IECEx OD504 Ed3.0
IECEx OD504 Ed3.0
IECEx
OPERATIONAL DOCUMENT
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in
any form or by any means, electronic or mechanical, including photocopying and microfilm, without permission
in writing from either IEC or IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this
publication, please contact the address below or your local IEC member National Committee for further
information.
Useful links:
IECEx OD 504
05 Edition 3.0, 2014-09
IECEx
OPERATIONAL DOCUMENT
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
IECEx OD 504 © IEC:2014(E) –1–
CONTENTS
Annex B (informative) Items in a knowledge test to cover all aspects of each Unit
of Competence ............................................................................................................... 60
Bibliography ................................................................................................................... 60
Table 4.1 – List of Units of Competence ......................................................................... 13
Table A.1 – Summary of prerequisite units and recommended general competence ....... 59
–4– IECEx OD 504 © IEC:2014(E)
This Operational Document, OD 504 sets out the competence requirements for personnel
working with electrical equipment for explosive atmospheres according to IEC International
Standards. Its purpose is to support certification where competence is required, e.g. Repair and
Overhaul Service Facilities, and may be considered for Certification of Persons undertaking the
work in various aspects of explosive atmospheres where it may be advantageous to maintain
competence certification.
Document History
Date Summary
October 2009 Original issue (Edition 1.0)
April 2013 Edition 2.0
September 2014 Edition 3.0 to incorporate details of Ex 000
and the changes to other Modules to
accommodate the introduction of Ex 000
Address:
IECEx Secretariat
Level 33, Australia Square
264 George Street
Sydney NSW 2000
Australia
Contact Details:
Tel: +61 2 4628 4690
e-mail: [email protected]
http://www.iecex.com
IECEx OD 504 © IEC:2014(E) –5–
INTRODUCTION
The objective of this IECEx Operational Document is to set out the generic cross-industry
competence requirements for work associated with electrical equipment in hazardous areas.
These requirements are intended for use by any industry sector or enterprise with regards to
explosion-protection related to the relevant functional areas.
The procedures, systems and methods of assessment as set out in this document are to be
followed in assessing an application for competence for carrying out work associated with
explosive atmospheres and Ex equipment.
This document sets out the specification for the IECEx Units of Competence, according to the
application of IEC Standards. Also included are requirements for competence evaluation.
–6– IECEx OD 504 © IEC:2014(E)
FOREWORD
The Basic Knowledge Unit 000 covers the safety obligation of person entering a hazardous area, and
demonstrates the person has an understanding of the nature of the risks associated with hazardous
areas, limitations on devices that may be taken into a hazardous area and the occupational health and
safety responsibilities and procedures related to hazardous areas
Concerns with the variability in skills of electrical workers and others dealing with equipment in
hazardous areas has led to the development of these standards of Skills in basic knowledge
and Competence for persons entering sites and or working on electrical equipment for use in
explosive atmospheres. Although training has been available, it was usually confined to the
technical aspects and there is generally no strategy to provide this specific assessment of
competence.
The concern over competence is heightened by the trend away from prescriptive regulations
towards performance-based regulations. The performance-based approach places the ‘duty of
care’ responsibilities on enterprises and individuals, which, in turn, is said to promote self-
monitored quality assurance. This results in greater compliance with requirements than is the
case with the inspectoral methods that accompany prescriptive regulations.
Since the early 1990s industries have expressed the need for an internationally structured
qualification system for identification of Competence to be used by any industry sector or
enterprise, with regards to explosion-protected equipment for explosive atmospheres.
IECEx OD 504 © IEC:2014(E) –7–
2 Normative references
The following publications contain provisions, which, through reference in this text, constitute
provisions of this Operational Document. At the time of publication, the editions indicated were
valid. The Ex Management Committee shall decide the timetable for the introduction of revised
editions of the publications.
IEC 60050-426, International Electrotechnical Vocabulary – Part 426: Equipment for explosive
atmospheres
IEC 61241, Electrical apparatus for use in the presence of combustible dust
For the definitions of any other terms, particularly those of a more general nature, reference
should be made to IEC 60050-426 or other appropriate parts of the IEV (International
Electrotechnical Vocabulary).
3.1
Actions to limit risk of an explosion
organizational arrangements for rectifying defects, shutting down plant or machinery under
emergency conditions, evacuating a hazardous area, reporting defects and conditions of plant
and machinery, monitoring the hazardous area for presence of an explosive atmosphere and
meeting Occupational Health & Safety (OH&S) obligations.
3.2
Appropriate personnel
the person who is the recipient of the output provided by a Competent person.
NOTE Examples of appropriate personnel are Site Managers, Project Managers, Line Managers, Maintenance
managers, Supervisors and Team Leaders etc.
3.3
Approved, approval
with the approval of, acceptable to the authority having jurisdiction.
3.4
Assessment of competence
the process of checking and confirming the ability to carry out specific work activities and/or
functions based on evidence that shows a person can carry out such work safely and to stated
requirements.
3.5
Authority, regulatory
a government agency responsible for relevant legislation and its application.
3.6
Certification
procedure by which a third party gives written assurance that a product, process or service
conforms to specified requirements.
3.7
Classification of explosive atmospheres
a method of analysing and classifying the environment where an explosive atmosphere may
occur to allow the proper selection of equipment, particularly electrical equipment, to be
installed and used safely in that environment.
3.8
competence
ability to apply knowledge and skills to achieve intended results [ISO/IEC 17024:2012, 3.6].
NOTE The concept of competence focuses on what is expected of an employee in the workplace rather than on the
learning process, and embodies the ability to transfer and apply skills and knowledge to new situations and
environments.
3.9
Ex Competent Person
person who can demonstrate a combination of knowledge and skills to effectively, efficiently
and safely carry out activities in or associated with hazardous areas, covered by IECEx
requirements.
NOTE Competence is specified by activity (e.g. classification, selection of equipment, installation, maintenance,
testing and inspection, etc.) and may be limited by types of protection, product types, groups etc. as detailed in
IECEx OD 502.
3.10
Competence, Unit of
the competence required for a useful work function and which resides with an individual.
IECEx OD 504 © IEC:2014(E) –9–
3.11
Basic Knowledge, Unit of
the basic knowledge required by an individual for entering a Hazardous Area.
3.12
Defects
visual damage or corrosion of the explosion-protection aspect of the installation or apparatus.
3.13
Equipment marking
information with regards to certification that is required to be marked on each item of equipment
incorporating an explosion-protection technique.
3.14
equipment protection level
EPL
level of protection assigned to equipment based on its likelihood of becoming a source of
ignition and distinguishing the differences between explosive gas atmospheres, explosive dust
atmospheres, and the explosive atmospheres in mines susceptible to firedamp.
3.15
Established procedures
formal arrangements of an organization, enterprise or statutory authority of how work is to be
done and by whom.
