Minimum Thickness of Concrete Slab, Beam, Column, Foundation

épaisseur minimales

Uploaded by

Samir Djezzar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
540 views10 pages

Minimum Thickness of Concrete Slab, Beam, Column, Foundation

épaisseur minimales

Uploaded by

Samir Djezzar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

(https://theconstructor.org/)

Minimum Thickness of Concrete Slab, Beam, C


Foundation

Minimum thickness of concrete slab, beam, column, foundation and other structural memb
the design requirements as per standard codes. Minimum thickness of concrete structural e
318-14, IRC 2009, IS 456 2000, and UBC 1997 is presented.

×
Get Noti cations
Design process includes proper assumption of structural element sizes and then check the s
make sure that it meets the requirements of the design.

If proper structural dimension is not assumed, then the design would be time consuming an
considerable effort since substantial trials will be involved till satisfactory dimensions are s

That is why majority of codes provide minimum dimensions and specifically thicknesses fo
elements.

1. Minimum Thickness of Slabs


1.1 Minimum thickness of One-way slab

ACI 318-14 provides suggested minimum thickness for one-way solid slab, as provided in Ta
deflections are calculated.

Table 1 minimum thickness of one-way solid slab unless deflections are calculated

Minimum thickness, h

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 1/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

Simply supported One end continuous Both end continuous

Members not supporting or attached to partitions or other construction likely to be damaged by

l/20 l/24 l/28

Notes: Values given shall be used directly for members with normal weight concrete and Gr
reinforcement. For other conditions, the values shall be modified as follows:

a) For lightweight concrete having equilibrium density (wc) in the range of 1440 to 1840 kg/
multiplied by (1.65 – 0.0003wc) but not less than 1.09.

b) For fy other than 420 MPa, the values shall be multiplied by (0.4 + fy/700).

×
Get Noti cations
Fig.1: one way slab thickness

1.2 Minimum thickness of Ribbed slab

ACI 318-14 recommend the same value of non-prestressed beams as provided in Table 2. Un
(UBC) specified minimum thickness of ribbed slab to be 1/12 distance between ribs or 51mm

Fig.2: Ribbed one way slab

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 2/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

Slab thickness with embedded conduits and pipes


UBC recommended minimum thickness of slabs with embedded conduits and pipes to be
overall depth of conduits or pipes.

ACI 318-14 specify that, conduits and pipes shall not be larger in outside dimension than
of slab, wall, or beam in which they are embedded

1.3 Minimum thickness of Slab on the ground

UBC recommends minimum thickness of Concrete floor slabs supported directly on the grou
whereas BCGBC4010A – Apply structural principles to residential low-rise constructions det
thickness to be 100mm.

×
Get Noti cations
Fig.3: slab on ground

1.4 Minimum thickness of Diaphragms

UBC recommend concrete slab and composite topping slab serving as structural diaphragm
earthquake forces to be 50mm.

1.5 Minimum thickness of Two-way slab

ACI 318-14 provided recommendations to determine minimum thickness of slabs (including


slabs, flat plates) that can be found here (https://theconstructor.org/structural-engg/minimu
slab-aci-318-deflection/15043/).

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 3/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

Fig.4: Two way slab

1.6 Minimum thickness of Drop panel

×
Get Noti cations
sometimes drop panels used at top of columns to improve shear strength of slabs. The minim
panels shall be quarter of slab thickness beyond the drop.

2. Minimum Thickness of Beams


ACI 318-14 provides suggested minimum thickness for non-prestressed beams, as provide
deflections are calculated.

Canadian Standard Association CSA provides similar table except for one end continuous

Table 2 minimum thickness of non-prestressed beams unless deflections are calculate

Minimum thickness, h

Simply supported One end continuous Both end continuous

Members not supporting or attached to partitions or other construction likely to be damaged by

l/16 l/18.5 l/21

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 4/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

Notes: Values given shall be used directly for members with normal weight concrete and Gr
reinforcement. For other conditions, the values shall be modified as follows:

a) For lightweight concrete having equilibrium density (wc) in the range of 1440 to 1840 kg/
multiplied by (1.65 – 0.0003wc) but not less than 1.09.

b) For fy other than 420 MPa, the values shall be multiplied by (0.4 + fy/700).

