Installation Instructions

Micro800 4-channel and 8-channel Analog


Voltage/Current Input and Output Modules

Catalog Numbers 2085-IF4, 2085-IF8, 2085-OF4


http://www.rockwellautomation.com/literature/
Cette publication est disponible en français Esta publicação está disponível em portugués
sous forme électronique (fichier PDF). Pour la como PDF. Vá ao endereço web que aparece
FR télécharger, rendez-vous sur la page Internet
PT acima para encontrar e fazer download da
indiquée ci-dessus. publicação.
Questa pubblicazione è disponibile in Italiano
in formato PDF. Per scaricarla collegarsi al sito
IT Web indicato sopra.
ZH

Diese Publikation ist als PDF auf Deutsch


verfügbar. Gehen Sie auf die oben genannte
DE Web-Adresse, um nach der Publikation zu
ZC
suchen und sie herunterzuladen.
Esta publicación está disponible en español
como PDF. Diríjase a la dirección web indicada
ES arriba para buscar y descarga esta publicación. KR

Table of Contents
Topic Page

Important User Information 2

Additional Resources 5

Overview 5

Module Description 6

Mount the Module 6

Wire the Modules 9

Specifications 9
2 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules

Important User Information


Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell
Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that
each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc.,
is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the
consequences.

SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that
dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that
surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Publication 2085-IN006C-EN-P - November 2016


Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 3

Environment and Enclosure


ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up
to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate precautions, there may be
difficulties with electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure
that is suitably designed for those specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from accessibility to live parts. The
enclosure must have suitable flame-retardant properties to prevent or minimize the spread of
flame, complying with a flame spread rating of 5VA or be approved for the application if
nonmetallic. The interior of the enclosure must be accessible only by the use of a tool.
Subsequent sections of this publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for
additional installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by enclosures.

Preventing Electrostatic Discharge


ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.

Publication 2085-IN006C-EN-P - November 2016


4 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules

North American Hazardous Location Approval


The following modules are North American Hazardous Location approved:
2085-IF4, 2085-IF8, 2085-OF4
The following information applies when operating Informations sur l’utilisation de cet équipement en
this equipment in hazardous locations: environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
use in Class I Division 2 Groups A, B, C, D, Hazardous conviennent qu'à une utilisation en environnements de Classe
Locations and nonhazardous locations only. Each product is I Division 2 Groupes A, B, C, D dangereux et non dangereux.
supplied with markings on the rating nameplate indicating Chaque produit est livré avec des marquages sur sa plaque
the hazardous location temperature code. When combining d'identification qui indiquent le code de température pour les
products within a system, the most adverse temperature environnements dangereux. Lorsque plusieurs produits sont
code (lowest "T" number) may be used to help determine the combinés dans un système, le code de température le plus
overall temperature code of the system. Combinations of défavorable (code de température le plus faible) peut être
equipment in your system are subject to investigation by the utilisé pour déterminer le code de température global du
local Authority Having Jurisdiction at the time of système. Les combinaisons d'équipements dans le système
installation. sont sujettes à inspection par les autorités locales qualifiées
au moment de l'installation.

WARNING: EXPLOSION HAZARD WARNING: RISQUE D’EXPLOSION


• Do not disconnect equipment unless • Couper le courant ou s'assurer que
power has been removed or the area is l'environnement est classé non dangereux
known to be nonhazardous. avant de débrancher l'équipement.
• Do not disconnect connections to this • Couper le courant ou s'assurer que
equipment unless power has been l'environnement est classé non dangereux
removed or the area is known to be avant de débrancher les connecteurs.
nonhazardous. Secure any external Fixer tous les connecteurs externes reliés
connections that mate to this à cet équipement à l'aide de vis, loquets
equipment by using screws, sliding coulissants, connecteurs filetés ou autres
latches, threaded connectors, or other moyens fournis avec ce produit.
means provided with this product. • La substitution de composants peut
• Substitution of components may impair rendre cet équipement inadapté à une
suitability for Class I, Division 2. utilisation en environnement de Classe I,
• If this product contains batteries, they Division 2.
must only be changed in an area known • S'assurer que l'environnement est classé
to be nonhazardous. non dangereux avant de changer les piles.

