LT & HT Panels Room

This document calculates the ventilation needs for high temperature (H.T.) and low temperature (L.T.) rooms. It determines the room volumes and required air changes per hour to calculate the ventilated air quantity for each room. It then selects appropriately sized wall-mounted axial fans with a static pressure of 0.5" W.G. to provide the necessary ventilation for each room.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views4 pages

LT & HT Panels Room

This document calculates the ventilation needs for high temperature (H.T.) and low temperature (L.T.) rooms. It determines the room volumes and required air changes per hour to calculate the ventilated air quantity for each room. It then selects appropriately sized wall-mounted axial fans with a static pressure of 0.5" W.G. to provide the necessary ventilation for each room.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

VENTILATION CALCULATION OF THE H.T & L.

T ROOMS

1- ASSUMPTIONS
Ambient temp. = 115 F
Acceptable Air Change/Hr = 10 times

2- CALCULATION
2.1 Ventilated Air Quantity for H.T Room (Room Ref. S/S-4)

Room Volume 331.7 Cu.M


11704.9 Cu.Ft

Where :-
Length L = 10.7 M
Width D = 6.2 M
Hight H = 5 M

Acceptable Air Change/Hr = 10 Times


THEN :-
Ventilated Air Quantity for H.T Room = 117049 Cu.Ft/Hr
= 1951 CFM

** Adopt Fan wall mounted axial type with Ext. Est. Static Pressure of 0.5 " W.G
Fan Capacity = 2000 CFM AND 1 KW

2.2 Ventilated Air Quantity for L.T Room (Room Ref. S/S-4)

Room Volume 278.2 Cu.M


9817.0 Cu.Ft

Where :-
Length L = 10.7 M
Width D = 5.2 M
Hight H = 5 M

Acceptable Air Change/Hr = 10 Times


THEN :-
Ventilated Air Quantity for H.T Room = 98170 Cu.Ft/Hr
= 1636 CFM

** Adopt Fan wall mounted axial type with Ext. Est. Static Pressure of 0.5 " W.G
Fan Capacity = 1600 CFM AND 1 KW
VENTILATION CALCULATION OF THE H.T & L.T ROOMS

1- ASSUMPTIONS
Ambient temp. = 115 F
Acceptable Air Change/Hr = 10 times

2- CALCULATION
2.1 Ventilated Air Quantity for H.T Room (Room Ref. S/S-1,5,6)

Room Volume 248 Cu.M


8751.3 Cu.Ft

Where :-
Length L = 8 M
Width D = 6.2 M
Hight H = 5 M

Acceptable Air Change/Hr = 10 Times


THEN :-
Ventilated Air Quantity for H.T Room = 87513 Cu.Ft/Hr
= 1459 CFM

** Adopt Fan wall mounted axial type with Ext. Est. Static Pressure of 0.5 " W.G
Fan Capacity = 1600 CFM AND 1 KW

2.2 Ventilated Air Quantity for L.T Room (Room Ref. S/S-1,5,6)

Room Volume 208 Cu.M


7339.8 Cu.Ft

Where :-
Length L = 8 M
Width D = 5.2 M
Hight H = 5 M

Acceptable Air Change/Hr = 10 Times


THEN :-
Ventilated Air Quantity for H.T Room = 73398 Cu.Ft/Hr
= 1223 CFM

** Adopt Fan wall mounted axial type with Ext. Est. Static Pressure of 0.5 " W.G
Fan Capacity = 1200 CFM AND 1 KW
VENTILATION CALCULATION OF THE H.T & L.T ROOMS

1- ASSUMPTIONS
Ambient temp. = 115 F
Acceptable Air Change/Hr = 10 times

2- CALCULATION
2.1 Ventilated Air Quantity for H.T Room (Room Ref. S/S-2,3)

Room Volume 126 Cu.M


4446.2 Cu.Ft

Where :-
Length L = 6 M
Width D = 6 M
Hight H = 3.5 M

Acceptable Air Change/Hr = 10 Times


THEN :-
Ventilated Air Quantity for H.T Room = 44462 Cu.Ft/Hr
= 741 CFM

** Adopt one Fan wall mounted axial type with Ext. Est. Static Pressure of 0.5 " W.G
Fan Capacity = 741 CFM AND 1 KW

2.2 Ventilated Air Quantity for L.T Room (Room Ref. S/S-2,3)

Room Volume 300 Cu.M


10586.3 Cu.Ft

Where :-
Length L = 8 M
Width D = 7.5 M
Hight H = 5 M

Acceptable Air Change/Hr = 10 Times


THEN :-
Ventilated Air Quantity for H.T Room = 105863 Cu.Ft/Hr
= 1764 CFM

** Adopt one Fan wall mounted axial type with Ext. Est. Static Pressure of 0.5 " W.G
Fan Capacity = 1764 CFM AND 1 KW