Proj: Andalus University Building EC Enter ST

The document provides calculations for sizing the heat exchanger, expansion tanks, boiler, and air handling units (AHUs) for a dormitory building project. It calculates the total heating capacity required as 248,803 Watts, sizing the boiler system at 150,000 Watts with two units. Heat loads and water flows are also calculated for AHUs serving different floors to condition fresh air intake. Sizing is based on occupancy data, system component capacities, and temperature differences.

Uploaded by

sameh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views7 pages

Proj: Andalus University Building EC Enter ST

The document provides calculations for sizing the heat exchanger, expansion tanks, boiler, and air handling units (AHUs) for a dormitory building project. It calculates the total heating capacity required as 248,803 Watts, sizing the boiler system at 150,000 Watts with two units. Heat loads and water flows are also calculated for AHUs serving different floors to condition fresh air intake. Sizing is based on occupancy data, system component capacities, and temperature differences.

Uploaded by

sameh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 7

TECCENTER EST.

Proj: Andalus University Building


Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building

Sizing of Heat Exchanger

1.0 Total capacity of Heat Exchanger in Dormitory

Given:
For the requirement of Dormitory
Each student = 120 Li/day
No. of Students = 36

Recovery Required :

Rr = No. of Students x Hourly usage


Rr = 36 x 120
Rr = 4,320 Li/day
Rr = 4320 / 10 hrs
Rr = 432 Li/Hr say 500 Li/Hr.

For the sizing of the Heat Exchanger

Where:
q = 500 f ∆T
q = Heat load total (W)
500 = constant rounded off from 8.33 x 60 (Btu - Gal/Hr - min - ºF)
∆T = Water temperature difference (ºF)
f = flow rate of water (gpm)

Given:
f = 500 Li/Hr = 2.2 gal/min
Tcws = 50ºF
Twhs = 150ºF

Solution:

q = 2.2 gpm x 500 Btu-gal / Hr - min - ºF x 100ºF


q = 110,000 Btu/Hr
q = 32,230 W
TECCENTER EST.
Proj: Andalus University Building
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building

Sizing of Expansion Tanks

1.0 Total capacity of Expansion Tanks in Dormitory

Given :
Boiler Capacity 250 gals
Radiators 455 gals
Air Handling Unit 50 gals
Heat Exchanger 135 gals
Water inside Pipe 170 gals

Total Gallon 1060 gals.

Solution:

Pf = Static pressure of the fluid in the tank when the system is filled (psig)
H = Distance of the inlet of expansion tank to the top of the system (ft)
Dc = Density of the fluid at its initial temperature (lb/ft³)
Vt = Minimun required tank volume (gals)
Vs = Fluid volume in the system (gals)
TECCENTER EST.
Proj: Andalus University Building
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building

Sizing of Boiler for Dormitory

1.0 Total capacity of Boiler in Dormitory


Given:

Ground Floor
Total Heating Capacity 31,686 W

Fisrt Floor
Total Heating Capacity 37,714 W

Second Floor
Total Heating Capacity 45,533 W

Air Handling Unit -01 60,060 W


Air Handling Unit -01 41,580 W

Heat Exchanger 32,230 W

Total Heat Load 248,803 W

Plus S. F. 20% 49,761 W

Grand Total Heat Load 298,564 W

Size of the Boiler 150,000.00 W 2 Units


TECCENTER EST.
Proj: Al- Andalus University Project Electro-Mechanical Works
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building

Calculation for AHU-02 Heat Load capacity and Flow of Water


Serving First & Second Flr.

1.0 Calculation for Heat Load capacity of Fresh Air


Given:
Q.= 990 l/s
Tr = 20ºC
To = -5ºC
cp = 1Kj/ Kg . ºC
p = 1.2 Kg/ m³

Where:
qs = Q x ∆T x cp x p
qs = Heat Loat Total (Watts)
Q. = Supply air capacity (Li/s)
∆T = Temperature difference (ºC)
Tr = Room Temperature (ºC)
To = Ambient Temperature (ºC)
cp = specific heat of air (Kj/ (Kg . ºC))
p = density of air at temperature To (Kg/ m³)

Solution:
qs = 990li/s x ((20 - (-5)ºC) x 1.2
qs = 29,700 Watts

Total Heat Load of AHU-02 including the load for Stair and Corridor
qt = 29,700 + 3,212 + 790 + 1,466 + 4,384
qt = 39,552 Watts

qt = 39,552 W x 3,413 Btu/Hr


1Kw / 1000 W
qt = 134,991 Btu/Hr
qt = 34,012 Kcal/Hr

2.0 For Flow of Water by Tredgold definition of BTU.


Given:
Q.= 134,991 Btu/Hr
∆T = 20ºF
p = 8.33 Gals/ºF

Where:
Fw = Q / ∆T x p
Fw = Flow of Water (Gpm)
Q. = Heat Load Total (Btu/hr)
∆T = Water Supply and ReturnTemperature difference (ºF)
p = The weight gallon of water (gal/ ºF)

