I Z
V
+ Angle
Comparator
Output
>= 900
IX IZ
V-IZ
Angle = 900
V
IR
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
IZ
I Z
V
+ Angle
Comparator
Output
>= 900
IX IZ
V-IZ
V
IR
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
IZ
I Z
V
+ Angle
Comparator
Output
>= 900
IX IZ
V-IZ
Internal fault
Angle >=900
V
IR
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
IZ
I Z
V
+ Angle
Comparator
Output
>= 900
IX IZ
V-IZ
External fault
Angle < 900
V
IR
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection : Ph-G Fault
For A-G fault
IZR is IA*ZR
Vpol is VA
Vpol – IZR is VA – IAZR
When polarizing voltage = Fault voltage
Self polarized Relay
For B-G fault
• Polarized voltage = Fault voltage = VB
Earlier designs were self polarized distance
relays
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Self Polarized Protection
Limitations
What happens if the fault is at the terminal of the
breaker?
• Fault voltage is 0
• Polarized voltage is 0
• No reference voltage Vpol to compare with
V-IZ
• Self polarized distance protection no good for
0 voltage phase to ground fault
Solution
Use memory voltage instead of faulted phase
voltage
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Memory Polarized Protection
IZ
I Z
V
+ Output
Angle
Comparator
>= 900
Memory
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Memory Polarization: Summary
Provides reference voltage (Vpol) under all phase
and ground faults
Expand the self polarized characteristic to cover
more fault resistance
No overreaching at reach point
Circle with a diameter = Source impedance + Reach
impedance
• Higher the source impedance (weak source) larger the
diameter means more fault resistance coverage
Numerical protections uses memory, self, healthy
phase voltages for polarizations and or different
combinations of the same
Partially or fully cross polarized protections are very
common now a days
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Cross Polarization
It is very common to use healthy phase
voltage for phase to ground fault
Provides polarizing voltage for a zero voltage fault
For A-G fault: Polarizing voltage is -(VB+VC)
• Called Cross polarizing
• Same effect as Memory Polarization
VC
-(VB+VC)
VA
VB
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Memory Polarization
How protection works for a 3 phase zero voltage faults?
Typically the protection memorizes 16-20 cycles of pre fault
voltages which is used when there is Zero Voltage Fault.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Switch on to Fault
A B
G Zs
21
How the protection works for a permanent 3 phase zero
voltage faults during closing of the breaker?
If the grounding chains were left on the breaker & breaker is
closed, protection has no voltage in the memory as well as
the fault voltage is zero. Protection sees only fault current.
Switch On To Fault - SOTF feature is employed which trips
the breaker if protection sees the current but no voltage
following breaker close.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
3 Zones of protection
Zone 1 operates with no intentional time
delay
Zone 2 provides back up protection to Zone
1 and operates with some time delay
Zone 3 typically has offset characteristic
and has a time delay longer then Zone 2
Zone 2 and Zone 3 are used in pilot
scheme if employed
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
General Application Rules
A B C D
Zone 3
Time
Zone 2
Zone 1
Zone 1 protects 80-85% of line length AB
Zone 2 protects line AB + 50% of line BC
Zone 3 Protects AB + Line BC + 20-30% of line CD + 20-30%
of line behind terminal A
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Reach Setting Criteria : Zone 1
A B C D
Zone 1
Zone 1 should never over reach for the faults on or
beyond remote terminal
Considering 5% accuracy of CTs and PTs maximum
reach of Zone 1 can be 90% of line length AB
Considering accuracy of Zone 1 protection 5% and safety
margin of 5% Zone 1 reach can be 80% of the line length.