WARNING: When you connect or disconnect the Removable Terminal Block (RTB) with field side
power applied, an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be
mounted in a suitable enclosure with proper wiring method that complies with the governing
electrical codes.
WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc
can occur. This could cause an explosion in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
WARNING: Do not connect directly to line voltage. Line voltage must be supplied by a suitable,
approved isolating transformer or power supply having short circuit capacity not exceeding
100 VA maximum or equivalent.
WARNING: If you insert or remove the module while backplane power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be sure that power is
removed before proceeding.
WARNING: Do not unscrew the RTB hold down screws and remove the RTB while power is on.
This could cause an explosion in hazardous location installations. Be sure that power is removed
before proceeding.

Publication 2085-IN006C-EN-P - November 2016


Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 5

Additional Resources
Resource Description
Micro830 and Micro850 Programmable A detailed description of how to install and use a Micro850
Controller User Manual, Programmable Controller.
publication 2080-UM002
Micro800 Bus Terminator Installation Information on installing the bus terminator module.
Instructions, publication 2085-IN002
Industrial Automation Wiring and More information on proper wiring and grounding techniques.
Grounding Guidelines, publication 1770-4.1

If you would like a manual, you can:


• download a free electronic version from the Internet:
http://www.rockwellautomation.com/literature/.
• purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative

Overview
The Micro800™ expansion I/O is a modular I/O that complements and extends the capabilities
of Micro850™ controllers. These expansion I/O modules interface with Micro850 controllers
using an I/O expansion port.
I/O Module Overview
2085-IF4 2085-OF4 2

1
6
6

5 1 5 1
45315 45316 45317

Front view Front view Left side view

Publication 2085-IN006C-EN-P - November 2016


6 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules

2085-IF8 2

3
6 3

4
3

5
1 1
45318 45319
Front view Right top view
Module Description
Description Description

1 Mounting screw hole / mounting foot 4 Module interconnect latch

2 Removable Terminal Block (RTB) 5 DIN rail mounting latch

3 RTB hold down screws 6 I/O status LED

This equipment is sensitive to electrostatic discharge (ESD).


Follow ESD prevention guidelines when handling this equipment.

ATTENTION: To comply with UL restrictions, this equipment must be powered from a source
compliant with the following:
Class 2 or Limited Voltage/Current.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

Mount the Module


For more information on proper grounding guidelines, see the Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.

Publication 2085-IN006C-EN-P - November 2016


Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 7

Module Spacing
Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown.
Mounting Dimensions and DIN Rail Mounting
150 mm (5.91 in.) 44.5 mm (1.75 in.)

90 mm 28 mm (1.1 in.)
(3.54 in.)

Bus terminator

87 mm (3.42 in.)

Micro850 Controller 45306


2085-IF8 2085-IF4 or 2085-OF4
Mounting dimensions do not include mounting feet or DIN rail latches.

DIN Rail Mounting


The module can be mounted using the following DIN rails: 35 x 7.5 mm x 1 mm
(EN 50 022 - 35 x 7.5).
TIP For environments with greater vibration and shock concerns, use the panel mounting
method, instead of DIN rail mounting.

ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials
(for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result
in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every
200 mm (7.8 in.) and use end-anchors appropriately.

Before mounting the module on a DIN rail, use a flat-blade screwdriver in the DIN rail latch and
pry it downwards until it is in the unlatched position.
1. Hook the top of the DIN rail mounting area of the module onto the DIN rail, and then
press the bottom until the module snaps onto the DIN rail.

2. Push the DIN rail latch back into the latched position.
Use DIN rail end anchors (Allen-Bradley part number 1492-EAJ35 or 1492-EAHJ35)
for vibration or shock environments.

To remove your module from the DIN rail, pry the DIN rail latch downwards until it is in the
unlatched position.

Publication 2085-IN006C-EN-P - November 2016


8 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules

Panel Mounting
The preferred mounting method is to use two M4 (#8) per module. Hole spacing tolerance:
±0.4 mm (0.016 in.). For mounting dimensions, refer to Micro830 and Micro850
Programmable Controller User Manual, publication 2080-UM002.
Follow these steps to install your module using mounting screws.
1. Place the module next to the controller against the panel where you are mounting it.
Make sure the controller and module are spaced properly.

