Generator Protection Scheme
Generator Protection Scheme
Abstract – Sometimes, power system events have shown the need for generators to operate in the overexcited region to
support stable operation. Operation up to, and transiently beyond, the overexcited limits from the capability curve is
sometimes required. The two main issues in the paper are the generator capability in this region and the design of OEL
(OverExcitation Limiters) in the excitation system that take full advantage of the capability allowed in the design and
standards Keywords – Synchronous Machines, Excitation Controls, Generator Controls, Protective Limiters, System
Stability, Voltage Stability.
1. Introduction- To insure that generators are operated safely in the overexcited region during
system events there are two key issues. One is the generator capability in both continuous and
transient regions. The second issue is the protective limiters in the excitation system, that are
designed to protect the generator. During power system disturbances, some generators are
called to support voltage by supplying vars, either at or transiently beyond the over excited
capability. In section 2 of this paper the issues relating to generator capability are discussed.
The top section of the capability curve relates to field heating, limiting field current to
allowable levels. The second area on the capability curve to be considered in overexcitation
situations is the stator current or MVA limit, on the right side of the curve. This is becoming
more of an issue for units where the turbine may have been uprated and the generator has
the original design. In this case the increase in generator MW output comes at the expense of
available var output and overall MVA output capability. Excitation limiters, specifically OEL and
SCL (Stator Current Limit) functions are improving, and Sections 3 and 4 outline the historical
perspective on these limit functions, and the approach taken in today’s excitation controls.
Done properly, the limits can insure more of the generator capability and design margins are
available during system contingency events. Features such as recalibration of the limits based
in inlet air temperature (air cooled machine), or hydrogen pressure for H2 cooled machines
are available in today’s excitation controls
5. Summary and Conclusions- The generator excitation is limited by the defined capability
curve. In the overexcited region, the limiting factor is the design of the field circuit, a function
of its cooling and thermal profile. In general, the design metrics are driven by the capability of
the insulation systems, and structural aspects of elongation and winding stress. The guidelines
for allowable overexcitation are those in C50.13. The design margins above C50.13 are a
function of the specific machine design, and can be somewhat higher in hydro-turbine
generators with salient pole laminated rotor structures. Studies and tests may allow increasing
hydro-turbine generator over excited capability. 0 50 100 150 200 250 300 350 200 150 100 50
0 50 100 150 200 250 300 LEAD MEGAVARS LAG MEGAWATTS 40 C Cold gas 0.85 PF 0.97 PF
0.95 PF 1.0 Original Turbine Power Uprated Turbine Power QOEL QSCL Fig 6 – SCL to Protect
the Unit if the Turbine is Uprated Page 6 The generator capability is one half of the story, the
remaining part is the limiters in the excitation system. Traditionally, limiters have been used as
an automatic way of insuring the generator remains within its defined capability for either
system events or operator action. Past limiter designs have been simplistic with fixed level and
timers, and were not generally designed for maximum utilization of the capability region.
Present designs, as shown, are much more flexible and can be tailored towards maximum
utilization if the generator capability. This may be a reason to consider upgrading an older
excitation system 6. systems. He is a registered professional engineer in the State of Virginia, a
member of the IEEE Excitation System Subcommittee, and has been issued 5 patents.
Alexander Murdoch received his BSEE from Worcester Polytechnic Institute in 1970, and his
MSEE and Ph.D. from Purdue University in 1972 and 1975, respectively. Since 1975 Dr.
Murdoch has worked for General Electric, in the Power Systems Energy Consulting, where he is
a senior engineer. His areas of interest include rotating machine modeling, excitation system
design and testing and advanced control theory
The purpose of both, reverse power and low forward power relays is same namely, to
prevent damage to the steam turbine. In low forward power protection relay trips the generator circuit
breaker when the power delivered to the grid drops below a certain level (typical setting being 0.5 %
of full load). In reverse power protection relay operates immediately(5s delay) after the generator
starts drawing power from the grid instead of delivering power to the grid. Both the philosophies are
followed.
