SIMATIC S7 - 200 Micro PLC: General
SIMATIC S7 - 200 Micro PLC: General
Isolation Isolation
Optical isolation (galvanic) 500 VAC for 1 min - Optical isolation (galvanic) 500 VAC for 1 min -
Isolation resistance - 100 M Ω, min when new Isolation resistance - 100 M Ω, min.
when new
Isolation coil to contact - 1500 VAC for 1 min Isolation coil to contact - 1500 VAC for 1 min
Isolation between open contacts - 750 VAC for 1 minute Isolation between open contacts - 750 VAC for 1 min
Inductive Load Clamping Inductive Load Clamping
Repetitive Energy dissipation < 1 W, all channels - Repetitive Energy dissipation < 1 W, all channels -
0.5 LI2 x switch. rate 0.5 LI2 x switch. rate
Clamp voltage limits L+ minus 48 V - Clamp voltage limits L+ minus 48 V -
Output Delay Output Delay
Off to On 50 µs, max. - Off to On 50 µs, max. -
On to Off 200 µs, max. - On to Off 200 µs, max. -
Relay Life Relay Life
Switching delayLifetime - 10 ms,maximum Switching delayLifetime - 10 ms, maximum
mechanical (no load) - 10,000,000 open/close mechanical (no load) - 30,000,000 open/
close
Lifetime contacts at rated load - 100,.000 open/close Lifetime contacts at rated Load - 30,.000 open/close
Description EM 231 AI4 x 12 Bit EM 232 AQ2 x 12 Bit EM 235 AI4/AQ1 x 12 Bit
General specifications
Power Consumption
From +5 VDC (I/O bus) 20 mA 20 mA 30 mA
From L+ 60 mA 70 mA (both outputs at 20 mA) 60 mA (with output at 20 mA)
L+ voltage range, Class 2 or DC 20.4 to 28.8 20.4 to 28. 20.4 to 28.8
sensor supply
LED indicator 24 VDC Power Supply Good 24 VDC Power Supply Good, 24 VDC Power Supply Good,
ON = no fault, ON = no fault, ON = no fault,
OFF = no 24 VDC power OFF = no 24 VDC power OFF = no 24 VDC power