2. Mark drilling holes through the mounting screw holes and mounting feet then remove
the module.

3. Drill the holes at the markings, then replace the module and mount it.
Leave the protective debris strip in place until you are finished wiring the module and
any other devices.

System Assembly
The Micro800 expansion I/O module is attached to the controller or another I/O module by
means of interconnecting latches and hooks, as well as the bus connector. The Micro850
controller and expansion I/O modules must terminate with a 2085-ECR Bus
Terminator module.
Be sure to lock the module interconnect latches and tighten the RTB hold down screws before
applying power to the module.
For installation of the 2085-ECR module, refer to Micro800 Bus Terminator Module
Installation Instructions, publication 2085-IN002.

ATTENTION: Failure to connect a bus terminator module to the last expansion I/O module will
result in a controller hard fault.

Field Wiring Connections


In solid-state control systems, grounding and wire routing helps limit the effects of noise due to
electromagnetic interference (EMI).

ATTENTION: Do not wire more than 2 conductors on any single terminal.

Publication 2085-IN006C-EN-P - November 2016


Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 9

ATTENTION: To comply with UL restrictions, this equipment must be powered from a source
compliant with the following:
Class 2 or Limited Voltage/Current.

Wire the Modules


Included with your 2085-IF4 or 2085-OF4 module is a single 12-pin Removable Terminal
Blocks (RTB). Included with your 2085-IF8 module are two 12-pin RTB. Basic wiring of your
module is shown below.
Basic Wiring to the 2085-IF4, 2085-IF8, 2085-OF4 Modules
2085-IF4 2085-OF4 2085-IF8
CI-0 CO-0 CI-0 CI-4
Current Current Current Current
VI-0 transmitter
VO-0 load
VI-0 transmitter VI-4 transmitter

COM0 COM0 COM0 COM4


Shielded cable Shielded cable Shielded cable Shielded cable

CI-1 CO-1 CI-1 CI-5

VI-1 VO-1 VI-1 VI-5


Voltage Voltage Voltage Voltage
transmitter load transmitter transmitter
COM1 COM1 COM1 COM5
Shielded cable Shielded cable Shielded cable Shielded cable

CI-2 CO-2 CI-2 CI-6


Current Current Current
VI-2 transmitter VO-2 VI-2 transmitter VI-6 transmitter
Voltage
load
COM2 COM2 COM2 COM6
Shielded cable Shielded cable Shielded cable Shielded cable

CI-3 CO-3 CI-3 CI-7


Current
VI-3 VO-3 load VI-3 Voltage
VI-7 Voltage
Voltage
transmitter transmitter transmitter

COM3 COM3 COM3 COM7


Shielded cable Shielded cable Shielded cable
Shielded cable

45320 45321 45322


Terminal Block 1 Terminal Block 2

Specifications
General Specifications
Attribute 2085-IF4 2085-OF4 2085-IF8

Number of I/O 4 8

Dimensions 28 x 90 x 87 mm 44.5 x 90 x 87 mm
HxWxD (1.1 x 3.54 x 3.42 in.) (1.75 x 3.54 x 3.42 in.)

Shipping weight, approx. 140 g (4.93 oz) 220 g (7.76 oz)

Bus current draw, max 5V DC, 100 mA 5V DC, 160 mA 5V DC, 110 mA
24V DC, 50 mA 24V DC, 120 mA 24V DC, 50 mA

Wire size
Min Max
2
Solid 0.34 mm (22 AWG) 2.5 mm2 (14 AWG) Copper wire rated @
90 °C (194 °F ), or greater,
Stranded 0.20 mm2 (22 AWG) 2.5 mm2 (14 AWG) 1.2 mm (3/64 in.)
insulation max

Publication 2085-IN006C-EN-P - November 2016


10 Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules

General Specifications
Attribute 2085-IF4 2085-OF4 2085-IF8

Wiring category(1) 2 – on signal ports

Wire type Shielded

Terminal screw torque 0.5…0.6 Nm


(4.4…5.3 lb-in.)(2)

Power dissipation, total 1.7 W 3.7 W 1.75 W

Enclosure type rating None (open-style)

Status indicators 1 green health indicator 1 green health indicator 1 green health indicator
4 red error indicator 8 red error indicators

Isolation voltage 50V (continuous), Reinforced Insulation Type, channel to system.