NOTE Examples of established procedures are documented in quality management systems, safety management
systems, work clearance systems, work instructions, reporting systems and arrangements for dealing with
emergencies.
3.16
Explosion properties of hazardous materials
there are two sets of properties:
a) for gases, vapours, flammable liquids and mists: vapour pressure; boiling point; flashpoint;
ignition temperature; explosive limits; relative vapour density; minimum ignition energy
b) for dusts: layer ignition temperature; cloud ignition temperature; minimum ignition energy
NOTE Explosive limits (lower/LEL and upper/UEL) and flammability limits (lower/LFL and upper/UFL) are deemed
to be synonymous. It should be recognized that some particular authorities having jurisdiction may have overriding
requirements that dictate the use of one of these sets of terms and not the other.
3.17
Explosion-protected equipment
equipment to which specific measures are applied to avoid ignition of a surrounding explosive
atmosphere.
NOTE The word ‘equipment’ includes ‘apparatus’, as mentioned in many relevant Standards.
3.18
Explosion-protection techniques
techniques applied to the design of electrical equipment, components and systems to prevent
the electrical energy from becoming an ignition source in the presence of flammable vapours
and gases or combustible dusts in explosive atmospheres.
NOTE Some of these techniques and also alternative techniques may be applied to the design of non-electrical
equipment for the avoidance of non-electrical ignition sources. These techniques are not yet standardised at
international level and are currently outside the scope of this document.
3.19
Group (of equipment for explosive atmospheres)
classification of electrical equipment related to the explosive atmosphere for which it is to be
used
NOTE 1 Equipment for use in explosive gas atmospheres is divided into two groups:
– Group I: Equipment for mines susceptible to firedamp; and
– Group II (which can be divided into subgroups IIA, IIB, IIC): Equipment for places with an explosive gas
atmosphere, other than mines susceptible to firedamp.
NOTE 2 This has also been known as ‘gas grouping’.
– Group III (which can be divided into subgroups IIA, IIB, IIC): Equipment for places with an explosive dust
atmosphere, other than mines susceptible to firedamp.
– 10 – IECEx OD 504 © IEC:2014(E)
3.20
Hazard and risk assessment
any recognized methodology of identifying hazards and assessing risks such as ‘hazard and
operability study’ (HAZOP) and ‘fault tree analysis’ (HAZAN).
3.21
Hazardous area
area in which an explosive atmosphere is present or may be expected to be present in quantities
such as to require special precautions for the construction, installation and use of electrical
equipment.
NOTE Explosive atmospheres may include a variety of adverse environmental conditions such as those
encountered in coal mines, shipping, oil/gas platforms and the like, which commonly require further specifications
stated in legislation or regulatory requirements.
3.22
Hazardous materials
in the context of this specification hazardous materials are flammable gases and vapours and
combustible dusts.
NOTE All vapours of flammable liquids are flammable vapours.
3.23
Inspection, close
an inspection which encompasses those aspects covered by a visual inspection and, in addition,
identifies those defects, such as loose bolts, which will be apparent only by the use of access
equipment, such as steps (where necessary) and tools. Close inspections do not normally
require the enclosure to be opened or the equipment to be de-energized.
3.24
Inspection, detailed
an inspection which encompasses those aspects covered by a close inspection and, in addition,
identifies those defects, such as loose terminations, which will only be apparent by opening the
enclosure, and using (where necessary) tools and test equipment.
3.25
Inspection, initial
an inspection of all electrical equipment, systems and installations before they are brought into
service.
3.26
Inspection, periodic
an inspection of all electrical equipment, systems and installations carried out on routine basis.
3.27
Inspection, sample
an inspection of a proportion of the electrical equipment, systems and installations.
3.28
Inspection, schedule
a formal arrangement for conducting inspections that details the extent, grade and frequency
of the inspections and the explosion-protected characteristics and compliances to be checked.
3.29
Inspection, visual
an inspection which identifies, without the use of access equipment or tools, those defects,
such as missing bolts, which will be apparent to the eye.
3.30
Inspector, actions taken by an
actions taken by an inspector in relation to defects, non-conformities, faults in a hazardous area
installation.
NOTE Examples of such actions are: disconnection or non-connection of supply until a defect or fault or non-
conformity is rectified, notice of period in which it has to be rectified, other actions within the scope of statutory
regulations.
IECEx OD 504 © IEC:2014(E) – 11 –
3.31
Installation
in the context of this specification an installation includes explosion-protected equipment, wiring
and other required items as they are fixed in place and connected as necessary, to operate as
intended.
3.32
Integrity (of explosion-protected equipment)
aspects of the equipment design and use that afford explosion-protection.
3.33
Non-conformance
equipment that does not satisfy the applicable Standards or requirements.
3.34
OH&S (Occupational Health and Safety) policies and procedures
arrangements of an organization or enterprise to meet its legal and ethical obligations of
ensuring the workplace is safe and without risk to health.
NOTE Ensuring a workplace is safe will include hazard identification and risk assessment mechanisms,
implementation of safety regulations, safety training, safety systems incorporating work clearance procedures,
isolation procedures, use of protective equipment and clothing and use of codes of practice.
3.35
Other items
items that are not in themselves explosion-protected but have an influence on the integrity of
the explosion-protection technique used. For example, an overload device for a motor or
associated apparatus in the case of the increased safety technique Ex ‘e’.
3.36
Pre-commission testing
tests specified, such as, performance and setting of protection devices and systems, earth loop
impedance, insulation resistance, and earth continuity equipment connection and operation
tests at no load.
3.37
Process specialist personnel
responsible persons with expertise in the technical aspects that relate to explosive hazards and
include chemical engineers, process engineers, mining engineers, safety managers, and the
like.
3.38
Re-certification/Supplementary approval
submission of previously certified/approved equipment/personnel to an accredited certification
body or authority, to determine whether the equipment/personnel continue to comply with the
relevant requirements.
3.39
Requirements
those to which equipment and procedures and their outcomes shall conform and include
statutory obligations and regulations and Standards called-up by legislation or regulations.
NOTE Requirements may include codes of practice, job specifications, Standards called up in specifications,
procedures and work instructions and quality management systems.
3.40
Scope Limitation
where personnel demonstrate competence relevant to a Unit of Competence for specific aspect
that may relate to the Explosion protection technique, Product Type, Group, Voltage etc. Any
scope limitation of a Unit of Competence is shown in the scope of the certificate.
NOTE The available scope limitations are given in OD 502.
3.41
Servicing
maintaining, fault finding and repair of equipment, plant machinery and installations.
– 12 – IECEx OD 504 © IEC:2014(E)
3.42
Special tools, equipment and testing devices
tools for the removal of enclosure covers and connecting conductors, measuring devices such
as feeler gauges and micrometer, gas and vapour sensors, electrical testing devices approved
for use in a particular hazardous area.
