SECTION 1: Design Criteria for the Structure
1 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
SECTION 3: Design Loads
2
Rroof.1 if AT.R 200 ft 0.600
1
else
2
if AT.R 600 ft
1
1.2 0.001 AT.R
2
1 ft
else
0.6
Ha He
FRoof.pitched tan αs 12 3.441 FRoof.arch 32 4.59
W0
QLr min augment 20 psf , max augment QL0 Rroof.1 Rroof.2 , 12 psf 12.00 psf
2 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
3.3 Wind Loads:
zg 900 ft
2
αz
15 ft
Kz.015 2.01 0.849
zg
2
αz
He
Kz.eave 2.01 0.902
zg
2
αz
Ha
Kz.apex 2.01 1.011
zg
3 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
2
Vwind lbf lbf
qz.015 0.00256 Kz.015 Kzt Kd 1 26.599
1 mph 2 2
ft ft
qz.015 1.274 kPa
2
Vwind lbf lbf
qz.eave 0.00256 Kz.eave Kzt Kd 1 28.260
1 mph 2 2
ft ft
qz.eave 1.353 kPa
3.3.1 Wind along ridge & Internal pressure positive - Ultimate Limit State
4 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
lbf
(h;2h) prR.h2.B qh Kge Cp.rR.h2.B qh GCpi 10.017
2
ft
prR.h2.B 0.48 kPa
lbf
(>2h) prR.h0.B qh Kge Cp.rR.h0.B qh GCpi 10.017
2
ft
prR.h0.B 0.48 kPa
3.3.2 Wind along ridge & Internal pressure negative - Ultimate Limit State
5 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
lbf
(h;2h) prR.h2.B qh Kge Cp.rR.h2.B qh GCpi 0.8122
2
ft
prR.h2.B 0.0389 kPa
lbf
(>2h) prR.h0.B qh Kge Cp.rR.h0.B qh GCpi 0.8122
2
ft
prR.h0.B 0.0389 kPa
3.3.3 Wind across ridge & Internal pressure positive - Ultimate Limit State
6 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
lbf
(h;2h) prW.h2.B qh Kge Cp.rW.h2.B qh GCpi 4.8009
2
ft
prW.h2.B 0.2299 kPa
lbf
(>2h) prW.h0.B qh Kge Cp.rW.h0.B qh GCpi 4.8009
2
ft
prW.h0.B 0.2299 kPa
3.3.4 Wind across ridge & Internal pressure negative - Ultimate Limit State
7 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
Leeward wall (L):
lbf
pwL qh Kge Cp.wL qh GCpi 7.3699
2
ft
pwL 0.3529 kPa
Side wall (S):
lbf
pwS qh Kge Cp.wS qh GCpi 0 17.8982
2
ft
pwS 0.857 kPa
8 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
lbf
(>2h) prL.h0.A qh Kge Cp.rL.h0.A qh GCpi 7.8045
2
ft
prL.h0.A 0.3737 kPa
9 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
ps 1.01 kPa
C1. 1.4D
10 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
C4G. 0.9D + 1.0W (3.3.4A)
C4H. 0.9D + 1.0W (3.3.4B)
11 / 12
24 Apr 2019 12:05:35 - R400-Rapid LAMS 100ft HD - Loads.sm
12 / 12