DOCUMENT REVISIONS
Sections changed in last revision are identified by a vertical line in the margin
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
- REFERENCE:
- HOLD
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
CONTENTS
7. LANGUAGE........................................................................................................................................................................ 9
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
1. PROJECT SCOPE
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
2. PURPOSE
The present Job Specification for Design defines the main principles to be applied for the design
and the implementation of the interface in between the instrumentation and the electrical devices
for the REHABILITATION AND ADAPTATION PROJECT, ALGIERS REFINERY in ALGERIA for
SONATRACH.
3. DEFINITIONS
For clarification purposes, the definitions used in the present Job Specification are recalled here:
OWNER: SONATRACH
CONTRACTOR: Technip France
PMC: Engineer India Limited EIL
ICSS Vendor: INVENSYS
LV switchgear Vendor: ABB
ECS Vendor: ABB
HV Switchgear Vendor: Siemens
VSDS Vendor: ANSALDO
For the definition and description of the main signals being exchanged, like Running, available,
local/remote, start and stop commands , refer to the document ECS I/O list: 9952T-000-NM-1661-
0001.
4. ABBREVIATIONS
The following abbreviations are used throughout this specification:
AI : Analog Input
AO : Analog Output
BMS : Burner Management System
CAI : Communication Analog Input
CCR : Central Control Room
CDI : Communication Digital Input
CDO : Communication Digital Output
DCE : Data Concentrator Electrical
DCS : Distributed Control System
DI : Digital (on/off) Input
DO : Digital (on/off) Output
ECS : Electrical Control System
EMI : Electromagnetic Interference.
FTA : Field Termination Assembly
HART : Instrumentation Digital
FAT : Factory Acceptance Test
FGS : Fire and Gas System
HV : High Voltage
HVAC : Heating, Ventilation and Air Conditioning
LV : Low Voltage
ICSS : Integrated Control and Safety System
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
5.2.3 Diagrams
9952T-000-PID-0090-1117 LEGEND SHEET – MOTORS TYPICALS
9952T-000-PID-0090-1118 LEGEND SHEET-PACKAGE’S MOTORS TYPICALS
9952T-000-PID-0090-0026 LEGEND SHEET-PACKAGE’S HEATERS TYPICALS
9952T-000-PID-0090-0027 LEGEND SHEET-PACKAGE’S HEATERS TYPICALS
9952T-000-PID-0090-0028 LEGEND SHEET-PACKAGE’S HEATERS TYPICALS
9952T-000-DW-1661-0001 ELECTRICAL CONTROL SYSTEM ARCHITECTURE DRAWING
It shall be the VENDOR responsibility to bring to the attention of the CONTRACTOR any discrepancy
between documents. The VENDOR shall not proceed with any such aspect of the work until he has
received any necessary confirmation, in writing form, from CONTRACTOR.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
Compliance by the VENDOR with the requirements of this specification does not relieve him of the
responsibilities for supplying equipment of proper design, mechanically and electrically suitable to
meet operating guarantees at specified service conditions.
7. LANGUAGE
English language shall be used for all documents related to the supply, such as correspondence,
descriptions, drawings, manuals, software and configuration. However the Human Machine
Interface’s displays descriptors, pop-up faceplates, or any other information displayed to the
operators, etc., shall be in French.
The drawing here attached presents the overall topology for the electrical equipment interfaced
with the instrumentation equipment.
The MCC typicals identification represented are the key to interpret the PIDs. The equipments
(pumps, air coolers, compressors, heaters, etc.) electrically powered are represented in the PID in
a simplified way with the respective typical identification (M0, M1, M2, M11, etc.). Other Symbols
PID represents the detailed interfaces per which typical.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
Conduit in between equipment supplied the LV vendor (DCE) and Invensys (DCS).
This conduit is dedicated to the exchange data in between the Data Concentrator Electric (DCE)
and the DCS. This link is redundant, therefore the connection is done with the two DCE: DCE-A,
mainly dedicated to group the motors of the LV switchgear’s busbar A; and the DCE-B, mainly
dedicated to group the motors of the LV switchgear’s busbar SIDE B.
Internal to the Low voltage Switchgear, a MMU (ABB) network is done in such a way that the
segment grouping the MMUs of the Switchgear side A is connected at one end to the DCE-A and
at the other end to the DCE-B; similarly other segment collects the MMUs of the side B, where one
end starts at the DCE-B and the other end is connected to the DCE-A. For further details refer to
the document: “Electrical Control System – Architecture Drawing”, 9952T-000-DW-1661-0001.