3.43
Specifications
all those attributes that define accurately the nature of the involved hazards, materials/products,
processes, equipment and installation design
NOTE Examples of specifications are design and manufacturer's specifications defining all the necessary
parameters and tolerances, process flow diagrams, explosive characteristics and technical data sheets for hazardous
materials and products, and the like.
3.44
Standards
technical documents which set out specifications and other criteria for equipment, materials and
methods, to ensure they consistently perform as intended. The Standards referred to in this
specification are those published by International Electrotechnical Commission.
3.45
Temperature classification
system of classification by which electrical equipment is allocated one of six temperature
classes according to its maximum surface temperature.
3.46
Verification dossier
a set of documents showing the compliance of electrical equipment and installations
NOTE The information in a ‘Verification Dossier’ is subject to audit under a formal inspection process.
3.47
Wiring system
permitted wiring and accessories for power, measurement, control or communications
purposes.
3.48
Zones, hazardous
the zones into which explosive atmospheres are classified based upon the frequency of the
appearance and duration of an explosive atmosphere.
3.49
Zones in explosive gas atmospheres
see IEC 60079-10-1 for the definitions of Zones 0, 1 and 2.
3.50
Zones in explosive dusts atmospheres
see IEC 60079-10-2 for the definitions of Zones 20, 21 and 22.
4 Units of Competence
4.1 Scope
This Section describes the Units of Competence for working with electrical equipment for
explosive atmospheres and to ensure the risk of any explosion hazard in such areas has been
minimized. The specific Units of Competence are described in detail in Clauses 4.2 to 4.12 and
a list of such Units is shown in Table 4.1.
It is likely that multiple Units of Competence will be assessed and under these circumstances,
where the elements of the ‘Evidence guide – Critical aspects of evidence it’ are repeated in
each unit, is not expected that the assessment requires any of the elements to be repeated. A
table showing the cross reference of these repeated elements is give in Section 6.
IECEx OD 504 © IEC:2014(E) – 13 –
a)
Reference Title Scope limitation
Unit Ex 000 – Basic knowledge and awareness to enter a site that includes a classified Not applicable
hazardous area.
Unit Ex 001 – Apply basic principles of protection in explosive atmospheres 1
Unit Ex 002 – Perform classification of hazardous areas 3
Unit Ex 003 – Install explosion-protected equipment and wiring systems 1, 2, 3, 4
Unit Ex 004 – Maintain equipment in explosive atmospheres 1, 2, 3, 4
Unit Ex 005 – Overhaul and repair of explosion-protected equipment 1, 2, 3, 4
Unit Ex 006 – Test electrical installations in or associated with explosive atmospheres 1, 3, 4
Unit Ex 007 – Perform visual and close inspection of electrical installations in or 3, 4
associated with explosive atmospheres
Unit Ex 008 – Perform detailed inspection of electrical installations in or associated with 1, 3, 4
explosive atmospheres
Unit Ex 009 – Design electrical installations in or associated with explosive atmospheres 1, 3, 4
Unit Ex 010 – Perform audit inspection of electrical installations in or associated with 3
explosive atmospheres
a)
Limitation by:
1. Explosion-protection technique or
2. Product Type
3. Group
4. Voltage
– 14 – IECEx OD 504 © IEC:2014(E)
4.2 Unit Ex 000 – Basic knowledge and awareness to enter a site that includes
a classified hazardous area
Scope
This Unit of Knowledge covers the safety obligations and minimum basic knowledge of persons
entering a site that has classified hazardous areas. It requires an understanding of the nature
of hazardous areas, limitations on devices that may be taken into a hazardous area and the
occupational health and safety responsibilities and procedures related to hazardous areas.
This unit does not include requirements for ensuring the explosion protection aspects of plant
and machinery.
Note. This unit covers the hazardous area aspects of occupational health and safety (OHS) and does not negate the
other competencies required for general and functional OHS.
Prerequisites
Typically this unit would be used in relation to any job function that may be performed in or
associated with hazardous area and does not require any prerequisites.
Scope limitations
Scope limitations are not applicable to Unit Ex 000 (refer Table 4.1).
Prerequisites
There is no minimum level of technical education applicable for this unit of Competence.
Competence in this unit shall be assessed in combination with, or after gaining other
competence required by a given industry or enterprise for plant or machinery operation or
installations, maintenance or service functions. (see Annex A).
NOTE Annex A sets out the specific prerequisite Units and the recommended general competence and level
assumed to be held by a person before undertaking assessment to achieve a Unit of Competence.
Elements and performance criteria
Elements Performance criteria Critical aspects of evidence
1.1 Prepare to work in 1.1.1 Nature of the explosion hazard in the area
hazardous area and risks are known and the status of the Following work permits and
explosion hazard is ascertained through clearance procedures.
established procedures.
1.1.2 Operation and condition of plant and Following work permits and
machinery, with regards to explosion- clearance procedure.
protection, is ascertained through Correctly operating plant and
established procedures. machinery.
1.1.3 Established procedures for use of the
plant and machinery, with regards to Correctly operating plant and
explosion-protection techniques used in machinery.
the area, are followed.
1.2 Observe condition of 1.2.1 OH&S policies and procedures, with
Following work permits and
explosion-protection regards to explosion-protection, are
clearance procedures.
system area followed.
1.2.2 Performance of plant and machinery is
Monitoring hazards and
monitored to identify faults that may affect
following evacuation
the integrity of the explosion-protected
procedures.
equipment and wiring system.
1.2.3 Observations of explosion-protected
equipment and wiring are made during
Identifying visual damage or
normal operations and visual and audible
deterioration of explosion-
non-conformances that may affect the
protected equipment.
integrity of the explosion-protection
technique are identified.
1.2.4 Explosion hazard monitoring equipment is
Monitoring hazards and
observed and a dangerous state of the
following evacuation
hazard is identified (e.g. by using gas
procedures.
detectors).
1.3 Take actions to limit 1.3.1 Variations outside normal operating
risk of an explosion conditions are reported and documented
in accordance with established
procedures.
1.3.2 Established procedures are followed in
the event of a potential or immediate
hazardous condition arising from any non- Following plant and electrical
conformance identified in isolation procedures.
equipment/wiring or changes in the
explosion hazard to a dangerous state.
– 16 – IECEx OD 504 © IEC:2014(E)
Scope limitations
Scope limitations by Explosion protection technique are applicable to Unit Ex 001 (refer Table
4.1).
This unit of competence is based on IEC 60079-10-1 and IEC 60079-10-2 and any other relevant
standard that apply to this Unit of Competence.
Prerequisites
Competence in this unit requires a degree, diploma or equivalent in a technical subject.
The area classification should be carried out by those who understand the relevance and
significance of properties of flammable materials and those who are familiar with the process
and the equipment along with safety, electrical, mechanical and other qualified engineering
personnel.
