Comprehnsive Review of Different Busbar Protection Schemes
Comprehnsive Review of Different Busbar Protection Schemes
2.1 INTRODUCTION
Modern electrical power system is spreaded over large geographical area with great
complexity. Power quality requirements resulting from such great complex electrical
network have motivated the improvement of fault location methods and development of
protection scheme for busbar. Busbar is a vital, often overlooked, part of the power
system. Even though faults on busbar are very rare, they can lead to disturbances & major
shutdown of power system network. Thus, protection of busbar requires highly reliable,
fast and high speed relaying scheme. With the fast changing technologies in the field of
busbar protection, new protection concepts addressing new technologies are coming to the
market. Therefore, there is an urgent need to keep track of different past and present
relaying techniques, international standards, design and service experiences of
digital/numerical relays and recent algorithmic developments taking place in the field of
busbar protection.
This chapter gives a bibliographical survey, comprehensive review of different
busbar relaying schemes and conceptual aspect of research and developments in the field
of busbar protection during the past 50 years, based on numerous published articles.
Different busbar protection techniques have been studied and a comparative evaluation of
them is undertaken with their relative advantages and disadvantages for identification of
optimum technique as applied to specific bus configuration.
2.2 BUSBAR FAULTS AND PROTECTION REQUIREMENT
Protection engineer try to implement a dedicated bus zone protection scheme from
the various schemes developed by researchers. If it is not implemented perfectly, the
clearing of bus fault will be performed by the backup protection provided to the lines
terminating at the bus. The high fault levels associated with a busbar require fast
protection. Typical fault clearing time should be less than 100 ms; with fast breakers, this
means that the measuring time should be about 20 to 30ms.
The prime requirement of the busbar protection scheme is the identification of fault
in a particular region and disconnection of circuit breakers associated with that particular
region so that healthy section of power system network remains unaffected. This
17
discriminating feature of the busbar protection scheme minimizes interruption of the plant.
Hence, it is justified that discrimination on the basis of time graded relays is not a good
choice, and hence, there is a need to develop genuine protection scheme for the busbar.
Busbar protection scheme should not operate for any external (through) fault, as
otherwise it unnecessarily trips other healthy lines connected to the bus. This is a very
important feature of the busbar protection scheme with respect to the stability of the power
system.
It is to be noted that all these requirements cannot be achieved completely by any of
the schemes without affecting the other requirements. Therefore, there is always a
compromise between many factors such as speed versus selectivity and stability versus
dependability.
Whenever bus fault occurs, it results in severe disturbances as clearance of this fault
requires tripping of all the breakers of the lines connected to the faulted bus. Moreover, the
danger caused because of unprotected bus during bus fault is found to be very severe
[110], [206]. Thus, in order to prevent hazard to the system, busbar protection scheme is
designed and implemented in such a way that unwanted tripping should not occur. By
involving bus sectionalizer and different bus arrangement, the number of circuits that must
be opened for a bus fault is minimized and hence, eliminating total interruption of power
[91]. Bus faults have been observed to be relatively rare around 8% of all faults compared
with line faults which are over 60% [195], [10], [183]. It has been observed from the
widely published literature that most of the bus faults are ground faults having 67% are
single line to ground faults, 15% are double line to ground faults and 19% are triple line to
ground faults [62].
Busbar faults can be broadly classified as:
(i) Fault due to insulation failure caused from damaged CBs or insulators
(ii) Arcing and insulator flashover caused by over voltages
(iii) Faulty handling of switching equipments especially earthing switch
(iv) Dropping off of metal parts across busbars
Thus, the protection provided must possess the following characteristics
(i) It is fast enough to minimize damage and maintain system stability
(ii) It provides correct operation during an internal fault
(iii) It maintains stability by avoiding maloperation in case of an external fault
(iv) It supervises all CTs, which provides actuating quantity to the relay in case of fault
18
2.3 CLASSIFICATION OF BUSBAR PROTECTION SCHEMES
The consolidated review of different techniques used by utilities along with their
relative merits and shortcomings are presented here. These techniques are classified in
three broad categories namely
Different techniques have been used by the utilities in order to detect faults on
busbar in power system. The schemes categorized under unit protection are:
Further, techniques used in commercial relay are sub-classified into five groups:
19
protection to clear busbar faults can be confined to radial system only. It is therefore
preferable to have a clearly defined busbar protection scheme such as unit protection
scheme which will be discussed in the next sub-section.
BUS + R1 R2 -
BUS Aux
P. T. CB-1 Line-2
AX1 A1
CT-1
R1 CB-2 TC CB-1
AX2 A2
Line-1
CT-2
TC CB-2
R1
(a) (b)
A1 & A2 are mechanical switch, AX1 & AX2 are contacts of Aux relay
TC CB is trip coil of circuit breaker
20
In case of an internal fault, contacts R1 and R2 closes simultaneously and
energizes the auxiliary relay (Aux) to trip both line circuit breakers. But the several
disadvantages of this scheme are reduction in the reliability of the scheme due to
too many series contacts, complex circuitry and requirement of careful and
periodic review.