To ensure reliability and reinforce the redundancy the DCE-A & DCE-B are interconnected in
between them.
The typical shown in the general topology (§8) represents a typical LV switchgear. Per each typical
a redundant link is considered from the DCS.
The link to the DCS is based on the MODBUS TCP/IP protocol over Ethernet. The physical media
is based in a single mode optical fiber from the DCE up to the FOP (fiber optic panel), and then
converted to Ethernet UTP cable to reach the Ethernet termination card on the DCS.
A preparation meeting and a prototype acceptance test is foreseen to validate the following
subjects:
9 Protocol
9 Data packaging and format (single precision-floating, integers, coils, bits, etc.)
9 Contiguous registers, to improve the scanning cycle.
9 Redundancy type
9 Speed
9 Physical media, evaluate need of converters.
9 IP addresses
9 Heartbit implementation, function code 8
9 Communication disruption strategy to be adapted to the electrical equipment under operation.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
Any way the MODBUS link shall be analysed and implemented to cope with link recovery after
short communication interruption, without impact to the electrical equipment.
For this link/conduit refer to the ABB’s vendor document: “LV MCC Switchgears, MMU type
UMC100 table of exchanged datas and communication interfaces”, reference vendor: 12-02-
J00909-B06.For further details about data parameters and characteristics of the data frames for the
feedbacks and commands.
MOTOR TYPE: M1Z Motor without START from DCS + ESD Trip
I/O type DCS
Hardwired
Signal Description Instrument TAG SOFT CONDUIT Signal type to/from
DCS to/from DCE ESD
Running Status MIR-YYYY CDI* "1" means RUNNING DCE
Available MXL-YYYY CDI* "1" means AVAILABLE DCE
"1" authorization to RUN.
STOP command MHSL-YYYY CDO* DCE
"0" Stop motor
"1" authorization to RUN.
(contact closed from relay ESD)
TRIP MZY-YYYY DO "0" Stop motor
MCC
(contact open from relay ESD)
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
MOTOR TYPE: M2Z Motor with start from DCS + ESD trip
I/O type DCS
Hardwired
Signal Description Instrument TAG SOFT CONDUIT Signal type to/from
DCS to/from DCE ESD
Running Status MIR-YYYY CDI* "1" means RUNNING DCE
Available MXL-YYYY CDI* "1" means AVAILABLE DCE
"1" means REMOTE
LOCAL/REMOTE MHL-YYYY CDI* DCE
"0" means LOCAL
"1" authorization to RUN.
STOP command MHSL-YYYY CDO* DCE
"0" Stop motor
START command MHSH-YYYY CDO* Pulse to "1" to START DCE
"1" authorization to RUN.
(contact closed from relay ESD)
TRIP MZY-YYYY DO "0" Stop motor
MCC
(contact open from relay ESD)
* refer to the ABB’s vendor document: “LV MCC Switchgears, MMU type UMC100 table of exchanged datas and communication interfaces”,
reference vendor: 12-02-J00909-B06
Conduit in between equipment supplied the ECS vendor (ECS controllershub) in the CCR and
Invensys (DCS).
This conduit is dedicated to the exchange data in between the Electrical Control System (ECS)
data concentrator and the DCS. This link is redundant; therefore the connection is done with the
two ECS controllers in the CCR:.
The typical shown in the general topology (§8) represents a typical HV switchgear. Per each typical
a redundant link is considered from the DCS.
The link to the DCS is based on the MODBUS TCP/IP protocol over Ethernet. The physical media
is based in a single mode optical fiber from the ECS up to the FOP (fiber optic panel), and then
converted to Ethernet UTP cable to reach the Ethernet termination card on the DCS.
A preparation meeting and a prototype acceptance test is foreseen to validate the following
subjects:
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
9 Protocol
9 Data packaging and format (single precision-floating, integers, coils, bits, etc.)
9 Contiguous registers, to improve the scanning cycle.
9 Redundancy type
9 Speed
9 Physical media, evaluate need of converters.
9 IP addresses
9 Heartbit implementation, function code 8
9 Communication disruption strategy to be adapted to the electrical equipment under operation.
Any way the MODBUS link shall be analysed and implemented to cope with link recovery after
short communication interruption, with respective system alarm.
The data exchanged via this conduit are detailed in the document number:
Conduit in between equipment supplied the VSDS vendor and Invensys (DCS).