IECEx OD 504 © IEC:2014(E) – 17 –
2.1 Determine the type 2.1.1 Functions and process equipment in the Accessing necessary
and extent of area are determined and hazardous information and identifying
explosion hazard materials identified from specifications, hazardous products involved
hazard and risk and/or written in a given process, explosive
consultation with process specialist properties of materials
personnel. involved in a given process,
and potential sources and
characteristics of release of
hazardous products.
2.1.2 Explosion and physical properties of
hazardous materials are listed, together
with the title of the authority from which
the data is obtained.
2.1.3 Gas groupings and temperature class of
flammable gases, vapours and/or dusts
that may be present in the area are
established from collected data.
2.1.4 Potential sources of release and/or
dusts layering are identified from
Analysing data in the context
specifications, and/or written
of explosion risk.
consultation with process specialist
personnel.
2.2 Establish the type 2.2.1 Zones are determined by similarity to Determining area delineation
and extent of zones examples in Standards or from first and documenting area
principles. classifications.
2.2.2 Where first principles are used, grades,
sources and magnitude of release and
dusts layering are established from
specifications and diagrams and
reviewed with process specialist
personnel.
2.3 Document 2.3.1 Area classification documentation is
classification and completed in accordance with
delineation of zones requirements and submitted to
appropriate personnel.
2.3.2 Classification documentation records
are filed for future reference and for
incorporation in the verification dossier.
Scope limitations
Scope limitations by Group are applicable to Unit Ex 002 (refer Table 4.1).
This unit of competence is based on IEC 60079-14 and any other relevant standard that apply
to this Unit of Competence.
Prerequisites
The applicant shall have the level of technical education (or equivalent) attained, relevant to
the application, through documents such as College Certificates and Vocational qualifications
etc.
3.2 Install the equipment 3.2.1 OH&S policies and procedures for Working safely in a
and wiring systems working in a hazardous area are hazardous area including, the
followed. use of work permits and
clearances, hazard
monitoring and evacuation
procedures, and plant and
electrical isolation.
3.2.2 Equipment is installed to conform with Handling and installing
design specifications, Standards and equipment and wiring in a
within the limits specified by the manner that does not reduce
equipment certification. the type of protection
afforded by the equipment
design.
Checking equipment against
certification documents
including conditions of
certification relating to the
safe use.
3.2.3 Equipment and wiring system Handling and installing
components are dismantled where equipment and wiring in a
necessary and parts stored to protect manner that does not reduce
them against loss or damage. the type of protection
afforded by the equipment
design.
3.2.4 Equipment and wiring are installed in Handling and installing
a manner that does not reduce the equipment and wiring in a
type of protection afforded by the manner that does not reduce
equipment design. the type of protection
afforded by the equipment
design.
3.2.5 Circuits are tested prior to connection
to devices to ensure resistance of
Testing installed
earthing is sufficiently low, installation
cables/circuits to ensure they
resistance is safe, polarity and
are safe.
connections are correct and each
circuit complies with requirements.
Scope limitations
Scope limitation by Explosion protection technique, Product Type, Group or Voltage are
applicable to Unit Ex 003 (refer Table 4.1). Any scope limitations shall be included in the
application according to OD 502.
– 20 – IECEx OD 504 © IEC:2014(E)
Competence in this unit shall be assessed either concurrently with or after Unit Ex 001 – Apply
basic principles of protection in explosive atmospheres (see Annex A). In addition, if the scope
limitation requires, the achievement of competence in developing and managing general
electrical/instrumentation maintenance programs will satisfy the prerequisite (see Annex A).
NOTE 2 For work on wiring and equipment operating above 1000 V a.c. or 1500 V d.c. competence in high voltage
switching and safe isolation should be held.
4.1 Prepare to carry out 4.1.1 OH&S policies and procedures for Working safely in a hazardous
maintenance preparing to work in a hazardous area in relation to, work permits
area are followed. and clearances, hazard
monitoring and evacuation
procedures, and plant and
electrical isolation. Following
established maintenance
procedures.
4.1.2 Area classification and details of
explosion-protected equipment and
wiring are ascertained from Following established
hazardous area layout drawings and maintenance procedures.
equipment certification documents
held in the verification dossier.
4.1.3 Extent of maintenance to be
conducted is established from the Following established
maintenance schedule and reports maintenance procedures.
held in the verification dossier.
4.1.4 Special tools, equipment and testing
devices needed to carry out the
Following established
maintenance work are obtained and
maintenance procedures.
checked for correct operation and
safety.
4.2 Carry out 4.2.1 OH&S policies and procedures for Working safely in a hazardous
maintenance working in a hazardous area are area in relation to, work permits
followed. and clearances, hazard
monitoring and evacuation
procedures, and plant and
electrical isolation. Following
established maintenance
procedures.
4.2.2 Work is carried out to planned
Following established
schedule to ensure all items are
maintenance procedures.
correctly maintained.
4.2.3 Equipment is checked and tested in
Identifying defects and faults.
accordance with established
Following established
procedures to determine whether it
maintenance procedures.
functions correctly, complies with
Applying relevant contingency
approval documentation and is not
management skills.
subject to deterioration or damage.
4.2.4 Equipment is adjusted or repaired Identifying defects and faults.
within the limits permitted by the Following established
equipment certification and in maintenance procedures.
accordance with manufacturers’ Applying relevant contingency
instructions. management skills.
4.2.5 Certification documentation for
replacement equipment is sighted to Following established
ensure that it is identical to the maintenance procedures.
equipment it replaces and is in Applying relevant contingency
accordance with the explosion- management skills.
protection system design.
– 22 – IECEx OD 504 © IEC:2014(E)
Scope limitations
Scope limitation by Explosion protection technique, Product Type, Group or Voltage are
applicable to Unit Ex 004 (refer Table 4.1). Any scope limitations shall be included in the
application according to OD 502.
This unit of competence is based on IEC 60079-19 and any other relevant standards that may
apply.
IECEx OD 504 © IEC:2014(E) – 25 –
Prerequisites
The applicant shall have the level of technical education (or equivalent) attained, relevant to
the application, through documents such as College Certificates and Trade Credentials etc.
For an operative a minimum 3 years experience in the overhaul and repair of general electrical,
electronic and/or mechanical equipment relevant to the scope of the unit of competence being
applied for taking into account the scope limitations.
For a responsible person a minimum 3 years experience in the servicing of Ex electrical,
electronic and/or mechanical equipment relevant to the scope of the unit of competence being
applied for taking into account the scope limitations.
Elements and performance criteria
4.7.3.1 Criteria for an operative
Elements Performance criteria Critical aspects of evidence
5.1 Prepare for 5.1.1 Equipment to be overhauled or repaired Identifying equipment from its
overhaul/repair of is identified by its markings and marking and certification
equipment certification documentation. documentation.