The consequences of generator motoring and the level of power drawn from the power
system will be dependent on the type of prime mover as under this condition prime mover acts as a
load for synchronous Motor. For steam turbines, the motoring power is around 0.5-3 % of rated power
of Generator. Under the failure of prime mover, due to motoring of turbine windage loss will be more
in turbine blades as there is no steam to cool it down. Thus it will lead to damage of turbine.
Normally reverse power setting is kept less than 50% of the motoring power. For example if the motoring
power of steam turbine is 4% then reverse power setting shall be kept less than 2%. It shall also be noted that
reverse power protection is provided with a time delay of around 5 s to prevent spurious operation due to
disturbances or following synchronization.
As discussed earlier, one cause of reverse power flow in a generator is failure of prime mover. Now
failure of prime mover may be because of failure of Governor or failure of Governor Valve or
maloperation of Boiler Pressure Control System.
Another cause of reverse power flow occurs during synchronization of Generator. Let us assume that
Generator is to be synchronized with the Grid. The general practice for synchronizing a Generator is
to close the breaker when the needle on the synchroscope is moving clockwise and crossing 11
O’clock position as shown in figure below.
Low Forward Power Protection is dedicated for the Generator Protection.This protection
scheme trips the generator in case of Low forward power condition.For a generator there is always a
lower limit on the power that is supplied to the grid.Because below that power limit the generator will
not be able to supply power to the grid and instead of that it will take reverse power from the grid.The
reason it takes reverse power from the grid is that below that power limit the steam supply to the
turbine becomes very less and the rotor of the Turbo-generator will not get suficient power from the
turbine to rotate(To maintain Rotor Inertia).So it will take power from the grid to maintain its
inertia,that is nothing but Reverse Power.Low Forward Power is thus provided to avoid
Reverse Power/Motoring Action of the Generator.
**Due to the motoring action the end blades of the LP Turbine get damaged.
Once the differential protection operated, the unit can not be taken into service unless the generator
winding is thoroughly examined by the maintenance staff of any internal faults
From the above figure, the short circuit ratio is given by the equation shown below.
Since the triangles Oab and Ode are similar. Therefore,
The direct axis synchronous reactance Xd is defined as the ratio of open circuit voltage for a given field current
to the armature short circuit current for the same field current.
For the field current equal to Oa, the direct axis synchronous reactance in ohms is given by the equation shown
below.
Therefore,
From the equation (7) it is clear that the short circuit ratio is equal to the reciprocal of the per unit value of the
direct axis synchronous reactance.
In a saturated magnetic circuit, the value of Xd depends upon the degree of saturation.
For the small value of the short circuit ratio (SCR), the synchronizing power is small. As the synchronizing
power keeps the machine in synchronism, a lower value of the SCR has a low stability limit. In other words, a
machine with a low SCR is less stable when operating in parallel with the other generators.
A synchronous machine with the high value of SCR had a better voltage regulation and improved steady state
stability limit, but the short circuit fault current in the armature is high. It also affects the size and cost of the
machine.
For the same value of Tph Excitation voltage is directly proportional to the field flux per pole.
Therefore,
Hence, the short circuit ratio is directly proportional to the air gap reluctance or air gap length.
If the length of the air gap is increased, the SCR can be increased. With the increase in the air gap length, the
field MMF is to be increased for the same value of excitation voltage (Ef). Hence, to increase the value of field
MMF either field current or the number of field turns has to be increased. All this requires a greater height of
field poles and, as a result, the overall diameter of the machine increases.
Thus, a conclusion is that the large value of SCR will increase the size, weight and the cost of the machine.
The typical values of the SCR for different types of machines are as follows:-
For cylindrical rotor machine, the value of SCR lies between 0.5 to 0.9.
In case of the Salient-pole machine, it lies between 1 to 1.5 and
For synchronous compensators, it is 0.4.