This conduit is dedicated to the exchange data in between the Data Concentrator Electric (DCE)
VSDS and the DCS. This link is redundant, therefore the connection is done with the two DCE-
VSDS: DCE-VSDS-A, mainly dedicated to group the motors of the LV switchgear’s busbar A; and
the DCE-VSDS-B, mainly dedicated to group the motors of the LV switchgear’s busbar B.
Internal to the Low voltage Switchgear, a VSDS network is done in such a way that the segment
grouping the VSDSs of the Switchgear side A is connected at one end to the DCE-VSDS-A and at
the other end to the DCE-VSDS-B; similarly other segment collects the MMUs of the side B, where
one end starts at the DCE-VSDS-B and the other end is connected to the DCE-VSDS-A. For
further details refer to the document: “Electrical Control System – Architecture Drawing”, 9952T-
000-DW-1661-0001.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
To ensure reliability and reinforce the redundancy the DCE-VSDS-A & DCE-VSDS-B are
interconnected in between them.
The typical shown in the general topology (§8) represents a typical LV switchgear. Per each typical
a redundant link is considered from the DCS.
The link to the DCS is based on the MODBUS TCP/IP protocol over Ethernet. The physical media
is based in a single mode optical fiber from the DCE up to the FOP (fiber optic panel), and then
converted to Ethernet UTP cable to reach the Ethernet termination card on the DCS.
In case that only one VSDS is present in switchgear, then the concentrator switch will not be used,
and the VSDS will directly linked to the DCS, with no redundancy.
The ESD trip remains hardwired.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
Some motors typicals uses the hardwired type connection in between the DCS/ESD,PLCs and the
MCC.
Generally the ESD commands, Variable speed settings to the VSDS and PLCs and other third
controllers (different to the ESD, DCS) commanded motors’ signals are interfaced by hardwired
cables per each signal.
Similarly for the HV motors’ feedbacks and commands, the interfaces are hardwired.
The identification “package” will be used to consider the: PLCs, Mark VI, standalone controllers,
Electrical Heaters equipped with thryristors, etc.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
The motors typicals are referenced in the PID: 9952T-000-PID-0090-1117/1118 and the PID for the
HV motors
The data identified in the column: “to/from”, as MCC, is the one related to this conduit:
MOTOR TYPE: M11Z Motor without START from Package + ESD Trip
I/O type package
Hardwired
Signal Description Instrument TAG HARDWIRED CONDUIT Signal type to/from
Package to/from MCC ESD
"1" means RUNNING
Running Status MIR-YYYY DI MCC
(contact closed at MCC)
"1" means AVAILABLE
Available MXL-YYYY DI MCC
(contact closed at MCC)
"1" authorization to START.
(contact closed from package)
STOP command MHSL-YYYY DO1 "0" Stop motor
MCC
(contact open from package)
"1" authorization to START.
(contact closed from relay ESD)
TRIP MZY-YYYY DO "0" Stop motor
MCC
(contact open from relay ESD)
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
MOTOR TYPE: M12Z Motor with start from Package + ESD trip
I/O type package
Hardwired
Signal Description Instrument TAG HARDWIRED CONDUIT Signal type to/from
Package to/from MCC ESD
"1" means RUNNING
Running Status MIR-YYYY DI MCC
(contact closed at MCC)
"1" means AVAILABLE
Available MXL-YYYY DI MCC
(contact closed at MCC)
"1" means REMOTE
(contact closed at MCC)
LOCAL/REMOTE MHL-YYYY DI MCC
"0" means LOCAL
(contact open at MCC)
"1" authorization to START.
STOP command MHSL-YYYY DO1 MCC
"0" Stop motor
START command MHSH-YYYY DO1 Pulse to "1" to START MCC
"1" authorization to START.
(contact closed from relay ESD)
TRIP MZY-YYYY DO "0" Stop motor
MCC
(contact open from relay ESD)
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
MOTOR TYPE: M22Z HV Motor with start from Package + ESD trip
I/O type package
Hardwired
Signal Description Instrument TAG HARDWIRED CONDUIT Signal type to/from
Package to/from MCC ESD
"1" means RUNNING
Running Status MIR-YYYY DI MCC
(contact closed at MCC)
"1" means AVAILABLE
Available MXL-YYYY DI MCC
(contact closed at MCC)
"1" means REMOTE
(contact closed at MCC)
LOCAL/REMOTE MHL-YYYY DI MCC
"0" means LOCAL
(contact open at MCC)
"1" authorization to START.
