Substation Inspection List
Substation Inspection List
AREA Crusher
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 191 IDEAL SETTING COMMENTS
1
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 191 IDEAL SETTING COMMENTS
2
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 191 IDEAL SETTING COMMENTS
3
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 191 IDEAL SETTING COMMENTS
4
AREA 194 Substation - Mix Storage Area
N° OS DATE OF EXECUTION
5
IMPLE
MENTA
TION
PROCE
DURE
CHECK INSPECT
POINT IDEAL SETTING ED COMMENTS
S
ROUTE ROUTE Nº 194
6
IMPLE
MENTA
TION
PROCE
DURE
CHECK INSPECT
POINT IDEAL SETTING ED COMMENTS
S
ROUTE ROUTE Nº 194
19
101CS100A01 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped c-breakers √
20
101CS100A02 I/O Cabinet
7
IMPLE
MENTA
TION
PROCE
DURE
CHECK INSPECT
POINT IDEAL SETTING ED COMMENTS
S
ROUTE ROUTE Nº 194
22
101UP210A04 UPS - Power Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped c-breakers √
23 GENERAL COMMENTS
8
AREA 291 Substation - Gypsum Crusher
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 291 IDEAL SETTING COMMENTS
9
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 291 IDEAL SETTING COMMENTS
10
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 291 IDEAL SETTING COMMENTS
201LV100 +
13 NA08 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
14 201LV100 +
NA09 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
15 201LV100 +
NA10 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
LDB201LG100A
16 1 Low Voltage Distribution Board
201LV200 Metering Unit - 1 (Reading) ……….……………kwh √ 119653
17
201UP100 110V DC Battery & Charger
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
18
101CS200A01 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
19
101CS200A02 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
24
212AF060U01 Apron Feeder Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
11
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 291 IDEAL SETTING COMMENTS
12
AREA 391 Substation - Raw Mill
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 391 IDEAL SETTING COMMENTS
13
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 391 IDEAL SETTING COMMENTS
14
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 391 IDEAL SETTING COMMENTS
301LV100 +
10 NA05 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
301LV100 +
11 NA06 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
Display Unit Working √
301LV100 +
12 NA07 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
Display Unit - 1 Working
301LV100 +
13 NA08 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
14 301LV100 +
NA09 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
15 301LV100 +
NA10 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
301LV100 +
16 NA011 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
301LV100 +
17 NA12 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
301LV100 +
18 NA13 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
301LV100 +
19 NA14 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped c-breakers √
20
301UP100A01 110V DC Battery & Charger
Door locks / locking mechanism In good working order √
15
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 391 IDEAL SETTING COMMENTS
24
311AF160U02 Apron Feeder Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
25
311SH162U01 Shredder Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
26
321MD152U01 Apron Feeder Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
27 LDB301LG100A
01 Lighting Distribution Board
301LV100 - Meter ……….……………kwh √ 443722
28
301UP110A01 UPS
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
29
301UP110A04 UPS - Power Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
30 GENERAL COMMENTS
16
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 391 IDEAL SETTING COMMENTS
17
AREA 491 Substation - Kiln
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 491 IDEAL SETTING COMMENTS
18
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 491 IDEAL SETTING COMMENTS
19
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 491 IDEAL SETTING COMMENTS
10 401LV100 +
NA07 Low Voltage Distribution Board
one capacitor circuit
Door locks / locking mechanism In good working order √ is damage
20
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 491 IDEAL SETTING COMMENTS
21 401LV100 +
NA18 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
22 401LV100 +
NA19 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
23 401LV100 +
NA20 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
24 401LV100 +
NA21 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
25 401LV100 +
NA22 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
26 401LV100 +
NA23 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
27 401LV100 +
NA24 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
28 401LV100 +
NA25 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
29
331EP300A01 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √ door lock is damage
31
331EP302A01 Low Voltage Distribution Board
21
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 491 IDEAL SETTING COMMENTS
22
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 491 IDEAL SETTING COMMENTS
48
401UP110A01 UPS
Door locks / locking mechanism In good working order √ There is a warning
23
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 491 IDEAL SETTING COMMENTS
GENERAL COMMENTS
52
24
AREA 492 Substation - Cooler
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 492 IDEAL SETTING COMMENTS
25
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 492 IDEAL SETTING COMMENTS
26
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 492 IDEAL SETTING COMMENTS
27
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 492 IDEAL SETTING COMMENTS
25
441FN300U01 Cooler Fan Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
26
441FN305U01 Cooler Fan Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
27
441FN310U01 Cooler Fan Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
28
