Pressure Solutions: C107: Current Loop
Pressure Solutions: C107: Current Loop
Transmitting voltage signals over a significant distance has problems. The technical problem is voltage
drop, which can introduce significant errors. The commercial one is cost, with 3 conductors required.
The well-known 4 – 20 mA current loop eliminates these problems. By converting the signal into a
regulated current, there are two significant advantages. First, the voltage drop in the lines does not
affect the measurement of the current. Secondly, the signal only needs 2 wires, not 3, thus making
significant savings on cabling. Everything in the loop, which at a minimum will be a transmitter and a
receiver, is connected in series.
The 4mA zero signal allows a bit over 3mA to be used for powering the transmitter. Some advanced
systems use signals less than 4mA or greater than 20 mA to indicate abnormal conditions or faults.
Concept:
This is a modification of the industry standard 3 – 15 lb/in² pneumatic signal.
The 4 – 20 mA current loop signal is a standard transmitter signal that modulates the output from 4 to
20 mA, where 4 mA represents the bottom of the range, and 20 mA represents the top of the
transmitter range. Whether the transmitter is measuring pH or pressure or anything else, the output is
a standard electrical signal.
The concept provides the following advantages, in addition to the advantages of standardisation:-
Only 2 wires required for signal and power supply.
No voltage drops to affect the signal on long lines.
Differentiation between instrument not working, and instrument working but measuring zero.
Ability to indicate malfunction or out-of-range conditions.
Practice:
The signal span is 16 mA (20 – 4).
When interpreting the signal, we have to look at the calibrated range of the transmitter, and correlate
between signal output and assigned values. Usually the signal will be linear, any linearisation being
done in the transmitter, but this is not always the case.
For example, using a DP transmitter to measure flow using an orifice plate means that the flow is
proportional to the square root of the pressure. Most transmitters will linearise this, so that the output
is proportional to flow rather than pressure. Another example is using pressure to measure volume in a
tank. A round horizontal tank will have a sine-wave calibration. In such cases a calibration chart can
get quite complex, but if we explain the interpretation of a linear signal, this will demonstrate the
theory, which can then be adjusted for non-linear signals
P.O.Box 3357, Benoni 1500. 169, Elston Ave, Benoni, 1501, Gauteng, South Africa
Phone 422-1749/1840 Fax 421-5379 Dial code international +2711 local 011
E-mail: [email protected] Web: www.pressuresolutions.co.za
It can be said that 4mA represents 0% of the desired signal, and 20 mA represents 100% of the
desired signal.
If we want to know what a signal of 12 mA represents, we must take away the 4mA zero signal,
leaving 8 mA of actual signal. We can calculate this in two ways, either 8 mA at 25 kPa = 200 kPa, or
more basically, 8/16 x 400 kPa.
Example:
If we have a pressure transmitter with a calibrated range of -100 to 300 kPa, usually -100 kPa input
would give a 4 mA output, and 300 kPa input would give a 20 mA output.
Worksheet:
We have a 1-2-3- spreadsheet titled “maloop”, which will do all the calculations automatically for you.
P.O.Box 3357, Benoni 1500. 169, Elston Ave, Benoni, 1501, Gauteng, South Africa
Phone 422-1749/1840 Fax 421-5379 Dial code international +2711 local 011
E-mail: [email protected] Web: www.pressuresolutions.co.za