0% found this document useful (0 votes)
781 views1 page

Table Arus Maksima 1

The document summarizes the electrical load calculations for a building. It lists various appliances and their wattages, and calculates the maximum and estimated currents. The maximum current is 123.14A and the estimated current is 39.58A. Based on the estimated current, the recommended service cable size is 2 x 35mm2 and the main switch rating is 40A. The MCB ratings are also specified based on the main switch rating.

Uploaded by

Haezzah Nasib
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
781 views1 page

Table Arus Maksima 1

The document summarizes the electrical load calculations for a building. It lists various appliances and their wattages, and calculates the maximum and estimated currents. The maximum current is 123.14A and the estimated current is 39.58A. Based on the estimated current, the recommended service cable size is 2 x 35mm2 and the main switch rating is 40A. The MCB ratings are also specified based on the main switch rating.

Uploaded by

Haezzah Nasib
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

BIL BEBAN ARUS MAKSIMA ARUS ANGGARAN

1. 16 x 38W lampu kalimantang 16 x 38W x 1.8 4.56 A x 66%


240 V =3A
= 4.56 A
2. 11 x 60W lampu pijar 11 x 60W 2.75 A x 66%
240 V = 1.82 A
= 2.75 A
3. 4 x 86 kipas siling 4 x 86W 1.69 A x 66%
240 V x 0.85 = 1.12 A
= 1.69 A
4. 8 x 13A soket alir keluar 4 litar x 20 A 8 x 300W
= 80 A 240 V
= 10 A
5. 1 x 2.5 k.k pendingin udara 1 x 2.5 x 746 W 9.14 A x 100%
240V x 0.85 = 9.14 A
= 9.14 A
6. 1 x 6 kW dapur elektrik 1 x 6000 W 10 A pertama + 30% selebihnya
240 V = 10 A + [ 30% (25 – 10)]
= 25 A = 10 A + 4.5 A
= 14.5 A
JUMLAH ARUS 4.56 + 2.75 + 1.69 + 80 + 39.58 A
9.14 + 25
= 123.14 A

i. Arus maksima = 123.14 A


ii. Arus anggaran = 39.58 A
iii. Saiz kabel perkhidmatan = 2 x 35mm²
iv. Kadaran/saiz suis utama= 40A SKN
v. Kadaran PAB = 40A / 100mA litar lampu
40A / 30mA litar kuasa

(b) Peratus pengurangan arus :