Type tested @ 720V DC for 60 s

North American temp code T4

(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.

(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

Input Specifications – 2085-IF4 and 2085-IF8


Attribute 2085-IF4 2085-IF8

Number of inputs 4 8

Resolution 14 bits (13 bits plus sign bit)


Voltage 1.28 mV/cnt unipolar; 1.28 mV/cnt bipolar
Current 1.28 A/cnt

Data format Left justified, 16 bit 2 s complement

Conversion type SAR

Update rate <2 ms per enabled channel without 50 Hz/60 Hz rejection, <8 ms for all channel
8 ms with 50 Hz/60 Hz rejection

Step response time 4…60 ms without 50Hz/60 Hz rejection – depends on number of enabled channel and
up to 63% filter setting
600 ms with 50 Hz/60 Hz rejection

Input current terminal, 4…20 mA (default)


user configurable 0…20 mA

Input voltage terminal, 10V


user configurable 0…10V

Input impedence Voltage terminal >1 M


Current terminal <100 

Absolute accuracy 0.10% Full Scale @ 25 C

Accuracy drift with temp Voltage terminal – 0.00428 % Full Scale/C


Current terminal – 0.00407 % Full Scale/C

Calibration required Factory calibrated. No customer calibration supported.

Overload, max. 30V continuous or 32 mA continuous, one channel at a time.

Channel diagnostics Over and under range or open circuit condition by bit reporting

Publication 2085-IN006C-EN-P - November 2016


Micro800 4-channel and 8-channel Analog Voltage/Current Input and Output Modules 11

Output Specifications – 2085-OF4


Attribute 2085-OF4

Number of outputs 4

Resolution 12 bits unipolar; 11 bits plus sign bipolar


Voltage 2.56 mV/cnt unipolar; 5.13 mV/cnt bipolar
Current 5.13 A/cnt

Data format Left justified, 16 bit 2s complement

Step response time up to 63% 2 ms

Conversion rate, max 2 ms per channel

Output current terminal, 0 mA output until module is configured


user configurable 4…20 mA (default)
0…20 mA

Output voltage terminal, 10V


user configurable 0…10V

Current load on voltage output, 3 mA


max

Absolute accuracy
Voltage terminal 0.133 % Full Scale @ 25 C or better
Current terminal 0.425 % Full Scale @ 25 C or better

Accuracy drift with temp Voltage terminal – 0.0045 % Full Scale/C


Current terminal – 0.0069 % Full Scale/C

Resistive load on mA output 15…500  @ 24V DC

Environmental Specifications
Attribute Value

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),


IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)

Temperature, surrounding air, max 65 °C (149 °F)

Temperature, non-operating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),


IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):


5…95% non-condensing

Vibration IEC 60068-2-6 (Test Fc, Operating):


2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):


25 g

Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):


25 g – for DIN rail mount
35 g – for panel mount

Emissions CISPR 11
Group 1, Class A

Publication 2085-IN006C-EN-P - November 2016


Environmental Specifications
Attribute Value

ESD immunity IEC 61000-4-2:


6 kV contact discharges
8 kV air discharges

Radiated RF immunity IEC 61000-4-3:


10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4:


±2 kV @ 5 kHz on signal ports

Surge transient immunity IEC 61000-4-5:


±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF immunity IEC 61000-4-6:


10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications
Certification (when Value
product is marked)(1)

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.


See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and
Canada. See UL File E334470

CE European Union 2014/30/EU EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:


Article 58-2 of Radio Waves Act, Clause 3

EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation

(1)
See the Product Certification link athttp://www.rockwellautomation.com/products/certification/ for Declaration of Conformity, Certificates, and
other certification details.

Allen-Bradley, Rockwell Automation, Micro800 and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Automation maintains current product environmental information on its website at


http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page

Publication 2085-IN006C-EN-P - November 2016 PN-396504


Supersedes Publication 2085-IN006B-EN-P - December 2012 Copyright © 2016 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.