STOP command MHSL-YYYY DO1 MCC
"0" Stop motor
START command MHSH-YYYY DO1 Pulse to "1" to START MCC
"1" authorization to START.
(contact closed from relay ESD)
TRIP MZY-YYYY DO "0" Stop motor
MCC
(contact open from relay ESD)
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
10.1 SCOPE
The electricals heaters can be of two different types:
Coils operated by loading thyristors, which allow temperature variation by modulating the power.
Coils simply powered by a nominal power, no modulation.
Even when based on the same signals as the conduits already explained, different typicals were
defined to represent the signals being exchanged. These typicals can be seen in the following
drawings: 9952T-000-PID-0090-0026/0027/0028.
Generally the control panels for the Thyristors powered heaters are supplied loose and installed in
the electrical substation, including and electronic modulating circuit top trgger the thyristors, the
respective terminals strip to interface the control sources signals from the DCS or Packages (PLCs,
other standalone controllers).
The nominal electrical heaters are simply powered by a MCC.
Special care shall be taken for the analog signals being exchanged, like: current measurements.
The DCS or Package, powers in 4-20 mA @ 24 VDC the loop, therefore the heaters current device
shall be passive. If it is not the case, the Heater panel shall be equipped with isolator for the
concerned signals.
The interface to the “nominal” powered heaters can be software or hardwired. If interfaced with the
DCS, mainly software; if interfaced with packages, hardwired.
10.2.1 Heater Typicals interfaced with DCS via software conduit + ESD:
The interfaces are only shown with the DCE since are expected only interfaces with LV MCCs
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
10.2.2 Heater Typicals interfaced in between the DCS via hardwired + ESD and thyristor electrical heaters
control panels:
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
Heater
"1" means AVAILABLE
Available MXL-YYYY DI control
(contact closed at MCC) panel
"1" means REMOTE Heater
(contact closed at MCC) control
LOCAL/REMOTE MHL-YYYY DI panel
"0" means LOCAL
(contact open at MCC)
Heater
"1" authorization to START.
STOP command MHSL-YYYY DO1 control
"0" Stop heater panel
Heater
START command MHSH-YYYY DO1 Pulse to "1" to START control
panel
Heater
4-20 mA@24VDC powered
Temperature set MSC-YYYY AO control
by the DCS panel
Heater
4-20 mA@24VDC powered
Heater current MI-YYYY AI control
by the DCS panel
HEATER TYPE: H3Z Heater with start from DCS + ESD trip
I/O type DCS
Hardwired
Signal Description Instrument TAG HARDWIRED CONDUIT Signal type to/from
DCS to/from MCC ESD
Heater
"1" means ON
ON Status MIR-YYYY DI control
(contact closed at MCC) panel
Heater
"1" means AVAILABLE
Available MXL-YYYY DI control
(contact closed at MCC) panel
"1" means REMOTE Heater
(contact closed at MCC) control
LOCAL/REMOTE MHL-YYYY DI panel
"0" means LOCAL
(contact open at MCC)
Heater
"1" authorization to START.
STOP command MHSL-YYYY DO1 control
"0" Stop motor panel
Heater
START command MHSH-YYYY DO1 Pulse to "1" to START control
panel
Pulse to "1" START (close Heater
START command control
MZYH-YYYY DO contact from relay ESD)
(if applicable) panel
"0" Stop motor
"1" authorization to RUN. Heater
(contact closed from relay ESD) control
TRIP MZY-YYYY DO "0" Stop heater panel
(contact open from relay ESD)
Heater
4-20 mA@24VDC powered by
Temperature set MSC-YYYY AO the DCS
control
panel
Heater
4-20 mA@24VDC powered by
Heater current MI-YYYY AI the DCS
control
panel
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
10.2.4 Typicals interfaced in between the Packages via hardwired + ESD and thyristor electrical heaters
control panels:
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
HEATER TYPE: H13Z Heater with start from package + ESD trip
I/O type package
Hardwired
Signal Description Instrument TAG HARDWIRED CONDUIT Signal type to/from
DCS to/from MCC ESD
Heater
"1" means ON
ON Status MIR-YYYY DI control
(contact closed at MCC) panel
Heater
"1" means AVAILABLE
Available MXL-YYYY DI control
(contact closed at MCC) panel
"1" means REMOTE Heater
(contact closed at MCC) control
LOCAL/REMOTE MHL-YYYY DI panel
"0" means LOCAL
(contact open at MCC)
Heater
"1" authorization to START.
