Demineralized Water Unit Foundation Design
Demineralized Water Unit Foundation Design
of Nigeria Ltd.
ANG-TPG-ASNG1-CX-1380-00056
ADDITIONAL AGREEMENT/APPROVAL RECORD
Party Ref Ind Name Sign Date
Revision Philosophy
All FEED documents for review will be issued at R01, with subsequent R02, R03, etc as required with status
IFR or IFA
All revisions approved for issue or design will be issued at A01, with subsequent A02, A03, etc as required with
status AFD.
All Detailed design documents for review will be issued at D01, with subsequent D02, D03, etc as required
Documents approved for Construction will be issued at C01, C02, and C03 respectively with status AFC.
Revisions approved for Tender will be issued as T01, with subsequent come as T02, T03 etc with status AFT
All revisions approved for Purchase will be issued as P01, with subsequent P02, P03, etc with status AFP
All Cancelled documents will be issued at X01, X02, and X03 respectively with status CAN.
Documents or drawings revised as “As built” will be issued as Z01, Z02, Z03 etc with status ASB.
Narrative sections revised from previous approved issues are to be noted in the table below and/or highlighted
in the RH margin (using the appropriate revision status) thus: | A02
Previous revision details to be removed from the cover page at subsequent issues
Drawings/diagrams revised from previous approved issues are highlighted by 'clouding' the affected areas and
by the use of a triangle containing the revision status.
Revision History
Page 2 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
Table of Contents
1. INTRODUCTION 4
1.1. Project Overview / Description 4
1.2. Scope 5
1.3. Definitions 5
1.4. Abbreviations 5
1.5. Language 6
1.6. Unit of measurement 6
1.7. Design Philosophy 7
1.8. Software 7
2. REFERENCE DOCUMENT 8
2.1. Project Specifications and Standards 8
2.2. SPDC Design Standards and Specifications 8
2.3. Design and Engineering Practice (DEP) Technical Specifications 9
2.4. Eurocodes and International Standards 9
2.5. Project Documents/Drawings 9
2.6. Other References 9
2.7. Order of Precedence 9
3. DESIGN LOADS (ACTIONS) AND LOAD COMBINATIONS 11
3.1. Permanent Load 11
3.2. Variable and Operating Load 11
3.3. Equipment Loading Details for Analysis 11
3.4. Applied Combination Loads 11
3.4.1. Equilibrium Limit State (EQU) Verification 11
3.4.2. Structural (STR) & Geotechnical (GEO) Limit States Verification 12
3.5. Environmental Load 13
3.6. Dynamic Load 13
3.7. Earthquake Load 13
3.8. Thermal Loads 13
3.9. Loads during Erection and Maintenance 13
4. DESIGN CALCULATION METHOD 14
4.1. Design Approach 14
4.2. Geotechnical Data 14
5. CONCLUSION 15
Appendices
Page 3 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
1. INTRODUCTION
This Document Provides a Detailed Calculation Report for the Structural Design of Demineralized
Water Unit Skid Foundation with respect to the Assa North-Ohaji South Project.
The key objective this design is to ensure that the skid foundation designed have adequate capacity
to withstand the effect of permanent loads, variable loads and various loads that the structure may
be exposed to in its service life.
Page 4 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
1.2. Scope
The general scope for the Demineralized Water Unit Skid Foundation comprises the deliverable
below:
Foundation Design Calculation Report
Foundation Layout Drawings and Details
Beam Layout Drawings and details
Reinforcement Details complete with Bar Bending Schedules
Civil Structural Material Take Off
1.3. Definitions
For this document, the following definitions shall have the meanings stated:
SHALL, indicates a mandatory requirement.
SHOULD, indicates a preferred course of action or strongly recommended to comply with the
requirements of this specification.
MAY, indicates an acceptable course of action.
PRINCIPAL is the party who initiates the project and ultimately pays for its design and
construction. The Principal will generally specify the technical requirements. The Principal
may also include an agent or consultant, authorized to act for, and on behalf of, the principal.
CONTRACTOR is the party, which carries out all or part of the engineering, procurement,
construction and commissioning or management of a project. The principal may sometimes
undertake all or part of the duties of the Contractor.
MANUFACTURER/SUPPLIER/VENDOR is the party, which manufactures and/or
supplies the equipment and services to perform the duties specified by the Contractor.
