Process Instrumentation and Interlock List

This document provides a list of interlocks, conditions, and parameters for the ABC inlet cooler process instrumentation at a cement plant. It includes 5 items: 1. Temperature interlocks for the grate plates that will alarm at 150°C and trip the cooler drives at 250°C. 2. Pressure interlocks for the ABC fan compartment that have operational, protect, and trip ranges. 3. An interlock for the ABC fixed inlet air blasters related to kiln operations. 4. An interlock to trip cooler drives when the ABC fan stops. 5. A compressed air pressure switch interlock to start air blasters and trip cooler drives after 30 minutes.

Uploaded by

Safrin Sangia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
429 views

Process Instrumentation and Interlock List

This document provides a list of interlocks, conditions, and parameters for the ABC inlet cooler process instrumentation at a cement plant. It includes 5 items: 1. Temperature interlocks for the grate plates that will alarm at 150°C and trip the cooler drives at 250°C. 2. Pressure interlocks for the ABC fan compartment that have operational, protect, and trip ranges. 3. An interlock for the ABC fixed inlet air blasters related to kiln operations. 4. An interlock to trip cooler drives when the ABC fan stops. 5. A compressed air pressure switch interlock to start air blasters and trip cooler drives after 30 minutes.

Uploaded by

Safrin Sangia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PT.

Holcim Indonesia Tbk- Narogong Cement Process Instrumentation and Interlock list for ABC-inlet
cooler

No Condition of Interlock, Unit Rang Type of Low Low High High Comments Timer
Equipment shut down or e interlock Low High (Sec)
Analog value
Temperature at Fixed ABC Inlet,
Deg H-Alarm.
1 Grate plates (if any one out of 02) Protect 150 250 120
C HH - Trip Cooler Drives.
*
Low 1 - minimum pressure requirement
Operational 500
before ABC inlet air blasters can fire
mm
2 ABC fan Compartment pressure Start 300 Low 2 - Cooler drive start permissive
WC
Protect 200 Low Low - Alarm & trip cooler drives 5
Air-blaster firing sequence must be
stopped if the kiln,
3 ABC-Fixed inlet Air Blasters Operational Cooler, Kiln feed Off or at a kiln speed
less than 1.5 rpm

4 ABC-Fan Stop Operational Trip Cooler drives


Start Pressure switch should be healthy to start
Compressed air pressure switch the ABC inlet air blaster and Cooler
5 drives
alarm**
Operational Trip the cooler drives 30 min

Note: 1. *Timer display should be flash in CCR screen for Grate plate temp alarm

2. **Timer display should be flash in CCR screen for compressed air pressure switch alarm and the pressure switch to be set at minimum 5.5 bar
pressure alarm