2) Directional Blocking Scheme: Figure 2.2 shows the control circuit of the directional
blocking scheme for bus bar protection. The power circuit is same as shown in
Figure 2.1(a). In this scheme, all the tripping contacts (R1 and R2) are connected in
parallel and then to the tripping relay (Aux) whereas all the blocking contacts are
connected in parallel and then to the blocking relay (B). During an external fault,
the blocking relay (B) operates and blocks the operation of bus protection as per
requirement by opening one of its contacts B-1, which is in series with auxiliary
tripping relay. However, the main disadvantage of this scheme is its inapplicability
in large cable network where the capacitance charging current is appreciable in
comparison with minimum ground fault current.
+
R1 -
B
B-1
Aux
R2
A1
AX1 TC CB-1
A2
AX2 TC CB-2
21
Differential Protection Scheme, High Impedance Voltage Scheme, Moderately High
Impedance Scheme and Protection using Liner Couplers. Each of this method is discussed
in details below.
1) Circulating Current Differential Protection: Figure 2.3 shows the concept of
circulating current differential protection. This scheme operates on Kirchhoff’s
current law i.e. current entering the substation bus equals to the vector sum of
currents leaving the substation bus. But the main requirement of this scheme is that
the CTs should be of the same ratio or matching CTs are required. However, the
main drawback of this scheme is its maloperation because of production of error
current due to CT saturation and also due to transient DC component.
BUSBAR
Three
CT-1
CT-3
CT-2
R Pole
Relay
BUS
Operating Current (rms)
CB-1 CB-2
Tripping
CT-1 CT-2 Zone
Blocking
Zone
Restraining
Coil
Operating Coil Restraint Current (rms)
22
Application guideline for choosing a secure slope when applying percentage
differential relay for bus protection is given in [132]. Maximum security for external
faults is obtained when all CTs have the same ratio. The main advantages of this
scheme are high tolerance against substantial CT saturation, reduced requirement of
dedicated CTs and its use where comparatively high speed tripping is required. But
the most important limitation of the said scheme is that the relay may maloperate in
case of a close-in external fault due to complete saturation of CT.
3) High Impedance Voltage Scheme: To overcome the problem of spill current due to
CT saturation in case of external fault, the high impedance voltage relaying scheme,
as shown in Figure 2.5, is widely used. The effect of saturation is controlled by
keeping CT secondary & lead resistance low & by adding resistance into relay
circuit. Here, full wave bridge rectifier adds substantial resistance to that leg of
circuit. The series L-C circuit is turned to 50 Hz fundamental frequency in order to
respond only fundamental component of current and make over voltage relay
immune to DC offset and harmonics. A dedicated IEEE standard was assigned as a
guide for protective relay applications to power system buses [81], [43]. This
scheme discriminates between internal and external faults by the relative
magnitudes of the voltage across the differential junction points. The main merits of
the said scheme are stability against transient DC component due to tuned circuit,
improved CT saturation characteristics because of stabilizing resistors and faster
operating time. This scheme, however, is not free from disadvantages. The most
important ones are requirement of dedicated CTs (cost increases), maloperation of
relay in case when the secondary leakage reactance is present and inapplicability of
the scheme to re-configurable busbars.
BUS
CB-1 CB-2 CB-3
CT-1
CT-3
C
CT-2
Variable
L Resistor
O/C
R
Relay
BUS
Voltage
LC1
Differential
LC2
LC3
R
Relay
LC – Linear Coupler
25
Power System Network
CT and PT
Storage Power
Unit Supply
27
distributed between a numbers of existing DAUs imposing more computational
demand for the central unit. On the other hand, this architecture is perceived
more reliable and suits better retrofit applications.
BUS
CB CB CB CB CB CB
CT
CT
CT
CT
CU CU
Copper
(a) Fiber (b)
Figure 2.8 Block diagram of digital differential relay
Fast tripping which is an essential requirement in case of busbar faults can be
achieved primarily by low/high impedance differential protection schemes [14], [78]. Till
now, high impedance differential protection scheme is widely used due to its low cost and
simple arrangement. However, the above scheme has several disadvantages such as
requirement of dedicated CTs, high cost due to additional switchgears and unavailability
of numerical protection technology [121]. On the other hand, low impedance differential
protection scheme inherits all the features of digital/numerical protection technology and
can also be applied to different complex busbar arrangements. Kasztenny and his
colleagues [29], [28] proposed low impedance differential protection scheme that
combines percentage differential and current directional protection principles within a
frame of an adaptive algorithm controlled by a dedicated CT saturation detection module.
However, need of large number of inputs and outputs and processing power requirements
are the major shortcomings of the said scheme. These problems can be solved by using
distributed or centralized architectures [66]. But the requirement of large quantities of
specialized hardware is the main weakness of this scheme.