In some instances based on the previous practices Zone
1 is set to 90% of line length
It is safe to set Zone 1 reach 80% of line length in general
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Reach Setting Criteria : Zone 2
A B C D
Zone 2
Zone 2 should always over reach for the faults on or
beyond remote terminal
Zone 2 should always reach beyond the remote terminal and
cover at least 50% of next line section
Zone 2 time delay should be larger then the operating time
of Protection + CB (at terminal C of line CD) + safety margin
• Breaker fail timer co ordination is required
Zone 2 is used in the pilot aided trip scheme to provide
instantaneous protection for faults anywhere on line BC
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Zone 2 Time Delay : Criteria
A B C D
1 2 3 4 5 6
Zone 2
Determine Zone 2 time if Breaker fail protection is employed
Breaker fail protection clears the fault by tripping back up breaker if
the primary breaker fails to clear the fault after the protection trip
For fault on line CD, protection at breaker 5 will see the fault and
issues a trip command to breaker 5 and at the same time initiates
breaker fail protection
If breaker 5 trip it resets the breaker fail protection
The fault is seen by the protection at breaker 3, in Zone 2.
If breaker 5 fails then Breaker fail protection trip all breakers at bus C
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Reach Criteria Zone 3
Zone 3 is a back up protection and last resort for the
isolation of the fault if everything fails
Time Delayed protection. Time delay is longer then
Zone 2 delay
When a very long line is following the short line Zone
3 reach may be very long
Can interfere with load on the line
Lens characteristic is a potential solution
It is used in the pilot aided protection when blocking
scheme is employed to detect the fault direction
Typically set in the offset mode to cover the reverse
fault
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Zone 3 : Load Encroachment
Load
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Zone 3 : Load Encroachment
Load
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Zone 3 : Load Encroachment
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Zone 1 Reach : 3 Terminal Line
X Ix Ix + Iy Z
d
Iy
Fault voltage at X = VF = Ix*ZF + Iy* (1-d)ZF
Fault current at X = Ix
Apparent Impedance at X =VF/IF= VF/Ix =ZF + Iy/Ix (1-d)ZF
Additional impedance due to in feed = Iy/Ix (1-d)ZF
Fault will be seen farther: Protection will not trip
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Zone 1 Reach : 3 Terminal Line
X Ix Z
F
Let’s Set the reach considering maximum in feed so protection trips
Now say breaker at Y is out for maintenance
Now the fault in the next line section will be seen as internal
Protection will trip for the external fault
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection-Infeed Effect
Step Distance Protection—Infeed Effect
Ignore Infeed while setting Zone 1 setting
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection-Infeed Effect
Step Distance Protection—Infeed Effect
Zone 1 is incorrectly set taking Infeed into account
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection-Infeed Effect
Step Distance Protection—Infeed Effect
Zones 2 and 3 are set with Infeed taken into account
These zones have delays and are intended to
overreach by varying amounts.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Arc Resistance Coverage
Ground Fault on lines result to mostly due to
flashover of the insulators.
The current path includes arc, tower impedance
and impedance between the tower foundation and
ground (tower footing resistance).
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Arc Resistance Coverage
Arc Resistance is more difficult to handle in case
of ground faults.
Ground wires when used provide a parallel path
to ground return
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Arc Resistance Coverage
Phase faults on the lines are often the result of high
winds swinging the conductors close enough to arc over.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Arc Resistance Coverage I Ir
X
Zf
Rf
E
E=Zf I+Rf(I+Ir)
Apparent Impedance=
Za=E/I=[Zf I+Rf(I+Ir)]/I
Za=Zf+Rf(1+Ir/I)
A R
Relay may not operate
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Arc Resistance Coverage
X
Arc resistance inversely
proportional to current
and directly proportional to line
spacing
Rarc = (8750 * L)/ I1.4
A R L is in feet
I is in amps
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Short Lines—Fault current below 2000 A---Effect of
arc resistance is most significant
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Protection
Long Lines-Steel Towers with ground wires the effect
is normally minimal
Long lines on wooden poles with no ground wires
the effect can be significant and the self polarized
mho is not suitable.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Arc Resistance
For Ground Relaying where arcs are involved
Quadrilateral characteristics is favored.