Solution:
Fw = 8.33 gals/ ºF x 20ºF
Fw = 166.6 Gals
Fw = 134,991 Btu/hr
166.6 gals x 60 min /hr
Fw = 13.5 gals/min
Fw = 1.0 l/s
TECCENTER EST.
Proj: Al- Andalus University Project Electro-Mechanical Works
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building

3.0 For the Temperature of Air Supply from AHU-02.


Given:
Q.= 990 l/s
Tr = 22ºC
To = -5ºC
cp = 1Kj/ Kg . ºC
p = 1.2 Kg/ m³

Where:
qs = Q x ∆T x cp x p
qs = Heat Loat Total (Watts)
Q. = Supply air capacity (Li/s)
∆T = Temperature difference (ºC)
cp = specific heat of air (Kj/ (Kg . ºC))
p = density of air at temperature To (Kg/ m³)

Solution:
39,552 Watts = 990li/s x ∆T x 1.2
∆T = 39,552 Watts
990 Li/s x 1.2
∆T = 33.ºC

∆T = Ts - To
33 = Ts - To
Ts = 33 + (-5)
Ts = 28ºC

Therfore: Increase the Supply Air Temperature up to 30ºC minimum

∆T = 35ºC

The Heating Load of AHU coil


q = 990 x 35 x 1.2
q = 41,580 Watts
q = 35,755 Kcal/Hr
TECCENTER EST.
Proj: Al- Andalus University Project Electro-Mechanical Works
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building

Calculation for AHU-01 Heat Load capacity and Flow of Water


Serving BSMT & Ground Flr.

1.0 Calculation for Heat Load capacity of Fresh Air


Given:
Q.= 1,430 l/s
Tr = 20ºC
To = -5ºC
cp = 1Kj/ Kg . ºC
p = 1.2 Kg/ m³

Where:
qs = Q x ∆T x cp x p
qs = Heat Loat Total (Watts)
Q. = Supply air capacity (Li/s)
∆T = Temperature difference (ºC)
Tr = Room Temperature (ºC)
To = Ambient Temperature (ºC)
cp = specific heat of air (Kj/ (Kg . ºC))
p = density of air at temperature To (Kg/ m³)

Solution:
qs = 1,430li/s x ((20 - (-5)ºC) x 1.2
qs = 42,900 Watts

Total Heat Load of AHU-01 including the load for Stair and Hallway
qt = 42,900 + 1,255 + 3,274 + 796
qt = 48,225 Watts

qt = 48,225 W x 3,413 Btu/Hr


1Kw / 1000 W
qt = 164,592 Btu/Hr
qt = 41,470 Kcal/Hr

2.0 For Flow of Water by Tredgold definition of BTU.


Given:
Q.= 164,592 Btu/Hr
∆T = 20ºF
p = 8.33 Gals/ºF

Where:
Fw = Q / ∆T x p
Fw = Flow of Water (Gpm)
Q. = Heat Load Total (Btu/hr)
∆T = Water Supply and ReturnTemperature difference (ºF)
p = The weight gallon of water (gal/ ºF)

Solution:
Fw = 8.33 gals/ ºF x 20ºF
Fw = 166.6 Gals
Fw = 164,592 Btu/hr
166.6 gals x 60 min /hr
Fw = 16.4 gals/min
Fw = 1.24 l/s
TECCENTER EST.
Proj: Al- Andalus University Project Electro-Mechanical Works
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building

3.0 For the Temperature of Air Supply from AHU-01.


Given:
Q.= 1,430 l/s
Tr = 20ºC
To = -5ºC
cp = 1Kj/ Kg . ºC
p = 1.2 Kg/ m³

Where:
qs = Q x ∆T x cp x p
qs = Heat Loat Total (Watts)
Q. = Supply air capacity (Li/s)
∆T = Temperature difference (ºC)
cp = specific heat of air (Kj/ (Kg . ºC))
p = density of air at temperature To (Kg/ m³)

Solution:
48,225 Watts = 1,430li/s x ∆T x 1.2
∆T = 48,225 Watts
1,430Li/s x 1.2
∆T = 28ºC

∆T = Ts - To
28 = Ts - To
Ts = 28 + (-5)
Ts = 23ºC

Therfore: Increase the Supply Air Temperature up to 30ºC minimum

∆T = 35ºC

The Heating Load of AHU coil


q = 1430 x 35 x 1.2
q = 60,060 Watts
q = 51,646 Kcal/Hr