This document provides a calculation for the cooling capacity needed for a cold room. It details the stored goods, room features, heat gains from goods refrigeration, transmission, air renewal, and internal loads. The total daily cooling needs are calculated to be 374,201 kJ/day. With a 10% security margin and 20 hours of compressor operation per day, the recommended cooling capacity is 5,717 W.

Uploaded by

Jay Patel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
134 views

Cooling Capacity Calculation Printing

This document provides a calculation for the cooling capacity needed for a cold room. It details the stored goods, room features, heat gains from goods refrigeration, transmission, air renewal, and internal loads. The total daily cooling needs are calculated to be 374,201 kJ/day. With a 10% security margin and 20 hours of compressor operation per day, the recommended cooling capacity is 5,717 W.

Uploaded by

Jay Patel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

4/6/2019 Cooling capacity calculation printing

Cold room calculation

Stored goods
Storage conditions: -20ºC / RH 90%
Freezing point: -2ºC
Specific heat (PT/NT): 3.53 / 1.85 kJ/(kg·K)
Latent heat: 266.8 kJ/kg

Cold room features


Ambient conditions: 45°C / 25.5 °C WT
Cold room internal volume: 108 m³
Internal sizes: 12 m (length) x 3 m (width) x 3 m (height)
Isolation thickness: 150 mm
Heat transmission rate: 0.025 W/(m·K)

1. Goods refrigeration loads 74844 kJ/day


- Goods rotation: 2700 kg at -5ºC each 24 hours 74844 kJ/day

2. Transmission heat gain 154183 kJ/day


- Walls: 91.4 m² x 0.16 W/(m²·K) x 65 °C = 83193 kJ/day
- Roof: 38.3 m² x 0.16 W/(m²·K) x 65 °C = 34637 kJ/day
- Floor: 38.3 m² x 0.15 W/(m²·K) x 65 °C = 31802 kJ/day
- Door: 5 m² x 0.16 W/(m²·K) x 65 °C = 4551 kJ/day

3. Air renewal heat gain 73030 kJ/day


- Air renewal rate: 4.8 renewals/day x 108 m³ x 140.9 kJ/m³

4. Internal loads heat gain 72144 kJ/day


- Heaters: 135 W
- Defrosting: 217 W
- Evaporator fans: 650 W

TOTAL COOLING NEEDS 374201 kJ/day


- Security margin: +10 %
- Comperssor operation time per day: 20 h
Cooling capacity needed: 5717 W

RECOMMENDED UNIT: BSF-QF 8271

The calculation is as acurate as possible in order to assure the precision, nevertheless any responsability
derivated on the use of this tool will be declined. Version.3.0 - ©JCC 2010