5.1.2 Specifications and instructions for the Confirming the expected
overhaul/repair work are received and outcomes of the
expected outcomes of the work overhaul/repair work.
confirmed with the responsible person*.
5.1.3 Special tools, equipment and testing Checked for correct
devices needed to carry out the operation, safety and
overhaul or repair work are obtained currency of calibration
and checked for correct operation, certification.
safety and currency of calibration
certification.
5.2 Carry out the 5.2.1 Specifications and instructions for the Following overhaul/repair
overhaul or repair overhaul/repair work are followed in specifications and
work accordance with established instructions.
procedures.
5.2.2 Replacement parts and components Identifying replacement parts
used in the overhaul or repair are and components as being
identified as being authorized by the authorized by the equipment
equipment manufacturer. manufacturer.
5.2.3 Overhaul/repair of equipment is done in Following overhaul/repair
a manner that does not reduce the type specifications and
of protection afforded by the equipment instructions.
design.
5.2.4 Quality checks are made to ensure that Using quality systems.
the overhaul/repair of the equipment
complies with the overhaul/repair
specifications and instruction.
5.3 Document 5.3.1 Overhaul/repair work carried out is Documenting overhaul/repair
overhaul/repair work documented in accordance with work.
established quality procedures.
5.3.2 The responsible person is notified of the Documenting overhaul/repair
completion of the work in accordance work.
with established quality procedures.
Scope limitations
The scope limitations will clearly state the Unit of Competence applies for either an Operative
or a Responsible person. Scope limitation by Explosion protection technique, Product Type,
Group or Voltage are applicable to Unit Ex 005 (refer Table 4.1). Any scope limitations shall be
included in the application according to OD 502.
Critical aspects of evidence for both operative and responsible person
Evidence of competence in this unit shall show:
a) Competent performance associated with each element by employing the techniques,
procedures, information and resources available in the workplace and encompassing the
following aspects for which competence is sought according to the Tables in 4.7.3.
IECEx OD 504 © IEC:2014(E) – 27 –
This unit of competence is based on IEC 60079-14 and any other relevant standards that may
apply.
Prerequisites
The applicant shall have the level of technical education (or equivalent) attained, relevant to
the application, through documents such as College Certificates and Trade Credentials etc.
Competence in this unit shall be assessed either concurrently with or after Unit Ex 001 – Apply
basic principles of protection in explosive atmospheres (see Annex A).
– 28 – IECEx OD 504 © IEC:2014(E)
NOTE For work on wiring and equipment operating above 1000 V a.c. or 1500 V d.c. competence in high voltage
switching and safe isolation should be held.
Scope limitations
The scope limitations will clearly state the Unit of Competence applies for either an Operative
or a Responsible person. Scope limitation by Explosion protection technique, Group or Voltage
are applicable to Unit Ex 006 (refer Table 4.1). Any scope limitations shall be included in the
application according to OD 502
Critical aspects of evidence
In addition to the requirements of 4.3.5 evidence of competence in this unit shall show:
4.9 Unit Ex 007 – Perform visual and close inspection of electrical installations
in or associated with explosive atmospheres
Scope
This Unit of Competence covers evaluating the completeness of a hazardous area verification
dossier and compliance of the explosion-protected aspects of the electrical installations within
the constraints of a visual or close inspection. It requires the ability to work safely in a hazardous
area, evaluate a verification dossier, identify explosion-protected equipment with their
certification and specified location, inspect an installation for compliance and report and act on
inspection results.
This unit of competence is based on IEC 60079-14 and IEC 60079-17 and any other relevant
standards that may apply.
Prerequisites
The applicant shall have the level of technical education (or equivalent) attained, relevant to
the application, through documents such as College Certificates and Trade Credentials etc
– 30 – IECEx OD 504 © IEC:2014(E)
Scope limitations
The scope limitations will clearly state the Unit of Competence applies for either an Operative
or a Responsible person. Scope limitation by Group or Voltage are applicable to Unit Ex 007
(refer Table 4.1). Any scope limitations shall be included in the application according to OD
502.
Critical aspects of evidence
In addition to the requirements of 4.3.5 evidence of competence in this unit shall show:
This unit of competence is based on IEC 60079-14 and IEC 60079-17 and any other relevant
standards that may apply.
– 32 – IECEx OD 504 © IEC:2014(E)
Prerequisites
The applicant shall have the level of technical education (or equivalent) attained, relevant to
the application, through documents such as College Certificates and Trade Credentials etc.
8.4 Prepare for 8.4.1 Type of inspection is ascertained from the Determining the extent of the
inspection inspection schedule retained in the inspection and location of
verification dossier. equipment.
8.5 Report inspection 8.5.1 Where applicable, a non-conformance Documenting inspection
results report, including the actions taken and a outcomes.
statement on whether circuits have been
re-energized, is made and forwarded to
the appropriate personnel.
8.5.2 Documentation in relation to all aspects of
the inspection forwarded to the
Documenting inspection
appropriate personnel for inclusion in the
outcomes.
verification dossier in accordance with
requirements.
Scope limitations
The scope limitations will clearly state the Unit of Competence applies for either an Operative
or a Responsible person. Scope limitation by Explosion protection technique, Group or Voltage
are applicable to Unit Ex 008 (refer Table 4.1). Any scope limitations shall be included in the
application according to OD 502.
Critical aspects of evidence
In addition to the requirements of 4.3.5 evidence of competence in this unit shall show:
This unit of competence is based on IEC 60079-14 and any other relevant standards that may
apply.
Prerequisites
The applicant shall have the level of technical education (or equivalent) attained, relevant to
the application, through documents such as Degree, Diploma and College Certificates etc
Competence in this unit shall be assessed either concurrently with or after Unit Ex 001 – Apply
basic principles of protection in explosive atmospheres (see Annex A).
9.1 Establish design 9.1.1 Site and plant specifications are Accessing and interpreting
brief obtained and reviewed to establish the relevant information
system requirements.
9.1.2 Classification of the area is obtained Accessing and interpreting
from the hazardous area layout drawings relevant information
or other classification documents.
9.1.3 Organizational policies and Accessing and interpreting
specifications for hazardous area relevant information
electrical systems are obtained or
established with the appropriate
personnel.
9.2 Design system and 9.2.1 Safety, functional and economic Providing design options and
installation considerations are incorporated in justifications including hazard
system design. risk, functionality and
economic considerations.
9.2.2 Design complies with all hazardous area Providing design options and
requirements and includes specifications justifications including hazard
and all other necessary documentation risk, functionality and
for explosion-protected equipment, economic considerations.
accessories and wiring systems.
9.3 Check and finalise 9.3.1 Design is checked under established Following checking and
design procedures for compliance with all documentation procedures.
relevant requirements.
9.3.2 Design is submitted for appropriate Following checking and
organizational approval and, where documentation procedures.
applicable, statutory or regulatory
approval.