441FN315U01 Cooler Fan Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
29
441FN320U01 Cooler Fan Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
30
441FN325U01 Cooler Fan Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
28
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 492 IDEAL SETTING COMMENTS
31
441FN330U01 Cooler Fan Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
32
441FN590U01 Cooler Fan Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
33
401UP200 110V DC Battery & Charger
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
Display Unit Working √
34
401CS200A01 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
35
401CS200A02 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
36
401CS200A03 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
37
401UP210A01 UPS
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √ The UPS is bypass
29
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 492 IDEAL SETTING COMMENTS
30
AREA 497 Substation - Clinker Transport
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 497 IDEAL SETTING COMMENTS
Main entrance Doors (locks) Working & not damaged √ The door is damage
31
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 497 IDEAL SETTING COMMENTS
11
401UP710A04 UPS - Power Distribution Board
Door locks / locking mechanism In good working order √
32
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 497 IDEAL SETTING COMMENTS
33
591/592 Substation - Cement Mills
AREA 1&2
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 591 - 592 IDEAL SETTING COMMENTS
34
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 591 - 592 IDEAL SETTING COMMENTS
35
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 591 - 592 IDEAL SETTING COMMENTS
36
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 591 - 592 IDEAL SETTING COMMENTS
37
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 591 - 592 IDEAL SETTING COMMENTS
33
532MD302U01 Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
34
531FN350U01 Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
35
532FN350U01 Frequency Drive Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
36
501UP100A01 110V DC Battery & Charger
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
37
501CS100A01 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
38
501CS100A02 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
39
501CS100A03 I/O Cabinet
Door locks / locking mechanism In good working order √ door lock is damage
41
502CS100A02 PLC & I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
42 LDB501LG100A
01 Lighting Distribution Board
Meter 501LV100 - Reading ……….……………kwh √ 403623
43
501UP110A01 UPS
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
38
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 591 - 592 IDEAL SETTING COMMENTS
44
501UP110A04 UPS - Power Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
45
502UP110A01 UPS
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
46
502UP110A04 UPS - Power Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
57
502UP100A01 110V DC Battery & Charger
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √ Battery test is fault
58 GENERAL COMMENTS
39
AREA 691 Substation - Packing Plant
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 691 IDEAL SETTING COMMENTS
40
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 691 IDEAL SETTING COMMENTS
Door locks / locking mechanism In good working order √ some earthing wire
disconnect & some
cables disconnect
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √ w/o isolation
Door locks / locking mechanism In good working order √ some earthing wire
disconnect & some
cables disconnect
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √ w/o isolation
41
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 691 IDEAL SETTING COMMENTS
42
791 Substation - Compressor Room
AREA 1
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 791 IDEAL SETTING COMMENTS
43
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 791 IDEAL SETTING COMMENTS
3
701LV100-1 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
4
701LV100-2 Low Voltage Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits (ON/OFF) Tripped C-Breakers √
5
401CS110A01 I/O Cabinet
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
6
701LG100A01 Lighting Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
7
701UP110A01 UPS
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
8
701UP110A04 UPS - Power Distribution Board
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
9
401CS120A01 Profibus Box
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
10
401CS120A02 Profibus Box
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
11 GENERAL COMMENTS
44
792 Substation - Compressor Room
AREA 2
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 792 IDEAL SETTING COMMENTS
45
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 792 IDEAL SETTING COMMENTS
12
701UP210A01 UPS
Door locks / locking mechanism In good working order √ not energized
46
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 792 IDEAL SETTING COMMENTS
14
701CS120A02 Profibus Box
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
15
701CS120A03 Profibus Box
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
16 GENERAL COMMENTS
47
AREA 891 Substation - Main
N° OS DATE OF EXECUTION
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 891 IDEAL SETTING COMMENTS
Main entrance Doors (locks) Working & not damaged √ The door is damage
48
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 891 IDEAL SETTING COMMENTS
5
801UP100A01 110V DC Battery & Charger
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
6
701CS100A01 I/O Cabinet
the door lock is
Door locks / locking mechanism In good working order √ damage
10
801UP120A01 UPS
Door locks / locking mechanism In good working order √
Check for tripped circuits - Alarms (ON/OFF) Tripped C-Breakers √
11
801UP120A04 UPS - Power Distribution Board
49
IMPLEMENTATION PROCEDURE
CHECK POINTS
INSPECTED
ROUTE ROUTE Nº 891 IDEAL SETTING COMMENTS
50