STOP command MHSL-YYYY DO1 control
"0" Stop motor panel
Heater
START command MHSH-YYYY DO1 Pulse to "1" to START control
panel
Pulse to "1" START (close Heater
START command control
MZYH-YYYY DO contact from relay ESD)
(if applicable) panel
"0" Stop motor
"1" authorization to RUN. Heater
(contact closed from relay ESD) control
TRIP MZY-YYYY DO "0" Stop heater panel
(contact open from relay ESD)
Heater
4-20 mA@24VDC powered by
Temperature set MSC-YYYY AO the package
control
panel
Heater
4-20 mA@24VDC powered by
Heater current MI-YYYY AI the package
control
panel
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
11.1 GENERAL
As shown in the topology (refer to §8.1) to execute this interface two cabinets are foreseen:
The Interposing panel (IRP), located in the instrumentation’s rackroom.
The Elec/Inst Marshalling (EIM) located in the Substation.
If it is a LV MCC:
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
Commands As described previously, the start and stop commands from the systems (DCS and
packages) are dry contact, voltfree type. Therefore these contacts are powered by
the control voltage from the MCC, in 24VDC and the current driven is not higher
than 0,5 Amp.
Status The MCC provides dry contacts capable of handling the 24 VDC supplied by the
Systems
ESD The ESD provides a dry contact powered by the MCC at 230 VAC
If it is a HV MCC:
Commands As described previously, the start and stop commands from the systems (DCS and
packages) are dry contact, voltfree type. Therefore these contacts are powered by
the control voltage from the MCC, in 110VDC and the current driven is not higher
than 2 0,5 Amp.
Status The MCC provides dry contacts capable of handling the 24 VDC supplied by the
Systems
ESD The ESD provides a dry contact powered by the MCC at 110 VDC
For the case of heaters with thyristors applies the same as the LV MCCs, as far concerns the
voltage levels.
The relays’ contact used for the commands shall be able to handle the current drawn by the MCC
coil, that will be no more than 0,5 amp.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
For the digital inputs, special consideration shall be taken to consider the channel protection: is it
galvanic protected, or a fuse is required. The packages shall consider the respective channel
protection for overvoltage, short-circuit, voltage reversal.
11.3.2 ESD
The ESD signals, a trip with a SIL identified equal or higher than 1, shall be interfaced by using a
special safety relay, normally named as SIL capable relay.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
MULTICABLE INTERNAL
FIELD TERMINATION ASSEMBLY INSTRUMENTATION MULTICABLE IN BETWEEN MULTICABLE INTERNAL
(FTA-PLC)
Digital Inputs
ROOM Interposing Panel INSTRUMENTATION Electrical Marshalling SUBSTATION
ROOM- SUBSTATION
1/6/12/24 pairs. 7G conductors/wires.
Isolation Voltage 300 V 1/6/12/24 pairs. Max current:0,5 Amp
Terminal Isolation Voltage 300 V Terminal Isolation Voltage 500 V
24 strips strips
VDC
X2 X2
X4: FEEDBACKS
X4 X4
MCC
Relay – deenergized condition
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
12.1 GENERAL
As shown in the topology (refer to §8.1) the DCS OPC server and the ECS OPC server are
interconnected.
The document ECS I/O list, number: 9952T-000-NM-1661-0001, list all the signals exchanged thru
this conduit.
The ECS OPC server will run the server license.
The DCS OPC server will run the client license.
Proper coordination required to settle the communication in between the DCS vendor and the ECS
vendor.
13.1 GENERAL
The UPS system shall be capable of operating at the following power supply specifications:
The system shall be compatible with an electrical AC feeder of the type insulated earthed neutral
(IT system with core balance and permanent insulation monitoring)TN-S.
All necessary transformers and accessories to comply with this requirement shall be included by
ICSS Vendor.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
13.1.2 Fire and Gas System (FGS) UPS autonomy & sizing
The autonomy for the UPS shall be, in general, of 8 hours.
The UPS sizing shall be based in the consumers list
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
14.1 GENERAL
The distribution panels/cabinets non-UPS 230 VAC for utilities, like cabinet’s socket and lamps, are
supplied by the electricals and installed in the instrumentation rackrooms.
The socket’s feeders shall be protected by differential current 30mA.
PP 1 - ANG - rev. 2
ALGIERS REFINERY
REHABILITATION AND ADAPTATION PROJECT
Document Class : CLASS 2 Project N° - Unit Doc Type Material Code Serial Number Rev. Page
PP 1 - ANG - rev. 2