9.3.3 Approved copies of design documents Following checking and
are issued for retention in the documentation procedures.
verification dossier, in accordance with
established procedures and
requirements.
Scope limitations
The scope limitations will clearly state the Unit of Competence applies for either an Operative
or a Responsible person. Scope limitation by Explosion protection technique, Group or Voltage
IECEx OD 504 © IEC:2014(E) – 35 –
are applicable to Unit Ex 009 (refer Table 4.1). Any scope limitations shall be included in the
application according to OD 502.
This unit of competence is based on IEC 60079-14 and IEC 60079-17 and any other relevant
standards that may apply.
Prerequisites
The applicant shall have the level of technical education (or equivalent) attained, relevant to
the application, through documents such as Degree, Diploma, College Certificates, Trade
Credentials etcetera.
– 36 – IECEx OD 504 © IEC:2014(E)
Competence in this unit shall be assessed either concurrently with or after Units Ex 002, Ex
008 and Ex 009.
10.1 Audit hazardous area 10.1.1 Records system (verification dossier) is Reviewing hazardous area
documentation reviewed to verify that essential documentation and
(verification dossier) hazardous area documentation is identifying the extent of the
and prepare to audit retained and procedures for maintaining audit.
as-built installation records are established. Handling and installing
equipment and wiring in a
manner that does not
reduce the type of
protection afforded by the
equipment design.
10.1.2 Hazardous area classification and Reviewing hazardous area
design drawings and documentation are documentation and
checked to verify that appropriate identifying the extent of the
procedures have been followed and are audit.
checked for traceability and Handling and installing
authentication. equipment and wiring in a
manner that does not
reduce the type of
protection afforded by the
equipment design.
10.1.3 Type and intended location of each item
of equipment and circuits subject to
audit are determined from design
drawings and documentation.
10.1.4 OH&S policies and procedures for Working safely in a
preparing to work in a hazardous area hazardous area in relation
are followed. to work permits and
clearances, hazard
monitoring and evacuation
procedures, and plant and
electrical isolation.
10.1.5 Appropriately qualified persons are Engaging and directing
engaged to assist in aspects of the audit appropriately qualified
process. persons as required.
10.1.6 Special tools, equipment and devices
needed for the inspection are obtained
and checked for correct operation and
safety.
10.2 Conduct audit 10.2.1 OH&S policies and procedures for Working safely in a
working in a hazardous area are hazardous area in relation
followed. to work permits and
clearances, hazard
monitoring and evacuation
procedures, and plant and
electrical isolation.
10.2.2 Parts of equipment that are dismantled
Conducting audit to
in order to conduct inspection are
industry Standards.
protected against loss or damage.
10.2.3 Appropriate qualified persons are
directed to access components of the Conducting audit to
installation as required to audit the industry Standards.
installation.
10.2.4 Equipment, systems and installations
are inspected for compliance with the
design specifications retained in the
hazardous areas documentation
(verification dossier) and in accordance
IECEx OD 504 © IEC:2014(E) – 37 –
Scope limitations
The scope limitations will clearly state the Unit of Competence applies for either an Operative
or a Responsible person. Scope limitation by Group is applicable to Unit Ex 010 (refer Table
4.1). Any scope limitations shall be included in the application according to OD 502.
AUTHOR NOTE: The highlighting of text above in 5.1 (a) iii) and following indicates a reduced
requirement for the Ex 005 Overhaul and Repair of explosion protected equipment Competence
Unit. Refer to Section 6 for more a summary of reduced requirements for Ex 005 details
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the flameproof (Ex ‘d’) technique.
NOTE Examples of characteristics and design features are flame paths, integrity under pressure, pressure
piling, and enclosure entries.
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Increased safety (Ex ‘e’) technique.
NOTE Examples of characteristics and design features are temperature rise, maximum power dissipation,
protection devices, certified components, creepage and clearance distances, absence of sparking contacts and
enclosure entries.
c) Actions or conditions that would void the protection provided by the Increased safety
technique.
d) The use of Standards in determining the requirements to which the design of the Increased
safety explosion-protected apparatus shall comply.
5.11 Type of protection ‘n’ (Ex ‘n’)
Evidence shall show an understanding of the characteristics and application of Type of
protection ‘n’ (Ex ‘n’) explosion-protection technique to an extent indicated by:
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Type of protection ‘n’ (Ex ‘n’) technique.
NOTE Examples of characteristics and design features are creepage and clearance distances and restricted
breathing.
b) Typical situations where the Type of protection ‘n’ explosion-protection technique is used.
c) Actions or conditions that would void the protection provided by the Type of protection ‘n’
technique.
d) The use of Standards in determining the requirements to which the design of the Type of
protection ‘n’ explosion-protected apparatus shall comply.
5.12 Encapsulation (Ex ‘m’) explosion-protection technique
Evidence shall show an understanding of the characteristics and application of Encapsulation
(Ex ‘m’) explosion-protection technique to an extent indicated by:
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Encapsulation (Ex ‘m’) technique.
NOTE An example of characteristics and design features is solenoid valve.
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Oil Immersion (Ex ‘o’) technique.
NOTE An example of characteristics and design features are transformers.
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Powder Filled (Ex ‘q’) technique.
NOTE An example of characteristics and design features is a capacitor used with a luminaire.
b) Typical situations where the Powder filled explosion-protection technique are used.
c) Actions or conditions that would void the protection provided by the Powder Filled technique.
– 44 – IECEx OD 504 © IEC:2014(E)
d) The use of Standards in determining the requirements to which the design of the Powder
Filled explosion-protected apparatus shall comply.
5.15 Intrinsic safety (Ex ‘i’) explosion-protection technique
Evidence shall show an understanding of the characteristics and application of Intrinsic safety
(Ex ‘i’) explosion-protection technique to an extent indicated by:
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Intrinsic safety (Ex ‘i’) technique.
NOTE Examples of characteristics and design features are field devices, cables, safe area devices, earthing,
entity versus integrated system concept, simple devices and interface devices and their parameters,
segregation, infallible components, current and voltage limiting, creepage and clearance distances.
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Pressurization (Ex ‘p’) technique.
NOTE Examples of characteristics and design features are exclusion and dilution, purge periods, controlled
shut down, monitoring and sources of internal release.
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the techniques for dusts.
b) Typical situations where dust explosion-protection technique is used.
c) Actions or conditions that would void the protection provided by protection by enclosure
technique.
d) The use of Standards in determining the requirements to which the design of the dust
explosion-protected enclosure shall comply.
5.18 Intrinsic safety (Ex ‘iD’) explosion-protection technique
Evidence shall show an understanding of the characteristics and application of Intrinsic safety
(Ex ‘iD’) explosion-protection technique to an extent indicated by:
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Intrinsic safety (Ex ‘iD’) technique.
