Kalani 1C PVC Cable

This document provides tables with information on current carrying capacity and voltage drop for single-core PVC insulated cables. Table A1 lists the current carrying capacity in amps for various cable cross-sectional areas, depending on installation methods and number of cables. Table A2 gives the voltage drop in mV/A/m for different cable configurations and cross-sectional areas. The tables can be used to select appropriate cable sizes based on current load and acceptable voltage drop.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
576 views2 pages

Kalani 1C PVC Cable

This document provides tables with information on current carrying capacity and voltage drop for single-core PVC insulated cables. Table A1 lists the current carrying capacity in amps for various cable cross-sectional areas, depending on installation methods and number of cables. Table A2 gives the voltage drop in mV/A/m for different cable configurations and cross-sectional areas. The tables can be used to select appropriate cable sizes based on current load and acceptable voltage drop.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

21

21 Current Carrying Capacity and Voltage Drop

SINGLE - CORE PVC INSULATED NON -ARMOURED

BS 6004/BS 6346

Ambient air temperature 30°C


Conductor operating temperature 70°C

PVC PVC Copper 0.310.5, 0.45/0.75, 0.6/1 kV

TABLE - A 1- Current carrying capacity

(Method F)
In free air or on a perforated cable tray
(Method A) (Method B) horizontal or vertical
Enclosed in conduit Enclosed in conduit (Method C)
In thermally on a wall, Clipped direct
insulating wall etc. .. or in trunking etc. .. Touching Spaced
Conduct by one diameter
or cross
sectional
area 2 Cables 3 or 4 2 Cables 3 or 4 2 Ca[,les 3 or 4 2 Cables 3 Cables 3 Cables 2 Cables
single cables single cables single cables single three three single phase ac or de
phase ac three phase ac three phase ac three phase ac
phase ac phase ac or 3 cables three
or de phase ac ordc phase ac or de flat phase ac or de
and flat and flat trefoi I phase ac flat
flat
touching touching
(mm 2) or trefoil. Horizontal Vertical
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
1 11 1.() .5 13.5 12 15.5 14 - - - - -
1.5 14.5 13.5 17.5 15.5 20 18 - - - - -
2.5 20 18 24 21 27 25 - - - - -
.4 26 24 32 28 37 33 - - - - -
6 34 31 41 36 47 43 - - - - -
10 46 42 57 50 65 59 - - - - -
16 61 56 76 68 87 79 - - - - -
25 80 73 101 89 114 104 131 114 110 146 130
35 99 89 125 110 141 129 162 143 137 181 162
50 119 108 151 134 182 167 196 174 167 219 ·197
70 151 136 192 171 234 214 251 225 216 281 254
95 182 164 232 207 284 261 304 275 264 341 311
120 210 188 269 239 330 303 352 321 308 396 362
150 240 216 300 262 381 349 406 372 356 456 419
185 273 245 341 296 436 400 463 427 409 521 480
240 321 286 400 346 515 472 546 507 485 615 569
300 367 328 458 394 594 545 629 587 56 '1 709 659
400 - - 546 467 694 634 754 689 656 852 795
500 - - 626 533 792 723 868 789 749 982 920
630 - - 720 611 904 826 1005 905 855 1138 1070
800 - - - - 1030 943 1086 1020 971 1265 1188
1000 - - - - 1154 1058 1216 1149 1079 1420 1337

Note - For rating factors-VCJri tion in ambient air temperature ref~r ta.hie Y-01
The data i tak n from BS 7( 71: 2008, Requirement ior Ele tri ill lnstllllation. IEE Wiring
Regu lations-Seventeenth Edition.
- See Table A2 for Voltage Drop.
L. I

21. Current Carrying Capacity and Voltage Drop

SINGLE - CORE PVC INSULATED NON - ARMOURED

BS 6004/BS 6346

Ambient air temperature 30°(


Conductor operating temperature 70°(

PVC PVC Copper 0.3/0.5, 0.45/0.75, 0.6/1 kV

TABLE - A2- Voltage drop

Voltage Drop (mV I A Im)

2 Cables single phase ac 3 or 4 cables three phase ac

Reference Reference Methods


Reference
C & F (clipped direct, Reference method C & F
Conduct 2 Cables Method Method
or on tray or in free air) (clipped direct, or on tray or in free air)
or cross
de A&B A&B
sectional (enclosed (enclosed Cables Cables Cables
area Cables Cables
in conduit in conduit touching, touching, spaced,
(mm
2
) or trunking) touching Spaced* or trunking) Trefoil Flat Flat
1 44 44 44 44 38 38 38 38
1.5 29 29 29 29 25 25 25 25
2.5 18 18 18 18 15 15 15 15
4 11 11 11 11 9.5 9.5 9 .5 9.5
6 7.3 7.3 7. 3 7.3 6.4 6.4 6.4 6.4'
10 4.4 4.4 4.4 4.4 3.8 3.8 3.8 3.8
16 2. 8 2.8 2.8 2.8 2.4 2.4 2.4 2.4
25 1.75 1.80 1.75 1.80 1.55 1.50 1.55 1.55
35 1.25 1.30 1.25 1.30 1.10 1.10 1 .10 1.15
50 0.93 1.00 0.95 0.97 0.85 0.82 0.84 0 .86
70 0.63 0.72 0.66 0.69 0.61 0.57 0.60 0.63
95 0.46 0 ..56 0.50 0.54 0.48 0.43 0.47 0 .51
120 0.36 0.47 0.41 0.45 0.41 0. 36 0.40 0.44
150 0.29 0.41 0.34 0.39 0. 3 6 0.30 0. 34 0.40
185 0.23 0.37 0.29 0.35 0. 32 0.26 0.31 0.36
240 0 .180 0.33 0.2 5 0.31 0.29 0.22 0.27 0.34
300 0.145 0 .31 0 .22 0 .29 0.27 0.190 0.25 0.32
400 0.105 0.29 0.20 0.27 0.25 0.175 0.24 0.31
500 0.086 0.28 0.185 0.26 0.25 0.160 0.23 0.30
630 0.068 0.27 0.175 0.25 0.24 0.150 0.22 0.29
800 0.05 3 - 0.165 0.25 - 0.145 0.22 0.29
1000 0.042 - 0.160 0.24 - 0.140 0.21 0 .28

Not -Ref r 1 ble /-0 I for ma irnum value of vollage drop in omumer in tallcition
-The cl, ta i · taken from B 7671: 008, Requirements for El 'ctri al In t, llation , IEE Wiring
R ·gulation -_ evente( nth Editi n