The depth of beam can also be estimated based on span/depth ratio. IS 456 2000 provides sp
control deflection of beam as provided in Table 3.

Table 3: Span to depth ratio based on the span and type of beams, IS 456 2000

Beam span Beam type Span

×
Simply supported 20

Get Noti cations


Up to 10m Cantilever 7

Continuous 26

Simply supported 20*10/span

Greater than 10m Cantilever –

Continuous 26*10/span

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 5/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

Fig.4: Reinforced concrete beam thickness,


h

3. Minimum Thickness of Columns


Dimensions of columns is based on the requirements of the design and several shapes can b
columns such as square, rectangular, trapezoidal, cylinders, and others.

×
Get Noti cations
Fig.5: Column dimensions

4. Minimum Thickness of Walls


4.1 Bearing walls

UBC recommends minimum thickness of bearing wall to 1/25 supported height or length wh
not less than 102mm.

4.2 Exterior basement wall and Foundation wall


UBC specified minimum thickness of exterior basement wall and foundation wall to be 1

The same value is recommended by International Residential Code (IRC 2009) for founda

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 6/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

×
Get Noti cations
Fig.6: wall thickness

5. Minimum Thickness of Footings


Footing on soil

The minimum depth for footing on soil is advised to be 150mm.

Footing on pile

The minimum depth for footing on pile is recommended to be 300mm

Plain concrete structural footing

The minimum thickness for plain concrete structural footing is suggested by ACI 318-14 and
same value is suggested by UBC. It shall be known that plain structural footing is not suitabl
of piles.

Raft foundation

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 7/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

The minimum thickness of raft foundation is 300mm.

Fig.7: Footing thickness

6. Minimum Thickness of Other Concrete Members

×
Get Noti cations
Table 4: minimum thickness for other structural elements

Structural Element

Pile cap

Levelling concrete below liquid retaining structures

Levelling concrete for other RCC foundations

Underground pit / reservoir (below ground water table) walls and slab

Underground pit (above water table) walls and slab

Parapet wall

Chajja

Cable / pipe trench walls and base slab

Precast trench cover

Insert plate

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 8/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

Corner angle

Madeh
Izat
Hamakareem

About Madeh Izat Hamakareem


(https://theconstructor.org/author/madeh/
Madeh is a Structural Engineer who works as Assistant Lecturer in Koya University. He is the au

×
Get Noti cations
at theconstructor.org.

Comments ( 7 )

Techoscapes International. (https://www.facebook.com/pages/Techoscapes-International/5660

 Jul 19, 2014 at 11:17 (https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/#

Nice one.

Immanuel Bulus (https://www.facebook.com/immanuel.bulus)

 Jul 4, 2014 at 07:41 (https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/#c

copied, thank you

Anas Khan (https://www.facebook.com/anas.gullo)

 Feb 13, 2014 at 16:14 (https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbxr… 9/10
04/05/2019 Minimum Thickness of Concrete Slab, Beam, Column, Foundation

great work

Waheed Ghiasi (https://www.facebook.com/eng.waheed.ahmad)

 May 9, 2013 at 09:24 (https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/

very good thank u.

Sarvesh Gupta (https://www.facebook.com/sarveshcraftone)

 Mar 21, 2013 at 04:22 (https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452

thnks

Ajay Jain (https://www.facebook.com/rissabg)

×
Get Noti cations
 Mar 20, 2013 at 06:24 (https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452

depends upon loading conditions.

Sushil Kumar (https://www.facebook.com/people/Sushil-Kumar/100001176945893)

 Mar 19, 2013 at 18:16 (https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452

Concrete thickness

Leave A Reply

You must login (https://theconstructor.org/login/) or register (https://theconstructor.org/login/) to ad

©2019 The Constructor - Civil Engineering Home

https://theconstructor.org/tips/thickness-concrete-slab-beam-column-footing/7452/?fbclid=IwAR07iInwWJSlPB_SMuPlIdPSdCqLSTJqVdRHcbx… 10/10

You might also like