NOTE Examples of characteristics and design features are field devices, cables, safe area devices, earthing,
entity versus integrated system concept, simple devices and interface devices and their parameters,
segregation, infallible components, current and voltage limiting, creepage and clearance distances.
d) The use of Standards in determining the requirements to which the design of the Intrinsic
safety explosion-protected apparatus shall comply.
5.19 Pressurization (Ex ‘pD’) explosion-protection technique
Evidence shall show an understanding of the characteristics and application of Pressurization
(Ex ‘pD’) explosion-protection technique to an extent indicated by:
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Pressurization (Ex ‘pD’) technique.
NOTE Examples of characteristics and design features are exclusion and dilution, purge periods, controlled
shut down, monitoring and sources of internal release.
a) The purpose and characteristics of the design features of apparatus and circuits protected
by the Encapsulation (Ex ‘m’) technique.
NOTE An example of characteristics and design features is solenoid valve.
a) The scope and limitations for overhaul and repair of explosion-protected equipment
encompassing:
i) the requirements for compliance of a workshop;
ii) the requirements of a ‘competent person’ for a registered workshop engaged in the
overhaul/repair of explosion-protected equipment; and
iii) the scope and limitations of work permitted under workshop registration.
b) Overhaul and repair (technical) Standard encompassing:
i) the documentation/information required to enable overhauls/repairs to be undertaken;
ii) categories of work, for example, overhaul; no repair; overhaul-repair;
iii) modifications that are, and are not, permitted within the equipment certification; and
iv) the requirements for overhaul/repair processes relevant to the type of protection and
equipment.
c) Requirements for documentation and identification of overhauled/repaired explosion-
protected encompassing:
i) overhaul/repair report document; and
ii) requirements for distribution of overhaul/repair reports.
d) Quality management systems as covered by international Standards encompassing:
i) documentation regime of a quality management system;
ii) principle of document and data control covering both internally and externally generated
documents and data; and
iii) principles of process control as applied to the overhaul and repair of explosion-protected
equipment.
5.31 Explosion-protected equipment overhaul and repair specific to each technique
Evidence shall show an understanding of overhaul and repair for specific explosion-protection
techniques to an extent indicated by:
a) The use of Standards in determining the requirements to which the design of explosion-
protected apparatus shall comply.
b) The level of overhaul/repair required encompassing:
i) Standards and their use for determining the requirement for a specific explosion-
protection technique;
ii) measurement/tests and equipment required to determine whether an item of equipment
meets the certification requirements;
IECEx OD 504 © IEC:2014(E) – 49 –
a) Working safely in a potentially hazardous area in relation to work permits and clearances,
hazard monitoring and evacuation procedures, and plant and electrical isolation.
b) Handling and installing equipment and wiring in a manner that does not adversely affect the
type of protection afforded by the equipment design.
c) Conducting tests.
d) Documenting testing outcomes.
5.36 Explosive atmospheres visual and close inspection requirements
Evidence shall show an understanding of the purpose and process of visual and close
inspections to an extent indicated by:
a) Working safely in a potentially hazardous area in relation to work permits and clearances,
hazard monitoring and evacuation procedures, and plant and electrical isolation.
b) Inspecting equipment and wiring in a manner that does not adversely affect the type of
protection afforded by the equipment design.
c) Conducting visual inspections.
d) Documenting inspection outcomes.
5.38 Explosive atmospheres detailed inspection techniques
Evidence shall show an understanding of techniques used in inspecting installations of
explosion-protected and associated apparatus and hazardous area wiring. The following
aspects indicate the extent of understanding required:
a) The relationship between the documentation held in a verification dossier and the installed
equipment encompassing:
i) consistency between the location and type of equipment with the area classification
details in the verification dossier; and
ii) equipment certification and any attached conditions that relate to the equipment as it is
installed.
IECEx OD 504 © IEC:2014(E) – 51 –
a) Working safely in a potentially hazardous area in relation to work permits and clearances,
hazard monitoring and evacuation procedures, and plant and electrical isolation.
b) Handling and installing equipment and wiring in a manner that does not adversely affect the
type of protection afforded by the equipment design.
c) Conducting inspections.
d) Documenting inspection outcomes.
5.40 Explosive atmospheres installation planning
Evidence shall show an understanding of hazardous area electrical installations planning and
the selection of appropriate explosion-protected equipment and wiring. The following aspects
indicate the extent of understanding required:
i) authenticity of documentation;
ii) hazardous area delineations shown in site diagrams;
iii) location and operating parameters of equipment shown in certification documents;
iv) compliance of equipment location;
v) compliance of wiring systems; and
vi) alignment of hazardous area documentation to as- built installation.
c) Reporting non-conformance of an installation.
5.46 Hazardous area audit inspection work performance
In assessing competent hazardous area detail inspection work performance evidence regarding
the following aspects of competence shall be considered:
a) Working safely in a potentially hazardous area in relation to work permits and clearances,
hazard monitoring and evacuation procedures, and plant and electrical isolation.
b) Accessing and interpreting relevant information.
c) Handling and installing equipment and wiring in a manner that does not adversely affect the
type of protection afforded by the equipment design.
d) Conducting inspections.
e) Documenting inspection outcomes.
f) Interpreting area classification documentation.
g) Documenting area classification.
h) Selecting equipment for a given classified area.
i) Selecting wiring systems for a given classified area.
j) Checking equipment certification for suitability for a given classified area.
k) Following checking and documentation procedures.
6 Summary of essential knowledge and associated skills for each Unit of Competence
NOTE: the use of “X” in the Table below denotes applicability in full. The use of “R” in the Table below denotes reduced requirements for Ex 005 Repair
Competence Unit – the applicable reduced requirements are specified as highlighted text in Clauses 5.1 to 5.19 above as relevant.
repair of explosion-protected
installations in or associated
installations in or associated
installations in or associated
installations in or associated
installations in or associated
close inspection of electrical
principles of protection in
Unit Ex 001 – Apply basic
equipment in explosive
protected equipment and
inspection of electrical
inspection of electrical
Unit Ex 002 – Perform
hazardous area
wiring systems
atmospheres
equipment
areas
Essential knowledge and associated skills
repair of explosion-protected
installations in or associated
installations in or associated
installations in or associated
installations in or associated
installations in or associated
close inspection of electrical
principles of protection in
Unit Ex 001 – Apply basic
equipment in explosive
protected equipment and
inspection of electrical
inspection of electrical
Unit Ex 002 – Perform
hazardous area
wiring systems
atmospheres
equipment
areas
Essential knowledge and associated skills
repair of explosion-protected
installations in or associated
installations in or associated
installations in or associated
installations in or associated
installations in or associated
close inspection of electrical
principles of protection in
Unit Ex 001 – Apply basic
equipment in explosive
protected equipment and
inspection of electrical
inspection of electrical
Unit Ex 002 – Perform
hazardous area
wiring systems
atmospheres
equipment
areas
Essential knowledge and associated skills
performance
work performance
Hazardous area auditing processes
Hazardous area audit inspection work
Essential knowledge and associated skills
installations in or associated
with explosive atmospheres
installations in or associated
with explosive atmospheres
Annex A
(informative)
Table A1 shows the specific prerequisite units and the recommended trade or profession
general competence and level assumed to be held by a person before undertaking assessment
to achieve Units of Competence in this specification.