1.4. Abbreviations
Page 5 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
DEP Design and Engineering Practice
EN European Norms
ESALs Equivalent Single Axle Loads
FEED Front End Engineering Design
FERA Fire Explosion and Risk Assessment
FGS Fire and Gas Detection System
FLB Field Logistics Base
HSE Health, Safety and Environment
HSSE & SP Health, Safety, Security, Environment & Social Performance
HDPE High Density Poly Ethylene
MMstb Million Stock Tank Barrel
MMscfd Million Standard Cubic Feet per Day
CEIP Community Electricity Interdependency Project
PTF Primary Treatment Facility
JV Joint Venture
SPDC Shell Petroleum Development Company of Nigeria Limited
TCF Trillion Cubic Feet
1.5. Language
Unless otherwise agreed in writing, the language of written and spoken communication between
the parties to this scope of supply is English. Where approval of the Principal to obtain
documentation in other languages is granted, the Contractor shall at no extra cost to the Principal,
provide translation to English, of such languages.
Page 6 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
1.7. Design Philosophy
The Analyses design calculations were carried out according to the procedures given in the
reference codes and standards as well as SPDC DEP specifications. The Limit State design
approach was used.
1.8. Software
Excel spreadsheet accompanied with hand calculations have been used for the analysis and design
of civil/structural works based on references in section 2 below and the site conditions and
parameters in the geotechnical reports.
Page 7 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
2. REFERENCE DOCUMENT
This section defines the reference documents and drawings used for this detailed engineering
design.
The construction shall comply fully with the latest edition of statutory laws and regulations of
Nigeria, relevant SPDC Standards and Specifications, International Standards & Codes of
Practice and industry-published guidelines.
All Building Structural elements were designed in accordance with the following specifications,
codes and standards below.
Where national regulations exist, their provision and those of the standards and codes to which
they refer, were applied.
In the case where the design of a structure or part of a structure is not covered by any of the
listed reference documents, the use of a reputable and fit for purpose international code or
regulation, subject to prior approval of the Principal was adopted by the contractor.
In all cases, Contractor avoided mixing the requirements of several different codes or
regulations when designing a particular item of a structure.
Only the main reference documents were indicated; the Contractor was responsible for
complying with all secondary reference documents dealing with the subject of this document.
The execution of the work and such design and detailing as the Contractor may be required to
carry out was performed in accordance with the relevant specification, codes or standards.
Unless otherwise stated, reference to any specification, code or standard meant the latest edition
of that standard or code, including addenda or supplements or revisions hereto, in being at
the time of contract award.
Page 8 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
2.3. Design and Engineering Practice (DEP) Technical Specifications
Document No Title
EN 1990:2002 Eurocode – Basis of Structural Design.
EN 1991 Eurocode 1 – Actions on Structures
EN 1992 Eurocode 2 – Design of Concrete Structures.
EN 1993 Eurocode 3 – Design of Steel Structures.
EN 1994 Eurocode 4 – Design of Composite Steel and Concrete Structures.
EN 1997 Eurocode 7 – Geotechnical Design.
EN 206 Concrete: Specification, Performance, Production and Conformity
ISO 14001 Environmental Management Systems Requirements with Guidance for Use
ISO9000 Series Quality Management System
Refer to the Project Specifications (if any) for other relevant/applicable Codes and Standards
Page 9 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
Project Specifications
Relevant Shell HSSE Standards (HSSE Control Framework and SPDC Reference Manuals),
including the relevant Shell Design & Engineering Practices (DEP), in particular the
mandatory DEM1 requirements and DEM2
International Codes, Standards, Agreements and Protocols, e.g. ISO, ASME, API, Montreal,
etc
Where there was conflict between the above standards and the project specifications, the project
specifications took precedence.
Page 10 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
3. DESIGN LOADS (ACTIONS) AND LOAD COMBINATIONS
Refer to Shell DEP 34.00.01.30 - Gen, EN 1993 – Eurocode 3 and to the following:
Table 4‑1: Equilibrium Limit State-Partial Factors on Actions (Excerpt from Annex A, Table A1)
Page 11 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
Table 4‑2: Equilibrium Limit State-Partial Factors for Soil Parameters (Excerpt from Annex A,
Table A2)
Table 4‑3: Structural & Geotechnical Limit State – Partial Factors on actions or the effect of actions
(Excerpt from Annex A, Table A3)
Table 4‑4: Structural & Geotechnical Limit State – Partial Factors for Soil Parameters (Excerpt
from Annex A, Table A4)
Page 12 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
Table 4‑5: Structural & Geotechnical Limit State – Partial Resistance Factors for Spread Foundation
(Excerpt from Annex A, Table A5)
Load combinations details applied in the design are as shown in the design calculations report.
Page 13 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
4. DESIGN CALCULATION METHOD
The design calculations were carried out according to the procedures given in the reference codes
and standards as well as Shell DEP specifications. The Limit State design approach was used.
Spreadsheets were utilized for the calculations.
Adequate sizing of all foundation structural elements and reinforcement steel was provided as per
requirements of reference codes and standards. Detailed design calculations and material take-off
are presented in Appendix A and Appendix B respectively.
Page 14 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
5. CONCLUSION
Foundation of size 6.805 m x 1.47 m x 0.8m deep is adequate for the Demineralized Water Unit
Skid Foundation.