X
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Arc Resistance
Ground fault overcurrent relaying also provides very
good protection involving arcs.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
There are ten 10 distinct short circuit faults that can occur on a
transmission line:
1 Three phase fault
3 phase to phase faults (AB, BC,CA)
3 phase to earth faults (A-E. B-E, C-E)
3 double phase to earth (A-B-E, B-C-E, C-A-E)
Hence it means that for each fault there has to be a distance relay
Which is fed by the right pair of PTs and CTs.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
We do not have not do this:
Basic principal of distance relays is that whatever the fault type
the relay will only measure positive sequence so we do not have
to have different inputs.
Hence, we only need to specify zone settings in terms of
positive sequence impedance to the fault.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
Let us work out an example to see how relay measure same impedance
to the fault point for three cases.
X
0+j5 4+j40
(0+j10) (10+j90)
System voltage is 13.8 kV (L-L) =7967.4 Volts
Positive and negative impedances are shown without parenthesis
Zero sequence impedance is shown in parenthesis
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
A
If there is a three phase fault at X
In this case only positive sequence exists.
We will look at phase a current and that is Ia
Ia=I 1 (positive sequence current)=7967.4/Positive Seq. Impedance
=7967.4/4+j45 =176.36<89.920
Ea is the voltage at A is equal to E1 and is:
7967.4- (j5*176.36<89.92 0 =7089.49<-0.630
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
Z measured is Ea/Ia=4+j40 ohms
For 3 Phase fault at X
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
A
If there is a b-c phase fault at X
In this case only I1 = -I2 =7967.4/2*(4+j45)=88.18< -84.920
Ib is also = -Ic =I 1 (a 2 –a)=152.73 <-174.92 0
Ib-Ic=305.46 < -174.92 0
Positive and Negative sequence voltages at A are
E 1 =7967.4 –j5*88.18 <-84.92 0 =7528.33 <-0.3 0
E 2 =j5*88.18 <-84.92 0 =440.90 <5.08 0
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
A
We get Eb and Ec at relay location
Eb =a2 E1 + aE2 = 7528.33 <-120.30 +440.90 <125.080 = -4051.3-j6139.3
Ec =aE1 +a2 E2 = 7528.33 <119.70 +440.90 <-114.900 = -3916.09 +j6139.3
Eb –Ec=12279.37 < -90.630
Now
(Eb –Ec)/ Ib –Ic)= (12279.37 < -90.630 )/ (305.46 < -174.92 0 )
=4+j30 Z measured is =4+j40 ohms
For Phase-to-Phase fault at X
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
Phase-to-earth fault
For phase to earth fault (A-E) the three symmetrical components for
The fault current are equal:
I1=I2 =I0 =7967.4/[(0+j10) + 2*(0+j5) +2*(4+j40)]
=41.75<-84.59 0
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
Phase-to-earth fault
A
Symmetrical components of voltages at A are:
E1=7967.4-j5*41.75<-84.59 0 =7759.58 –j19.68
E2=0-j5*41.75<-84.59 0 = - 207.82-j19.68
E0=0-j10*41.75<-84.59 0 = -415.64-j39.36
Phase a voltage Ea=E1+E2+E0=7136.55<-0.630
Phase a current Ia=I1+I2+I0=125.25<-84.59 0
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
Phase-to-earth fault
A
If we divide Ea/Ia we do not get 4+j40:
The ground resistance for the return path has to be compensated for
We need to adjust the ground fault current by a factor k0
K0=(Z0-Z1)/Z1
In this case we gat K0=(10+j90-4-j40)/(4+j40)=1.253<-1.130
Compensated current is Ia’=Ia+1.253<-1.130 =177.54 <-84.920
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
Phase-to-earth fault
A
Now if we divide Ea by Ia’ we get
(7136.55 <-0.630 )/ 177.54 <-84.920
=4+j40
Z measured is =4+j40 ohms
For Phase-to-Earth fault at X
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Distance Relays
Phase-to-earth fault
A
For K0 please note that different manufacturers have different
Formulas. He one we used is
K0=(Z0-Z1)/Z1
Some use K0=(Z0-Z1)/3Z1
Always refer to manufacturer instruction manual while setting
ground distance element reach.
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary
Questions
Thank You
Copyright © 2012, Quanta Technology, LLC Confidential and Proprietary