Thereafter, a concept of phase-segregated low impedance digital protection schemes
for medium and large voltage busbars have been proposed in 2001-2002 [26], [76]. This
concept has many benefits such as low cost, initial maturity and simplicity.
Jiali and his colleagues [77] presented a protection scheme based on distributed
principle. This scheme has distinguishing advantages over the traditional centralized
principle such as enhancement in adaptability using the information of the whole power
28
system and reduction in the possibility of a serious blackout of the whole bus due to
maloperation of the busbar protection scheme. However, the main weakness of the above
scheme is the possibility of maloperation in case of severe CT saturation. Wong et al.
[165] described a multi agent system which integrates case based and object oriented
based approaches in the development of a distributed intelligent system. Thereafter, B-Al-
Fakhari and his colleague [19] proposed a differential protection scheme for busbar and
transformer using incremental currents. But the prime limitation of this scheme is that if
CT saturation occurs in the first one or two cycles with an external fault then incremental
currents are not sufficient. Hence, operating quantity exceeds restraining quantity and
relay maloperates.
2.4.3 Performance of Busbar Protection Scheme during CT Saturation and Ratio
Mismatch
The iron core CTs are widely used in the electric power system for the protection of
busbar. These types of CTs are not linear transducers due to the characteristics of the iron
core. Different levels of saturation occur in almost all CTs depending on the magnitude of
the fault current being measured. Figure 2.9 shows a block diagram of CT saturation. The
secondary current I2, transformed from the primary current I1 by a CT, is sampled into a
discrete-time sequence of values, i2(t), by a data-acquisition module. If a sample of i2(t) is
determined within a saturation portion of the fault current waveform by the CT saturation
detection scheme, a compensated sample will be generated by a compensation algorithm.
Finally, the compensated currents are supplied to protective relays. The distorted
secondary current can be compensated based on the detection of the CT saturation period
[71].
Primary
CT
Current
Secondary
Current (I2)
Data Acquisition CT Saturation Normal Protective
(A/D) Detection Relay
i2(t)
Saturated
Current
Compensated
Sample
Current
CT Saturation
Compensation
30
elements called neurons are capable of realizing basic logic functions. The unique feature
of ANN structure can be used to estimate any continuous function.
Figure 2.10 shows the block diagram of Artificial Neural Network (ANN) based
differential relaying scheme for busbar protection. Current samples in secondary form,
acquired from the power system network are given as an input to Analog to Digital
Converter (ADC) through Signal Conditioning (SC) and Anti Aliasing Filter (AAF) block.
AAF is a low pass filter and used to remove high frequency signals. The differential
current signals are given as an input to ANN block. Depending upon nonlinearity in the
input signal, the structure of ANN can be decided. Generally, the structure of ANN
contains input layer, output layer and two or three hidden layers. The output of ANN is
given to decision logic block, which gives tripping or blocking signal.
AAF
CT Decision
Power System SC Trip
Units ANN Logic
Network Id ADC
32
CT
Id
AAF Decomposition of
Relay Fault
SC different current Trip
Logic Classification
ADC Using WPT
Digital protective relaying of transmission lines has been greatly benefited from the
development of artificial intelligence and signal processing techniques [154]. Fernandez et
al. [160] presented an overview of the wavelet transform applications in a power system,
which indicates that the use of wavelet transform in power system protection is increasing
day-by-day. Eissa [118] presented busbar protection scheme which uses Continuous
Wavelet Transform (CWT) in order to derive operating and restraining quantities. Soon
after, Mohammed [112] described differential busbar protection technique using Wavelet
Packet Transform. However, the above two schemes may maloperate in case of varying
load conditions. Thereafter, Valsan et al. [169] presented a new busbar protection
technique based on directional signal which is derived as the product of high frequency
details of branch currents and bus voltage using a Wavelet transform approach. But the
main disadvantage of this technique is that it requires voltage information which is not
always available in bus protection applications.
2.5 CONCLUSION
In this chapter an attempt is made to review most of the existing schemes of busbar
in power system networks. The chapter also covers the concepts of the different protection
schemes of busbars, with a bibliographical survey of relevant background, practical
requirements, the historical events, the present state and techniques. Comparative
evaluation of different techniques is also undertaken for identification of optimum
technique as required by specific application. The citations listed in this bibliography
provide a representative sample of current engineering thinking pertaining to next
generation busbar protection problem. This chapter is based on many research articles
published in the last 50 years and periodic bibliographic updates on this topic will be
useful as the restructuring of power system network continues to evolve. Although,
33
numbers of busbar protection schemes have been proposed so far there exists a lot of
scope for further improvement especially on the effective discrimination between in-zone
and out of zone fault. A clear consensus is presently heading towards SVM and other AI
based digital busbar protection scheme and can handle the present day complex busbar
protection problem.
34