Paha
Paha
3 PHASE 3 PHASE
VOLTAGE VOLTAGE
INPUT INPUT
ASYM ASYM
10 20 10 20
75,0 mm
% %
5 25 5 25
3-PHASE
UPPER LOWER UPPER LOWER
SYM SYM SYM SYM
5 15 5 15 5 15 5 15
% % % %
PHASE MONITORING
E E O O
O O L
L
A N F A N F
Y F Y F
6 5 8 6 5 8 A2
FEATURES Description:
The PAHA & PAHI are 3 wire relays for sequence control and phase
• Active contact function for both phase sequences monitoring. The PAHI includes a true time delay. The PAMA & PAMI are
with two relays 4 wire relays for sequence control and phase and neutral monitoring. The
PAMI includes a true time delay.
• Detects phase sequence, phase failure, phase
The phase sequence and phase and neutral monitoring relays are designed
regeneration and phase loss in three-phase mains for applications where the sequence of a three-phase system needs to
be controlled. In addition to the sequence control the relays monitors the
• High sensitivity for the protection of installations, three-phase system for phase unbalance, and according to the selected
control gear, motors and power transformers setting, they can further monitor balanced under or over voltage, as well
as both under and over voltage. The relays work in "fail-safe" mode and
• Time delay - on and off - individually adjustable. the 35mm modules need no external power supply. If an external stable
PAHI and PAMI includes a true time delay indepen- power supply is available, the 45mm modules offer separate terminals for
the internal power.
dent of the power supply
Unbalance, due to phase angle and phase voltage deviation, is very
• Insensitive to harmonics and spikes as the detection accurately measured by measuring the inverse phase system relatively
system includes a narrow band pass filter to the main system. The method is independent of the actual balanced
voltage and perfect for the protection of three-phase motors, generators
• Adjustable set points with individual adjustments for and transformers. The measuring system is insensitive to higher harmonics
unbalanced and balanced under and over voltage and secures the relays from false triggering due to "noisy" power lines. As
settings the measuring system includes the phase angles in the measurement, it
provides full protection against regenerated phases. Balanced voltage is
measured by adding the three individual rectified phase voltages.
• Function setting with DIP-switch
Operation:
• 12 standard mains voltages covered by just 4 units Under normal phase conditions the green input LED is on and one of the
sequence sensitive relays will be energized, indicated by a yellow LED.
• LED indication of the state of input, relay and timing The yellow LED, next to the description, shows the sequence of the three-
function phase system. If there is a phase deviation beyond one of the set levels,
the failure will be detected, and the red input LED will go on. During the
set delay period the yellow timing LED for off delay will be on. At the end
of the timing period the relay will drop out and only the red input LED will
PROGRAMMABLE FEATURES stay on. If the common phase voltage drops below -40%, the relay will
drop out, even if the under voltage detection is disabled. If the phase or
the separate supply voltage is lost, the relay and all LED’s will de-energize
ACTUATOR
VOLTAGE SETTING with out delay for PAHA and PAMA. The PAHI and PAMI will be able to
TYPE
110 V
TYPE
230 V
TYPE
400 V
TYPE
460 V FUNCTION SET hold the relays for more than 6 sec.
100 V 220 V 380 V 440 V ASYM A
110 V 230 V 400 V 460 V ASYM & SYM LOW B
Application:
115 V 240 V 415 V 480 V ASYM & SYM HIGH
To prevent motors from rotating in the wrong direction and being switched
C
on to a faulty supply. Motor protection by controlling the direction of
ASYM & SYM HIGH, LOW D
rotation and on-off switching depending on supply conditions. E.g. pumps,
compressors, ventilators and refrigerators. Automatic control of phase
sequence and monitoring of phase and neutral voltages in mobile equipment
like refrigerated containers, control and distribution panels and machines
used on building sites and on service jobs.
CONNECTION DIAGRAM
35mm Rail mounting 45mm Rail Mounting
5 A1 A2 5
L1 L1
L2 L2
L3 L3
6 8 6 8 41
ADJUSTMENT
Trimpot and dipswitch adj. A
International Standards HOUSING
Directive 2002/95/EC of Rail mounting 45mm wide A4
27 January 2003 RoHS Socket 11-pin 35mm wide E3
EMC directive 89/336: Emission and EN50283:2000
CODE END C
Immunity EN61000-3-2
EN61000-3-3
Low voltage directive 73/23: Electrical Relays EN60255
L1 L2 L3
6
5 7
N L1 L2 L3 L1 L2 L3 4 8
L3 L2 L1 L1 L2 L3
L3 L2 L1 3 9
2 10
1 11
6 5 8
(A1) (N) (A2)
+ -
M
*CE up to 230V phase to phase voltage