The foundation maximum settlement is 9.2mm which is less than 25mm hence okay.
The 0.3m thick provided supporting slab passed all requirements for bending, shear and
deflection.
The 0.8m deep beams provided passed all requirements for bending, shear and deflection.
Total volume of reinforced concrete is 13.16 m3.
Total volume of blinding concrete is 1.85 m3.
Total tonnage of reinforcing steel is 0.53 tonnes.
Eight (8) 20mm diameter anchor bolts provided by vendor is adequate. Bolt length calculated is
350mm.
Page 15 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
Appendix A – Demineralized Water Unit Skid Foundation Calculation
Page 16 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
SHELL PETROLEUM DEVELOPMENT COMPANY OF NIGERIA
DEMINERALIZED WATER UNIT SKID FOUNDATION CALCULATION
CUSTOMER SPDC REVISION D01
LOCATION Assa North Ohaji South DATE 22-Mar-19
DOC. NO. ANG-TPG-ASNG1-CX-1380-00056 ORIGINATOR I. Joseph
Part of structure Demineralized Water Unit Skid Foundation CHECKER A. Sobowale
PART APPROVER A. Sobowale
REF. CALCULATIONS OUTPUT
1 of 13
6805 mm
6505 mm
BEAM 1
PANEL 1 (P1)
1470 mm
1170 mm
BEAM 2
BEAM 2
BEAM 1
6805 mm
FGL 100 mm
800 mm
700 mm
300 mm
300 mm
6505 mm
3253 3253
SKID FOOTPRINT
585 ey = 0.02m
ex = 0.05m
585 Wo
2 of 13
Section 7.9.3 Force coefficient-cf = cf,o* ψγ*k ; k is a factor for most unfavorable wind direction.
a = 3.15m
b=0.5
a= 6.71 m
b= 0.50 m
3 of 13
Section 7.13 ,
Table 7.16 Effective slenderness ratio : For l < 15m, λ = Min(2l/b or 70) = 4.290
Cf = cf,o* ψγ *k = 0.786
Eqn 7.20 Aref : l x b = 20.963 m2
WL = (cscd)*cf*qpze*Aref 14.303 KN
4 of 13
5 of 13
14.26 30.29
6 of 13
7 of 13
A B
Vmax= -93.7 kN
8 of 13
9 of 13
A B
Vmax = 3.57 kN
A B
10 of 13
Asw/s = VED/(zfywdcotθ )
z = 0.9d 693.72 mm
fywd = 0.8fyk 328.00 N/mm2
cotθ = 2.50
Asw/s = VED/(zfywdcotθ ) 0.002
Asw cross sectional area for 12mm diameter two legged links = 157.10 mm2
s = Asw/0.002 78627.31 mm
Provide H10 @250 mm c/c as links
11 of 13
0.10 m
0.65 m
12 of 13
1296
BOLTING LAYOUT
13 of 13
Page 17 of 17
Demineralized Water Unit Skid Foundation Design
ANG-TPG-ASNG1-CX-1380-00056
Report
This document is controlled electronically and is uncontrolled when printed.
SHELL PETROLEUM DEVELOPMENT COMPANY OF NIGERIA
DEMINERALIZED WATER UNIT SKID FOUNDATION MTO
CUSTOMER SPDC REVISION D01
LOCATION Assa North Ohaji South DATE 22-Mar-19
DOC. NO. ANG-TPG-ASNG1-CX-1380-00056 ORIGINATOR I. Joseph
Part of structure Demineralized Water Unit Skid Foundation CHECKER A. Sobowale
PART APPROVER A. Sobowale
STRUCTURAL
ITEM MTO CALCULATIONS
MATERIAL
PIECE NO Unit
MATERIAL Contingency Factored Actual Weight
DESCRIPTION Size of piece Qty Cal. Quantity Unit Unit Wgt
GRADE (0%) Quantity 3 (mT)
(kg/m )
0%
A C25/30 REINFORCED CONCRETE 2400
Raft Slab GRADE 30 3.00 1 3.00 m3 0.0 3.00 m3 7.20
Raft Beam 1 GRADE 30 1.02 2 2.04 m3 0.0 2.04 m3 4.90
Raft Beam 2 GRADE 30 0.22 2 0.44 m3 0.0 0.44 m3 1.06
5.48 m3 0.00 5.48 m3 13.16
C REINFORCEMENT 7650
Rebar Sizes H8 H10 H12 H16 H20 H25
Raft Slab 410N/mm2 204.76 Kg 0.20
Raft Beam 1 410N/mm2 58.52 72.51 144.1 Kg 0.28
Raft Beam 2 410N/mm2 9.36 17.31 27.42 Kg 0.05
0.00 294.58 0.00 0.00 0.53