IECEx OD 504 © IEC:2014(E) – 59 –
Unit Ex 000 – Basic knowledge and awareness to enter a site which none nil
includes a classified hazardous area
Unit Ex 001 – Apply basic principles of protection in explosive none Competence in plant or machinery operation or installations, maintenance or
atmospheres service functions
Unit Ex 002 – Perform classification of hazardous areas none Competence in gathering and analysing technical data and using this data for
risk assessment
Unit Ex 003 – Install explosion-protected equipment and wiring systems Unit Ex 001 Competence in installation of electrical, electronic, instrumentation and/or
data communication equipment and wiring systems
Unit Ex 004 – Maintain equipment in explosive atmospheres Unit Ex 001 Competence in maintenance of industrial electrical, electronic,
instrumentation and/or data communication equipment and wiring systems
Unit Ex 005 – Overhaul and repair of explosion-protected equipment none Competence in overhaul and repair of industrial electrical/electronic
equipment
Unit Ex 006 – Test electrical installations in or associated with explosive Unit Ex 001 Competence in conducting testing of general electrical, electronic,
atmospheres instrumentation and/or data communication installations
Unit Ex 007 – Perform visual and close inspection of electrical Unit Ex 001 Competence in general electrical installation inspection are an alternative to
installations in or associated with explosive atmospheres the specific units listed in Column 2
Unit Ex 008 – Perform detailed inspection of electrical installations in or Unit Ex 001 Competence in general electrical installation inspection are an alternative to
associated with explosive atmospheres the specific units listed in Column 2
Unit Ex 009 – Design electrical installations in or associated with Unit Ex 001 Competence in designing electrical systems and installations
explosive atmospheres
Unit Ex 010 – Perform audit inspection of electrical installations in or Unit Ex 002, Competence in general electrical installation inspection are an alternative to
associated with explosive atmospheres Unit Ex 008 and the specific units listed in Column 2
Unit Ex 009
– 60 – IECEx OD 504 © IEC:2014(E)
Annex B
(informative)
Constructed Response C
2 3 2
5.28 Explosive atmospheres management
Bibliography
IEC 60079-2, Explosive atmospheres – Part 2: Equipment protection by pressurized enclosures ‘p’
IEC 60079-5, Explosive atmospheres – Part 5: Equipment protection by powder filling ‘q’
IEC 60079-6, Explosive atmospheres – Part 6: Equipment protection by oil immersion ‘o’
IEC 60079-7, Explosive atmospheres – Part 7: Equipment protection by increased safety ‘e’
IEC 60079-10-1, Explosive atmospheres – Part 10-1: Classification of areas – Explosive gas
atmospheres
IEC 60079-10-2, Explosive atmospheres – Part 10-2: Classification of areas – Combustible dust
atmospheres
IEC 60079-11, Explosive atmospheres – Part 11: Equipment protection by intrinsic safety ‘i’
IEC 60079-13, Explosive atmospheres – Part 13: Equipment protection by pressurized room ‘p’
IEC 60079-14, Explosive atmospheres – Part 14: Electrical installations, design, selection and erection
IEC 60079-15, Explosive atmospheres – Part 15: Equipment protection by type of protection ‘n’
IEC 60079-16, Electrical apparatus for explosive gas atmospheres – Part 16: Artificial ventilation for the
protection of analyzer(s) houses
IEC 60079-17, Explosive atmospheres – Part 17: Electrical installations inspection and maintenance
IEC 60079-18, Explosive atmospheres – Part 18: Equipment protection by encapsulation ‘m’
IEC 60079-19, Explosive atmospheres – Part 19: Equipment repair, overhaul and reclamation
IEC 60079-20-1, Explosive atmospheres – Part 20-1: Material characteristics for gas and vapour
classification – Test methods and data
IEC 60079-20-2, Electrical apparatus for explosive gas atmospheres – Part 20-2: Test methods and data
– Classification of combustible dust materials
IEC 60079-25, Explosive atmospheres – Part 25: Intrinsically safe electrical systems
IEC 60079-26, Explosive atmospheres – Part 26: Equipment with equipment protection level (EPL) Ga
IEC 60079-27, Electrical apparatus for explosive gas atmospheres – Part 27: Fieldbus intrinsically safe
concept (FISCO) and Fieldbus non-incendive concept (FNICO)
IEC 60079-28, Explosive atmospheres – Part 28: Protection of equipment and transmission systems
using optical radiation
IEC 60079-29-1, Explosive atmospheres – Part 29-1: Gas detectors – Performance requirements of
detectors for flammable gases
IEC 60079-29-2, Explosive atmospheres – Part 29-2: Gas detectors – Selection, installation, use and
maintenance of detectors for flammable gases and oxygen
IEC 60079-31, Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure ‘t’
IEC 60243-1, Electric strength of insulating materials – Test methods – Part 1: Tests at power
frequencies
IECEx OD 504 © IEC:2014(E) – 63 –
IEC 60332-1-2, Tests on electric and optical cables under fire conditions – Part 1-2: Test for vertical
flame propagation for a single insulated wire or cable-Procedure for 1 KW pre-mixed flame
IEC 60364 (all parts), Low-voltage electrical installations
IEC 60364-4-41, Low-voltage electrical installations – Part 4-41: Protection for safety –Protection against
electric shock
IEC 60529, Degrees of protection provided by enclosures (IP code)
IEC 60950 (all parts), Information technology equipment – Safety
IEC 61010-1, Safety requirements for electrical equipment for measurement, control, and laboratory use
– Part 1: General requirements
IEC 61241-2-1, Electrical apparatus for use in the presence of combustible dust – Part 2: Test methods
– Section 1: Methods for determining the minimum ignition temperatures of dust
IEC 61558-2-6, Safety of power transformers, power supply units and similar products for supply
voltages up to 1100 V – Part 2-6: Particular requirements and tests for safety isolating transformers
and power supply units incorporating safety isolating transformers
IEC 61892-7, Mobile and fixed offshore units – Electrical installations – Part 7: Hazardous areas
IEC 60092-502, Electrical installations in ships – Part 502: Tankers – Special features
IEC 60092-506, Electrical installations in ships – Part 506: Special Features – Ships carrying specific
dangerous goods and materials hazardous only in bulk
IEC 62305-3, Protection against lightning – Part 3: Physical damage to structures and life hazard
ISO 10807, Pipework – Corrugated flexible metallic hose assemblies for the protection of electric cables
in explosive atmospheres